| 2005-12-21 00:00:00 | ******DENIED****** |
| | |
| | BUILDING #5 |
| | |
| | 1) NFPA 101, 2003 EDITION SHALL BE |
| | REFERENCED AFTER JAN. 1, 2005. |
| | |
| | 2) PERMIT APPLICATION INDICATES 117 |
| | UNITS AND SHT A-002 SHOWS 114. PLEASE |
| | CORRULATE. |
| | |
| | 3) DO TURN AROUNDS MEET THE THE 50' |
| | RADIUS REQUIREMENTS OF NFPA 1 ? |
| | |
| | 4) PARKING GARAGE TO MEET SEPARATION AND |
| | ALL OTHER REQUIREMENTS IN ACCORDANCE |
| | WITH FBC AND NFPA 88A. |
| | |
| | 5) WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| | TO, DURING AND AFTER CONSTRUCTION. |
| | |
| | 6) PLEASE ILLUSTRATE THE HEIGHT OF THE |
| | BUILDING. HIGHRISE? |
| | |
| | 7) STAIRS ARE TO BE KEPT UP WITH |
| | CONSTRUCTION. |
| | |
| | 8) PLEASE REVIEW ALL DOOR SWINGS THAT |
| | SERVE AREA WITH OCCUPANT LOADS > 50. |
| | |
| | 9) THE DOORS LEADING FROM THE POOL AREA |
| | TO THE CORRIDORS SWING AGAINST THE |
| | DIRECTION OF TRAVEL BASED ON OCCUPANT |
| | LOADS GREATER THAN 50. |
| | |
| | 10) THE LOBBY ENTRANCE DOORS SWING |
| | AGAINST THE DIRECTION OF TRAVEL. |
| | |
| | 11) PLEASE INDICATE THE TYPE AND |
| | QUANTITY OF STORAGE PLANNED FOR POOL |
| | EQUIPMENT AREA. |
| | |
| | 12) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | REQUIREMENT FOR HANDRAILS AND GUARDS. |
| | |
| | 13) PLEASE PROVIDE ADDITIONAL |
| | INFORMATION ON TYPE OF BOILERS PLANNED. |
| | |
| | 14) 2A-10B,C RATED FIRE EXTINGUISHERS |
| | ARE REQUIRED. |
| | |
| | 15) PLEASE PROVIDE MANUFACTURER SPEC |
| | SHEETS FOR FABRIC AWNINGS. |
| | |
| | 16) PLEASE INDICATE THE INTERIOR FINISH |
| | CLASSIFICATION OF WALLS AND CEILINGS IN |
| | TERMS OF CLASS A,B, OR C. |
| | |
| | 17) AN ADDRESS IS REQUIRED FOR BUILDING, |
| | AND SHALL BE A MINIMUM OF 3" IN HEIGHT |
| | AND CONTRASTING TO BACKGROUND. |
| | |
| | 18) WILL CARD READING DEVICES IMPACT |
| | REQUIRED EXITING? |
| | |
| | 19) ELEVATORS TO COMPLY WITH ASME A |
| | 17.1. |
| | |
| | 20) WARNING SIGNS REQUIRED IN ELEVATOR |
| | LOBBIES. |
| | |
| | 21) IN ACCORDANCE WITH LOCAL |
| | REQUIREMENTS, DUCT SMOKE DETECTORS SHALL |
| | CAUSE A GENERAL FIRE ALARM WHEN |
| | ACTIVATED. |
| | |
| | 22) EXITS SIGNS TO BE MOUNTED AT |
| | DISTANCES NOT TO EXCEED 100'. |
| | |
| | 23) HOW WILL OCCUPANT NOTIFICATION OCCUR |
| | IN REGARDS TO CO SENSORS? |
| | |
| | 24) PLEASE REVIEW ALL ELECTRICAL SHTS |
| | AND ARRANGE EXIT LIGHT LOCATIONS TO MEET |
| | THE MINIMUM 100' DISTANCE REQUIREMENT. |
| | |
| | 25) COOLING TOWERS TO COMPLY WITH NFPA |
| | 214. |
| | |
| | 26) FIRE ALARM SYSTEM TO BE UL CERTIFIED |
| | FOR CENTRAL STATION SERVICE. |
| | DOCUMENTATION SHALL BE AVAILABLE AT THE |
| | TIME OF FIRE ALARM FINAL. |
| | |
| | 27) FIRE ALARM SYSTEM TO BE CLASS A, |
| | STYLE D OR FULLY ADDRESSABLE. |
| | |
| | 28) PLANS DON'T SHOW SMOKE DETECTORS IN |
| | COMMON AREA CORRIDORS. PLEASE MAKE |
| | CORRECTION. |
| | |
| | 29) ARE AUDIBLE DEVICES PLANNED FOR |
| | LIVING UNITS? |
| | |
| | 30) SEPARATE SHOP DRAWINGS AND PERMITS |
| | REQUIRED FOR FIRE SPRINKLER AND FIRE |
| | ALARM SYSTEMS. |
| | |
| | 31) FIRE PUMP TO COMPLY WITH NFPA 20, |
| | 2003 EDITION. |
| | |
| | 32) SEPARATE SHOP DRAWING, PERMIT AND |
| | MANUFACTURER SPEC SHEETS REQUIRED FOR |
| | FIRE PUMP. |
| | |
| | 33) A 1000 GPM FIRE PUMP IS PROPOSED. |
| | PLEASE PROVIDE DETAILS FROM MEETING HELD |
| | WITH CITY FIRE MARSHAL AND WHAT |
| | ARRANGEMENT HAS BEEN ACCEPTED BY THIS |
| | OFFICE. PLEASE INDICATE WHAT BUILDINGS |
| | WILL BE SUPPLIED BY FIRE PUMP. |
| | |
| | 34) FIRE DEPARTMENT VALVES ON STANDPIPES |
| | ARE REQUIRED TO BE 2 1/2" TO 1 1/2" |
| | REDUCER WITH CHAIN. |
| | |
| | 35) IN ADDITION TO ELECTRONIC |
| | SUPERVISION, DOUBLE CHECK DETECTOR |
| | ASSEMBLY SHALL BE SECURED WITH LOCKAND |
| | CHAIN. |
| | |
| | 36) NO CUTTING OR WELDING OPERATIONS TO |
| | OCCUR WITHOUT APPROVAL OF BUREAU OF FIRE |
| | PREVENTION AND COMPLIANCE WITH NFPA 51B. |
| | |
| | 37) LOCKING KNOX BOX CAP REQUIRED ON |
| | FIRE DEPARTMENT CONNECTION. |
| | |
| | 38) FA SHEETS ILLUSTRATE FIRE PUMP ROOM |
| | AND A SHEETS SHOW ANOTHER LOCATION. |
| | PLEASE EXPLAIN. |
| | |
| | 39) FIRE ALARM SHAEETS DON'T SHOW SMOKE |
| | DETECTORS IN ELECTRICAL ROOMS, FIRE PUMP |
| | ROOM, CATV ROOM, MAIL ROOM ETC. |
| | |
| | 40) FS SHT 0.1 REFERENCES NFPA 13R. NFPA |
| | 13 SHALL BE USED FOR BUILDINGS GREATER |
| | THAN 4 STORIES IN HEIGHT. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |