| 2005-12-07 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | WPB CITY CODE |
| | |
| | 1. SHT P-0 SPECIFIC DEMO NOTES: |
| | #1 IN THE INSTALLATION OR REMOVAL OF |
| | ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS |
| | SHALL BE PROHIBITED. SECTION 704.5. ALL |
| | CAPPED SECTIONS SHALL BE APPROVED BY THE |
| | PLUMBING INSPECTOR PRIOR TO COVERING. |
| | 2. SHT P-1 KEY NOTES: |
| | #4 BACKFLOW PREVENTER IF INSTALLED |
| | INSIDE SHALL BE LOCATED A MAXIMUM 4' |
| | ABOVE THE FLOOR FOR SERVICE AND |
| | CERTIFICATION. |
| | #7 FLOOR SINK OR HUB DRAIN REQUIRED. |
| | SECTIONS 802.3 & 802.3.2. FLOOR SINKS |
| | ARE NOT APPROVED INDIRECT WASTE |
| | RECEPTORS. |
| | #12 WATER FILTERS SHALL MEET THE |
| | REQUIREMENTS OF NSF-42. SUBMIT MANUF. |
| | SPECIFICATIONS FOR FILTER. SECTION 611.1 |
| | #16. NOT SHOWN AT THE 3-COMP SINK, BUT |
| | BY THE TEA/COFFEE MACHINES. PLEASE |
| | CLARIFY. SECTION 104.2.1. |
| | #18 ALSO SHOWN AT 3-COMP SINK. PLEASE |
| | CLARIFY. SECTION 104.2.1. |
| | #20 GREASE TRAP SHALL BE SIZED BY LYNN |
| | MASSON, ENVIRONMENTAL COMPLIANCE MANAGER |
| | AND THE GREASE INTERCEPTOR SHALL BE |
| | LOCATED OUTSIDE THE BUILDING. PLEASE |
| | CONTACT LYNN MASSON AT (561) 822-2271, |
| | FAX (561) 822-2279, OR E-MAIL |
| | [email protected]. |
| | #26 NOT APPROVED. |
| | 3. SHT P-2 SEE COMMENTS #1 & #2 KEY NOTE |
| | #20. |
| | 4. SHT P-2 PLUMBING SPECIFICATIONS AND |
| | NOTES: |
| | #4 AIR CHAMBERS ARE NOT APPROVED. |
| | PLEASE DELETE FROM REFERENCE. SECTION |
| | 604.9. |
| | #10 1/4"FT SLOPE REQUIRED FOR 2-1/2" |
| | PIPE AND SMALLER. TABLE 704.1. |
| | 4. ALL PME SHEETS: |
| | A PROFESSIONAL ENGINEER SHALL SIGN HIS |
| | NAME AND AFFIX HIS SEAL TO ALL PLANS, |
| | SPECIFICATIONS, REPORTS AND FINAL BID |
| | DOCUMENTS PROVIDED TO THE OWNER OR THE |
| | OWNER'S REPRESENTATIVE, OR OTHER DOCU- |
| | MENTS PREPARED OR ISSUED BY SAID REGIS- |
| | TRANT AND BEING FILED FOR PUBLIC RECORD. |
| | THE DATE THAT THE SIGNATURE AND SEAL IS |
| | AFFIXED AS PROVIDED HEREIN SHALL BE EN- |
| | TERED ON SAID PLANS, SPECIFICATIONS, RE- |
| | PORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL |
| | ENGINEER, FAC 61G15-23.002(1) |
| | FS 471.025 |
| | EACH SHEET OF PLANS AND PRINTS WHICH |
| | MUST BE SEALED UNDER THE PROVISIONS OF |
| | CHAPTER 471 SHALL BE SEALED, SIGNED AND |
| | DATED BY THE PROFESSIONAL ENGINEER IN |
| | RESPONSIBLE CHARGE. FAC 61G15-23.002(2) |
| | FS 471.025 |
| | ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| | SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| | EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME AND LICENSE NUMBER, AS WELL |
| | AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. A TITLE BLOCK |
| | WILL SATISFY THIS REQUIREMENT. FAC |
| | 61G15-23.002(2) - FS 471.025 - THE |
| | SIGNATURE FOR THESE SHEETS ARE SEALED |
| | PHOTOCOPIES AND ARE NOT APPROVED. A |
| | "WET" SEAL IS REQUIRED. NO TITLE BLOCK |
| | OR REQUIRED INFORMATION IS ON EACH SHEET |
| | AS REQUIRED. |
| | |
| | REVIEW BY KEN STEVENS |