Plan Review Notes
Plan Review Notes For Permit 05091456
Permit Number 05091456
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-12-21 00:00:00******DENIED******
  
 BUILDING #5
  
 1) NFPA 101, 2003 EDITION SHALL BE
 REFERENCED AFTER JAN. 1, 2005.
  
 2) PERMIT APPLICATION INDICATES 117
 UNITS AND SHT A-002 SHOWS 114. PLEASE
 CORRULATE.
  
 3) DO TURN AROUNDS MEET THE THE 50'
 RADIUS REQUIREMENTS OF NFPA 1 ?
  
 4) PARKING GARAGE TO MEET SEPARATION AND
 ALL OTHER REQUIREMENTS IN ACCORDANCE
 WITH FBC AND NFPA 88A.
  
 5) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 6) PLEASE ILLUSTRATE THE HEIGHT OF THE
 BUILDING. HIGHRISE?
  
 7) STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 8) PLEASE REVIEW ALL DOOR SWINGS THAT
 SERVE AREA WITH OCCUPANT LOADS > 50.
  
 9) THE DOORS LEADING FROM THE POOL AREA
 TO THE CORRIDORS SWING AGAINST THE
 DIRECTION OF TRAVEL BASED ON OCCUPANT
 LOADS GREATER THAN 50.
  
 10) THE LOBBY ENTRANCE DOORS SWING
 AGAINST THE DIRECTION OF TRAVEL.
  
 11) PLEASE INDICATE THE TYPE AND
 QUANTITY OF STORAGE PLANNED FOR POOL
 EQUIPMENT AREA.
  
 12) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
 13) PLEASE PROVIDE ADDITIONAL
 INFORMATION ON TYPE OF BOILERS PLANNED.
  
 14) 2A-10B,C RATED FIRE EXTINGUISHERS
 ARE REQUIRED.
  
 15) PLEASE PROVIDE MANUFACTURER SPEC
 SHEETS FOR FABRIC AWNINGS.
  
 16) PLEASE INDICATE THE INTERIOR FINISH
 CLASSIFICATION OF WALLS AND CEILINGS IN
 TERMS OF CLASS A,B, OR C.
  
 17) AN ADDRESS IS REQUIRED FOR BUILDING,
 AND SHALL BE A MINIMUM OF 3" IN HEIGHT
 AND CONTRASTING TO BACKGROUND.
  
 18) WILL CARD READING DEVICES IMPACT
 REQUIRED EXITING?
  
 19) ELEVATORS TO COMPLY WITH ASME A
 17.1.
  
 20) WARNING SIGNS REQUIRED IN ELEVATOR
 LOBBIES.
  
 21) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, DUCT SMOKE DETECTORS SHALL
 CAUSE A GENERAL FIRE ALARM WHEN
 ACTIVATED.
  
 22) EXITS SIGNS TO BE MOUNTED AT
 DISTANCES NOT TO EXCEED 100'.
  
 23) HOW WILL OCCUPANT NOTIFICATION OCCUR
 IN REGARDS TO CO SENSORS?
  
 24) PLEASE REVIEW ALL ELECTRICAL SHTS
 AND ARRANGE EXIT LIGHT LOCATIONS TO MEET
 THE MINIMUM 100' DISTANCE REQUIREMENT.
  
 25) COOLING TOWERS TO COMPLY WITH NFPA
 214.
  
 26) FIRE ALARM SYSTEM TO BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
 DOCUMENTATION SHALL BE AVAILABLE AT THE
 TIME OF FIRE ALARM FINAL.
  
 27) FIRE ALARM SYSTEM TO BE CLASS A,
 STYLE D OR FULLY ADDRESSABLE.
  
 28) PLANS DON'T SHOW SMOKE DETECTORS IN
 COMMON AREA CORRIDORS. PLEASE MAKE
 CORRECTION.
  
 29) ARE AUDIBLE DEVICES PLANNED FOR
 LIVING UNITS?
  
 30) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 31) FIRE PUMP TO COMPLY WITH NFPA 20,
 2003 EDITION.
  
 32) SEPARATE SHOP DRAWING, PERMIT AND
 MANUFACTURER SPEC SHEETS REQUIRED FOR
 FIRE PUMP.
  
 33) A 1000 GPM FIRE PUMP IS PROPOSED.
 PLEASE PROVIDE DETAILS FROM MEETING HELD
 WITH CITY FIRE MARSHAL AND WHAT
 ARRANGEMENT HAS BEEN ACCEPTED BY THIS
 OFFICE. PLEASE INDICATE WHAT BUILDINGS
 WILL BE SUPPLIED BY FIRE PUMP.
  
 34) FIRE DEPARTMENT VALVES ON STANDPIPES
 ARE REQUIRED TO BE 2 1/2" TO 1 1/2"
 REDUCER WITH CHAIN.
  
 35) IN ADDITION TO ELECTRONIC
 SUPERVISION, DOUBLE CHECK DETECTOR
 ASSEMBLY SHALL BE SECURED WITH LOCKAND
 CHAIN.
  
 36) NO CUTTING OR WELDING OPERATIONS TO
 OCCUR WITHOUT APPROVAL OF BUREAU OF FIRE
 PREVENTION AND COMPLIANCE WITH NFPA 51B.
  
 37) LOCKING KNOX BOX CAP REQUIRED ON
 FIRE DEPARTMENT CONNECTION.
  
 38) FA SHEETS ILLUSTRATE FIRE PUMP ROOM
 AND A SHEETS SHOW ANOTHER LOCATION.
 PLEASE EXPLAIN.
  
 39) FIRE ALARM SHAEETS DON'T SHOW SMOKE
 DETECTORS IN ELECTRICAL ROOMS, FIRE PUMP
 ROOM, CATV ROOM, MAIL ROOM ETC.
  
 40) FS SHT 0.1 REFERENCES NFPA 13R. NFPA
 13 SHALL BE USED FOR BUILDINGS GREATER
 THAN 4 STORIES IN HEIGHT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  