| Plan Review Notes For Permit 05091456 |
| Permit Number |
05091456 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-10 00:00:00 | PLAN DENIED | | | 1) PLEASE REFER TO TABLE 403.3 2001 | | | FBC(M).PRIVIT GARAGE. | | | 2) PLEASE PROVIDE TYPE OF METRIALS USED | | | FOR CONDENSER WATER PIPING ON PLANS. | | | 3) PLEASE REFER TO SECTION 610.1.ABC.3.7 | | | FLORIDA ENERGY CODE 2001 MECHANICAL | | | CLOSET. | | | 4) ALL DOORS FOR MECHANICAL CLOSETS | | | SHALL BE NOMCOMBUSTIBLE SECTION | | | 602.2.1 METERIALS EXPOSED WITHIN | | | PLENUMS. | | | 5) PLEASE SUBMIT A COPEY OF | | | MANUFACTURERS INSTRUCTIONS FOR AHU, | | | RTU,CCC TOWERS,AND CW.PUMPS. | | | 6) PLEASE REFER TO SECTION 306.1 FBC(M) | | | CLEARANCES FOR MAINTENANCE AND | | | REPLACEMENT. ON AHU. | | | 7) PLEASE REFER TO SECTION 307.2.3 | | | FBC(M) 2001 AUXILIARY DRAIN PANS. | | | 8) PLEASE PROVIDE FIRE STOP DETAILS | | | FOR CONDENSER WATER PIPING ON | | | MECHANICAL PLANS. | | | 9) PLEASE INDECATE ON PLANS WITCH RTU. | | | IS NUMBER TWO. | | | 10) PLEASE SUBMIT DETAIL ON AHU ON PLANS | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|