2006-01-10 00:00:00PLAN DENIED
 1) PLEASE REFER TO TABLE 403.3 2001
 FBC(M).PRIVIT GARAGE.
 2) PLEASE PROVIDE TYPE OF METRIALS USED
 FOR CONDENSER WATER PIPING ON PLANS.
 3) PLEASE REFER TO SECTION 610.1.ABC.3.7
 FLORIDA ENERGY CODE 2001 MECHANICAL
 CLOSET.
 4) ALL DOORS FOR MECHANICAL CLOSETS
 SHALL BE NOMCOMBUSTIBLE SECTION
 602.2.1 METERIALS EXPOSED WITHIN
 PLENUMS.
 5) PLEASE SUBMIT A COPEY OF
 MANUFACTURERS INSTRUCTIONS FOR AHU,
 RTU,CCC TOWERS,AND CW.PUMPS.
 6) PLEASE REFER TO SECTION 306.1 FBC(M)
 CLEARANCES FOR MAINTENANCE AND
 REPLACEMENT. ON AHU.
 7) PLEASE REFER TO SECTION 307.2.3
 FBC(M) 2001 AUXILIARY DRAIN PANS.
 8) PLEASE PROVIDE FIRE STOP DETAILS
 FOR CONDENSER WATER PIPING ON
 MECHANICAL PLANS.
 9) PLEASE INDECATE ON PLANS WITCH RTU.
 IS NUMBER TWO.
 10) PLEASE SUBMIT DETAIL ON AHU ON PLANS