| Date |
Text |
| 2006-07-06 00:00:00 | |
| | RESPONSE TO COMMENTS FROM REVIEW DATED |
| | 12/28/05 |
| | |
| | COMMENT #1 - OK |
| | COMMENT #2 - OK (SEE COMMENT #3) |
| | |
| | COMMENT #3 - REPONSE INDICATES SHEET |
| | AC-5 PROVIDES MUFFLER ELEVATION.PLAN |
| | ONLY INDICATES MUFFLER EXHAUST TO |
| | TERMINATE A MINIMUM OF 10 FT FROM O/A |
| | INTAKES.PLEASE PROVIDE ELEVATION FROM |
| | THE ADJOINGING GRADE LEVEL.PLEASE |
| | NOTE, MUFFLER AND EF-23 EXHAUST |
| | TERMINATIONS ARE WITHIN 10 FT OF THE |
| | FRESH AIR INTAKE TO THE GENERATOR ROOM. |
| | |
| | COMMENT #4 - OK - PLEASE PROVIDE |
| | INFORMATION ON WHAT WILL BE STORED IN |
| | THE JANITOR CLOSET #1. |
| | |
| | COMMENT #5 - OK FOR THE COMMON AREAS |
| | ONLY.PLEASE PROVIDE O/A CALCULATIONS |
| | FOR THE RESIDENCE IN ACCORDANCE WITH |
| | 2001 FBC 403.3, VENTILATION SYSTEMS FOR |
| | OTHER THAN R-E (ONE & TWO FAMILY |
| | DWELLINGS), SHALL BE DESIGNED TO HAVE |
| | THE CAPACITY TO SUPPLY THE MINIMUM |
| | OUTDOOR AIR FLOW RATE DETERMINED IN |
| | ACCORDANCE WITH TABLE 403.3. |
| | |
| | COMMENT #6 - OK |
| | COMMENT #7 - OK |
| | COMMENT #8 - OK |
| | COMMENT #9 - OK |
| | COMMENT #10 - PLAN SHEET AC-14 UNIT C-5, |
| | PLEASE NOTE, RETURN AIR TO BE EQUAL TO |
| | SUPPLY INTO THAT AREA.R/A SHALL BE A |
| | MINIMUM OF 8". |
| | |
| | COMMENT #11 - PLAN SHEET AC-4 |
| | VENTILATION FOR THE POOL EXHAUST AND AIR |
| | MAKE-UP ARE TERMINATING IN THE ENCLOSED |
| | GARAGE.GARAGE VENTILATION IS NOT |
| | CONTINUOUS, THEREFORE HOW WILL THIS |
| | APPLICATION PROVIDE FRESH AIR INTO THIS |
| | ROOM.PLAN SHEET AC-7 THE POOL |
| | EQUIPMENT ROOM LOUVERED DOOR APPEARS TO |
| | BE WITHIN 3FT OF THE TERMINATION OF |
| | EF-12.PLEASE INDICATE WHAT CHEMICALS & |
| | THE AMOUNT THAT WILL BE STORED IN WHICH |
| | EQUIPMENT ROOM. |
| | |
| | COMMENT #12 - OK, PLEASE NOTE, RESPONSE |
| | INDICATES COMBUSTION AIR CALCULATIONS |
| | ARE INDICATED ON PLAN SHEET AC-9 & |
| | AC-11.THERE ARE NO COMBUSTION AIR |
| | CALCS ON AC-9 BUT AC-7 INSTEAD. |
| | |
| | COMMENT #13 - OK, SEE COMMENT 12. |
| | |
| | COMMENT #14 - OK |
| | COMMENT #15 - PLAN SHEET AC-29, PROPOSED |
| | SMOKE CONTROL SYSTEM.PLEASE INDICATE |
| | WHICH METHOD IS INTEND TO BE UTILIZED |
| | UNDER 2001 FBC 412.5 ITEMS 1, 2, 3 OR 4. |
| | SHOULD SUBMITTAL BE UNDER ITEM 4, THIS |
| | MUST BE SUBMITTED TO THE BUILDING |
| | OFFICAL, NEIL MELICK.PLEASE PROVIDE |
| | ALL SUPPORTING DOCUMENTATION. |
| | |
| | COMMENT #16 - OK |
| | COMMENT #17 - OK |
| | COMMENT #18 - OK |
| | **************************************** |
| | NEW COMMENT |
| | 19. PLAN SHEET A-4.1 - THE DOOR SCHEDULE |
| | INDICATES THE A/C CLOSET DOOR IN THE |
| | APARTMENTS ARE TO BE WOOD.PLEASE |
| | VERIFY WITH THE DOOR MANUFACTURER IF |
| | THIS MEETS THE CRITERIA FOR A NON |
| | COMBUSTIBLE DOOR AS REQUIRED IN 2001 FMC |
| | 602.2.1. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |
| | |
| | |