| 2005-11-16 00:00:00 | ********** UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SEE ALL M |
| | SEALED PHOTCOPIES OF ENGINEER'S ORIGINAL |
| | SIGNATURE. PLEASE SEE FS 471.025 AND FAC |
| | 61G15-23 WHICH REQUIRES THE ENGINEER TO |
| | SIGN, DATE WITH AN "ORIGINAL" SIGNATURE. |
| | THIS IS REQUIRED OF ALL TRADES AND FOR |
| | ALL SHEETS WHETHER OR NOT THE COMMENT IS |
| | MADE BY OTHER REVIEWER(S), |
| | PLEASE KNOW, ONE COPY MAY BE RETAINED |
| | FOR POSSIBLE REVIEW BY FBPE'S, PLEASE |
| | MAKE CORRECTIONS. |
| | |
| | 2)NOTE: PLEASE SEE MISSING TITLE |
| | BLOCK/TITLE BLOCK INFORMATION WHICH IS |
| | REQUIRED UNDER FLORIDA ADMINISTRATIVE |
| | CODE (FAC) 61G15-23.002. |
| | PLEASE SEE MISSING PRINTED NAME AND |
| | LICENSE # OF PE. |
| | PLEASE SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER. |
| | PLEASE SEE OTHER INFORMATION ETC AS |
| | LISTED. |
| | PLEASE KNOW, THIS INFORMATION IS ALSO |
| | REQUIRED FOR ALL SHEETS AND FOR ALL |
| | TRADES. |
| | |
| | 3)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULES. |
| | PLEASE SEE 700.12E FOR CIRCUITING OF |
| | EM/EXT LTS. |
| | THE BRANCH CIRCUIT FEEDING THE UNIT |
| | EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | |
| | 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| | AT 125%. 215.3,230.42 ETC. |
| | (LIGHTING ETC) |
| | |
| | 5)NOTE: PLEASE SEE 2002 NEC 210.8B3, |
| | WHICH REQUIRES ALL 15 AND 20A 120V |
| | CIRCUITS/DEVICES LOCATED IN KITCHEN |
| | AREAS TO BE GFI/GFI PROTECTED. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAYAFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO REMOVE ANY |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | PLEASE BE SURE ONE SET OF OLD/VOIDED |
| | SHEETS IS SUBMITTED FOR REFERENCE. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |