Plan Review Notes
Plan Review Notes For Permit 05091455
Permit Number 05091455
Review Stop E
Sequence Number 2
Notes
Date Text
2006-07-23 00:00:00********* UNSAT 2ND REVIEW **********
  
 ** PLEASE SEE ALL NOTES FROM PREVIOUS
 REVIEW.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW WITH
 FUTHER DETAIL ADDED TO EACH NOTE TO HELP
 PROJECT ALONG.
 ** PLEASE ALSO SEE NEW NOTE ADDED.
  
 **IMPORTANT**
 NOTES FROM MULTIPLE REVIEWERS IN
 PREVIOUS REVIEW INCLUDING ELECTRICAL
 REQUESTED FOR ALL OLD/VOIDED SHEETS TO
 BE COMPLETELY "REMOVED" FROM SETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ALSO MENTIONS ONLY TO SUBMIT "ONE" COPY
 OF THE OLD /VOIDED SHEETS SEPARATELY FOR
 REFERENCE.NONE OF THIS WAS DONE.
 PLEASE DO SO BEFORE RESUBMITTING PLANS
 FOR THE NEXT REVIEW.
  
 ***********************************
  
 1)NOTE: NO, PLEASE SEE NUMEROUS PAGES
 ARE STILL CONTAIN A RAISED SEAL OF
 PHOTO-COPIED SIGNATURES. PLEASE SEE THAT
 SOME SHEETS WERE DONE NEW , HOWEVER THE
 MECHANICAL WERE NOT DONE AT ALL AND MANY
 OF THE ELECTRICAL SHEETS ARE STILL THE
 SAME FROM PREVIOUS REVIEW.
 THE PREVIOUS REVIEW NOTE MENTIONED THIS
 WAS REQUIRED FOR ALL M>E>P SHEETS
 WHETHER OR NOT COMMENT WAS MADE BY OTHER
 REVIEWER(S). PLEASE KNOW, ONE SET OF MEP
 PLANS FROM BOTH HAVE NOW BEEN RETAINED.
 PLEASE SEENEW COMMENT AT THE END OF
 REVIEW.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE ALL M
 SEALED PHOTCOPIES OF ENGINEER'S ORIGINAL
 SIGNATURE. PLEASE SEE FS 471.025 AND FAC
 61G15-23 WHICH REQUIRES THE ENGINEER TO
 SIGN, DATE WITH AN "ORIGINAL" SIGNATURE.
 THIS IS REQUIRED OF ALL TRADES AND FOR
 ALL SHEETS WHETHER OR NOT THE COMMENT IS
 MADE BY OTHER REVIEWER(S),
 PLEASE KNOW, ONE COPY MAY BE RETAINED
 FOR POSSIBLE REVIEW BY FBPE'S, PLEASE
 MAKE CORRECTIONS.
  
 2)NOTE: NO, PLEASE SEE MANY SHEETS ARE
 THE SAME FROM THE PREVIOUS REVIEW AND
 NEW SHEETS ARE STILL MISSING THE
 REQUIRED INFORMATION ON SAID TITLE
 BLOCKS.
 PLEASE SEE MISSING PRINTED NAME AND
 LICENSE NUMBER FOR THE ENGINEER OF
 RECORD.
 PLEASE SEE THE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED.
 PLEASE SEEMISSING THE PRINTED LICENSE
 NUMBER OF THE ARCHITECT ON THE SHEETS
 DONE BY THE ARCHITECTURAL SHEETS.
 PLEASE SEE FLORIDA ADMINISTRATIVE
 CODES;61G1-16.004, 61G15-23.002 AND
 FLORIDA STATUES 471.023
 ** PLANS ARE BEING RETAINED**
  
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING TITLE
 BLOCK/TITLE BLOCK INFORMATION WHICH IS
 REQUIRED UNDER FLORIDA ADMINISTRATIVE
 CODE (FAC) 61G15-23.002.
 PLEASE SEE MISSING PRINTED NAME AND
 LICENSE # OF PE.
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER.
 PLEASE SEE OTHER INFORMATION ETC AS
 LISTED.
 PLEASE KNOW, THIS INFORMATION IS ALSO
 REQUIRED FOR ALL SHEETS AND FOR ALL
 TRADES.
  
 3)NOTE:NO, PLEASE SEE SHEET E-3 WHICH
 REPLACED OLD SHEET 3 IS COMPLETELY
 DIFFERENT AND NO LIGHTING IS SHOWN??
 WHERE IS THE LIGHTING ?
 PLEASE SEE PREVIOUS NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 4)NOTE: NO, NOT DONE. SMAE SHEET.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3,230.42 ETC.
 (LIGHTING ETC)
  
 5)NOTE: NO.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 2002 NEC 210.8B3,
 WHICH REQUIRES ALL 15 AND 20A 120V
 CIRCUITS/DEVICES LOCATED IN KITCHEN
 AREAS TO BE GFI/GFI PROTECTED.
  
  
 ********* NEW NOTES ************
  
 6) NOTE: PLEASE SEE NEW SHEETS DO NOT
 CONTAIN ANY REVISION NOTED IN TITLE
 BLOCKS FOR LOCATIONS OF ANY POSSIBLE
 CHANGES. PLEASE KNOW, ALL REV'S SHOULD
 BE IDENTIFIED BY CLOUDS/TRIANGLES AND
 REVISED SHEET DATES ETC SHOUDL CORRELATE
 IN TITLE BLOCKS.
 IT IS UNCLEAR WHAT CHANGES WERE MADE AS
 SOME OF THE NEW SHEETS ARE NOW
 COMPLETELY DIFFERENT FROM THE SAME
 SHEETS PERVIOUSLY SUBMITTED.
 PLEASE KNOW, A REPONSE LETTER FROM THE
 DESIGN TEAM ON HOW EACH COMMENT WAS
 ADDRESSED OR COMMENTS WITH REPSECT TO
 REVIEW COMMENTS WOULD GREATLY HELP
 EXPEDITE THE REVIEW PROCESS. PLEASE SEE
 THAT NO RESPONSE LETTER WAS IN PACKAGE
 SUBMITTED.
  
 7) NOTE: PLEASE SEE ADDRESS IN TITLE
 BLOCKS FOR LOCATION OF SAID PROJECT IS
 NOT CORRECT ON SHEETS. PLEASE SEE MORE
 THAN ONE ADDRESS IS BEING SHOWN, HOWEVER
 THE ADDRESS OF RECORD AS APPLIED FOR IS
 2995 45TH ST. THIS ADDRESS MUST BE
 CORRECT ON "ALL" SHEETS AND FOR "ALL"
 TRADES. THIS WAS NOTED BY THE BUIDLIGN
 REVIEWER ALSO.
  
 8) NOTE: PLEASE SEE THE BRIGHT COLORED
 SHEET NOW ATTACHED TO REVIEW NOTES WHICH
 REFERENCES FS 553.80(2)(B) WITH RESPECT
 TO THE DESIGN PROFESSIONALS AND REPEAT
 CODE COMPLIANT COMMENTS. PLEASE KNOW,
 ONE SET OF PLANS ARE NOW RETAINED BY
 THIS OFFICE FOR POSSIBLE REVIEW BY THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS
 AND STATE'S LEGAL COUNSEL TO THE BOARD
 FOR SAID COMMENTS ABOVE.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAYAFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVE ANY
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE BE SURE ONE SET OF OLD/VOIDED
 SHEETS IS SUBMITTED FOR REFERENCE.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]