| Plan Review Notes For Permit 05091455 |
| Permit Number |
05091455 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-08-11 00:00:00 | DENIED: | | | ORIGINAL REVIEW BY HAROLD MOSER DATED | | | 11-14-06. | | | | | | COMMENT 1:OKAY | | | COMMENT 2:PLEASE INDICATE THE RETURN | | | AIR SIZES TO P/U 1 & 2.PLAN INDICATES | | | A R/A PLENUM BOX AS 26" X 18".PLEASE | | | CLARIFY DUCT SIZE FROM PLENUM BOX TO R/A | | | GRILLE.WILL THE DUCTS BE THE SAME SIZE | | | AS THE "NECK SIZE" AS SHOWN ON THE AIR | | | DISTRIBUTION SCHEDULE? | | | | | | COMMENT 3:SEE COMMENT 2. | | | | | | ***************NEW COMMENT************** | | | COMMENT 4:ENGINEER'S SIGNATURE ON | | | PLAN SHEET M-1 IS A PHOTOCOPY WHICH IS | | | NOT ACCEPTABLE PER FS 471.025 & FAC | | | 61G15-23. | | | | | | COMMENT 5:ADDTIONAL PERMIT IS REQUIRED | | | FOR ANY NEW WALK-IN COOLERS OR HOODS. | | | PLEASE PROVIDE PLANS & MANUFACTURER'S | | | SUBMITTAL DATA WITH PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719 OR | | | E-MAIL [email protected]. | | | |
|