| Plan Review Notes For Permit 05091425 |
| Permit Number |
05091425 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2007-01-23 14:20:27 | | | | REVISION DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1. SHT P1 THE DRAINS FROM THE FIRE SPRINKLER SHALL BE | | | INDIRECT WASTED AND REQUIRES A TRAP. SECTIONS 802.1.4 & | | | 901.2.1. A FLOOR SINK OR HUB DRAIN IS REQUIRED. (SEE | | | REVISION 13 - REVISION STATES BLDG DEPT COMMENT. I | | | BELIEVE THE COMMENT WAS THAT INDIRECT WASTE RECEPTORS | | | ARE NOT ALLOWED IN THE STAIRWELL, NOT THAT THE WASTE | | | RECEPTORS ARE NOT NEEDED. SEE PROVISO ON PLANS). PLEASE | | | CLARIFY. | | | | | | 2. SHT P-1 PLEASE TURN OFF ALL PREVIOUS REVISIONS AS | | | THIS SLOWS THE REVISION PROCESS DOWN. ONLY INDICATE THE | | | REVISIONS BE SUBMITTED AT THIS TIME ON THE PLANS. | | | SECTION 104.2.1.-- THERE ARE CHANGES TO THE ROUTING | | | OF THEWATER SUPPLY TO THE FIRE PUMP AS WELL AS A | | | BYPASS THAT HAS NOT BEEN CLOUDED, NOR INDICATED AS A | | | REVISION. CLOUD AND NUMBER ALL REVISIONS. - - MANY | | | REVISIONS SHOWN HAVE NO CHANGES TO STAMPED SET OF | | | PLANS. PLEASE CLARIFY. (SEE REVISIONS 10 & 12). | | | | | | 3. SHT P-22REVISION #4 NOT APPROVED. SEE COMMENT #1. | | | | | | | | | **********APPROVED SHEETS********** | | | P-5, &P-5A. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|