Plan Review Notes For Permit 05091455
Permit Number 05091455
Review Stop P
Sequence Number 1
Notes
Date Text
2005-12-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB CITY CODE
  
 1. SHT P-0 SPECIFIC DEMO NOTES:
 #1 IN THE INSTALLATION OR REMOVAL OF
 ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED. SECTION 704.5. ALL
 CAPPED SECTIONS SHALL BE APPROVED BY THE
 PLUMBING INSPECTOR PRIOR TO COVERING.
 2. SHT P-1 KEY NOTES:
 #4 BACKFLOW PREVENTER IF INSTALLED
 INSIDE SHALL BE LOCATED A MAXIMUM 4'
 ABOVE THE FLOOR FOR SERVICE AND
 CERTIFICATION.
 #7 FLOOR SINK OR HUB DRAIN REQUIRED.
 SECTIONS 802.3 & 802.3.2. FLOOR SINKS
 ARE NOT APPROVED INDIRECT WASTE
 RECEPTORS.
 #12 WATER FILTERS SHALL MEET THE
 REQUIREMENTS OF NSF-42. SUBMIT MANUF.
 SPECIFICATIONS FOR FILTER. SECTION 611.1
 #16. NOT SHOWN AT THE 3-COMP SINK, BUT
 BY THE TEA/COFFEE MACHINES. PLEASE
 CLARIFY. SECTION 104.2.1.
 #18 ALSO SHOWN AT 3-COMP SINK. PLEASE
 CLARIFY. SECTION 104.2.1.
 #20 GREASE TRAP SHALL BE SIZED BY LYNN
 MASSON, ENVIRONMENTAL COMPLIANCE MANAGER
 AND THE GREASE INTERCEPTOR SHALL BE
 LOCATED OUTSIDE THE BUILDING. PLEASE
 CONTACT LYNN MASSON AT (561) 822-2271,
 FAX (561) 822-2279, OR E-MAIL
 [email protected].
 #26 NOT APPROVED.
 3. SHT P-2 SEE COMMENTS #1 & #2 KEY NOTE
 #20.
 4. SHT P-2 PLUMBING SPECIFICATIONS AND
 NOTES:
 #4 AIR CHAMBERS ARE NOT APPROVED.
 PLEASE DELETE FROM REFERENCE. SECTION
 604.9.
 #10 1/4"FT SLOPE REQUIRED FOR 2-1/2"
 PIPE AND SMALLER. TABLE 704.1.
 4. ALL PME SHEETS:
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025 - THE
 SIGNATURE FOR THESE SHEETS ARE SEALED
 PHOTOCOPIES AND ARE NOT APPROVED. A
 "WET" SEAL IS REQUIRED. NO TITLE BLOCK
 OR REQUIRED INFORMATION IS ON EACH SHEET
 AS REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]