| 2007-02-11 17:34:08 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6652 |
| | E-MAIL: [email protected] |
| | |
| | REVISION SUBMITTED 12/18/06 FOR CLUBROOM AND FITNESS |
| | CENTER BUILDOUT. |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | 1) FBC 704.1.2.3OCCUPANCY SEPARATION FOR FITNESS |
| | CENTER AND CLUB LOUNGE.THE PLANS SHALL STATE THE |
| | TOTAL AREA OF THE FITNESS CENTER AND TOTAL AREA OF THE |
| | CLUB LOUNGE.PER FBC 304.1.2 THEY ARE CLASSIFIED AS |
| | ASSEMBLY OCCUPANCY.IF THE AREA EXCEEDS 2,000 SQ FT, |
| | THEY SHALL BE SEPARATED FROM THE RESIDENTIAL OCCUPANCY |
| | BY 2 HOUR FIRE RESISTANT CONSTRUCTION.THE FITNESS |
| | CENTER AND CLUB LOUNGE BOTH EXCEED 750 SQ FT SO, PER |
| | FBC 704.1.2.2, THEY CANNOT BE CONSIDERED AS INCIDENTAL |
| | TO THE RESIDENTIAL OCCPANCY.AMEND THE PLANS TO STATE |
| | THE AREA OF THE FITNESS CENTER AND CLUB LOUNGE, AND |
| | INCREASE THE OCCUPANCY SEPARATION FIRE RESISTANCE TO 2 |
| | HOURS IF APPROPRIATE. |
| | |
| | 2) FBC 1012.1.2FITNESS CENTER DOOR 51.THE DOOR TO |
| | THE EXIT ACCESS CORRIDOR IS SHOWN SWINGING INTO THE |
| | FITNESS CENTER.THE DOOR SHALL OPEN IN THE DIRECTION |
| | OF EGRESS.AMEND THE PLANS. |
| | |
| | 3) FBC 1012.7FITNESS CENTER EGRESS DOORS.PER FBC |
| | 1004.1.2 NOT LESS THAN TWO EGRESS DOORS ARE REQUIRED. |
| | THE DOOR SCHEDULE ON SHEET A-4.1 SPECIFIES MAGNETIC |
| | LOCKS (HARDWARE NOTE 9) FOR DOOR 51 AND DOOR 50 |
| | (LEADING TO THE POOL DECK WHICH GIVES ACCESS TO STAIR |
| | 3).PER FBC 1012.7 MAGNETIC LOCKS ARE NOT PERMISSABLE |
| | FOR REQUIRED EGRESS SERVING ASSEMBLY OCCUPANCIES. |
| | SPECIFY PANIC HARDWARE OR FIRE/EXIT HARDWARE FOR DOOR |
| | 51.ALSO, EITHER SPECIFY PANIC HARDWARE OR FIRE/EXIT |
| | HARDWARE FOR DOOR 50, OR PROVIDE A SECOND DOOR FROM THE |
| | FITNESS CENTER TO THE EXIT ACCESS CORRIDOR. |
| | |
| | 4) FBC 1012.1.2CLUB LOUNGE DOOR 66.THE DOOR TO THE |
| | EXIT ACCESS CORRIDOR IS SHOWN SWINGING INTO THE CLUB |
| | LOUNGE.THE DOOR SHALL OPEN IN THE DIRECTION OF |
| | EGRESS.AMEND THE PLANS. |
| | |
| | 5) FBC 1012.7CLUB LOUNGE EGRESS DOORS.PER FBC |
| | 1004.1.2 NOT LESS THAN TWO EGRESS DOORS ARE REQUIRED. |
| | THE DOOR SCHEDULE ON SHEET A-4.1 SPECIFIES MAGNETIC |
| | LOCKS (HARDWARE NOTE 9) FOR DOOR 66 AND DOOR 50 |
| | (LEADING TO THE POOL DECK WHICH GIVES ACCESS TO STAIR |
| | 3).PER FBC 1012.7 MAGNETIC LOCKS ARE NOT PERMISSABLE |
| | FOR REQUIRED EGRESS SERVING ASSEMBLY OCCUPANCIES. |
| | SPECIFY PANIC HARDWARE OR FIRE/EXIT HARDWARE FOR DOOR |
| | 66 AND DOOR 50. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |