| 2006-08-26 00:00:00 | |
| | |
| | |
| | |
| | PASSED/PROVISO |
| | |
| | SHTS P-1 & P-22 FLOOR DRAINS ARE NOT |
| | APPROVED IN THE STAIRWELLS. POSITIVE |
| | PRESSURES CAUSED BY THE STAIRWELL |
| | PRESSURIZATION MAY CONFLICT WITH SECTION |
| | 901.2. ALSO PENETRATIONS IN AN EXIT |
| | ENCLOSUER ASSEMBLY OTHER THAN THOSE |
| | LIMITED TO NFPA 101 SECTION 7.1.3.2.1(5) |
| | ARE NOT ALLOWED. - REVISIONS REQUIRED |
| | FOR THESE SHEETS |
| | |
| | |
| | |
| | |
| | GAS APPLIANCE VENTING SHALL BE FIELD |
| | INSPECTED AND APPROVED. |
| | MANUF. SPECIFICATION SHEETS SHALL BE |
| | SUBMITTED AT THE TIME OF GAS PERMIT |
| | APPLICATION. MANUF. SPECIFICATIONS |
| | SHEETS REQUIRED FOR THE GAS REGULATORS. |
| | VENTS FOR REGULATORS SHALL BE MADE OF |
| | NON COMBUSTABLE MATERIAL. GAS RISER - A |
| | SHUT OFF VALVE SHALL BE INSTALLED PRIOR |
| | TO THE REGULATORS WITH A UNION BETWEEN |
| | OR AFTER REGULATOR. (SHT P-6). SECTION |
| | 410.2(5). REVISIONS REQUIRED FOR THESE |
| | SHEETS. |
| | |
| | |
| | |
| | |
| | SHTS P-4 & P-21A COOLING TOWER WATER |
| | RISER DIAGRAM. THE CHECK VALVES TO THE |
| | FOUNTAINS AND THE TRASH CHUTES ARE NOT |
| | APPROVED. INSTALL N-36 VACUUM BREAKERS |
| | FOR THIS APPLICATION. - THE IRRIGATION |
| | SYSTEM REQUIRES A PRESSURE VACUUM |
| | BREAKER TO THAT LINE SEPARATE FROM THE |
| | REST OF THE SYSTEM. - CLARIFY WATER |
| | PIPING TO POOL HEATERS AS THERE IS MAKE |
| | UP WATER TO THE COLLECTING TANKS. - |
| | REVISION REQUIRED FOR THESE SHEETS. |
| | |
| | |
| | |
| | |
| | SEE PROVISO REQUIREMENTS FOR SHEETS P-1, |
| | P-4, P-6, P-21A, & P-22. |
| | |
| | |