| 2006-01-04 00:00:00 | ******DENIED****** |
| | |
| | PLAN REVIEW WAS STARTED BY F.M. M. |
| | CARSILLO AND STOPPED AFTER 32 COMMENTS. |
| | THE FOLLOWING IS A CONTINUATION OF THE |
| | SAME PLAN REVIEW: |
| | |
| | 33) A MINIMUM OF (2) FIRE DEPARTMENT |
| | CONNECTIONS REQUIRED FOR HIGHRISE |
| | BUILDINGS. |
| | |
| | 34) THE FIRE ALARM SYSTEM SHALL BE UL |
| | CERTIFIED FOR CENTRAL STATION SERVICE. |
| | |
| | 35) LOCKING KNOX BOX CAPS REQUIRED FOR |
| | FIRE DEPARTMENT CONNECTIONS. |
| | |
| | 36) THE FIRE ALRM SYSTEM SHALL MEET THE |
| | SURVIVABILITY REQUIREMENTS OF NFPA 72. |
| | |
| | 37) THE BUILDING IS TO MEET ALL HIGHRISE |
| | REQUIREMENTS IN ACCORDANCE WITH |
| | APPLICABLE BUILDING AND FIRE CODES. |
| | |
| | 38) SEPARATE SHOP DRAWINGS AND PERMITS |
| | REQUIRED FOR FIRE SPRINKLER AND FIRE |
| | ALARM SYSTEMS. |
| | |
| | 39) SEPARATE SHOP DRAWINGS AND |
| | MANUFACTURER SPEC SHEETS REQUIRED FOR |
| | FIRE PUMP AND ASSOCIATED EQUIPMENT. |
| | |
| | 40) PLEASE NOTE THAT VARIOUS CODE |
| | EDITIONS ON SHT SP-14 ARE INCORRECT. |
| | NFPA 101 AND NFPA 1, 2003 EDITION, NFPA |
| | 13, 2002 EDITION, NFPA 14, 2003 EDITION, |
| | AND NFPA 20, 2003 EDITION. |
| | |
| | 41) IN ADDITION TO ELECTRONIC SWITCHES, |
| | THE DOUBLE CHECK DETECTOR ASSEMBLY SHALL |
| | BE SECURED WITH A LOCK AND CHAIN. |
| | |
| | 42) ALL ELEVATORS TO COMPLY WITH ASME |
| | A17.1. |
| | |
| | 43) PARKING GARAGE TO COMPLY WITH THE |
| | APPLICABLE BUILDING CODES AND NFPA 88A. |
| | |
| | 44) PLEASE PROVIDE INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILINGS IN |
| | TERMS OF CLASS A,B, OR C. |
| | |
| | 45) AN ADDRESS IS REQUIRED ON BUILDING |
| | AND SHALL BE A MINIMUM OF 6" IN HEIGHT |
| | AND CONTRASTING WITH BACKGROUND. |
| | |
| | 46) ALL SMOKE DETECTORS SHALL BE LOCATED |
| | A MINIMUM OF (3) FEET FROM AC DIFFUSERS. |
| | |
| | 47) FIRE ALARM SYSTEM SHALL BE CLASS A, |
| | STYLE D OR FULLY ADDRESSABLE. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPFR |
| | FIRE PLANS REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| 2005-11-18 00:00:00 | 1. CONSTRUCTION, DEMOLITION, AND |
| | RENOVATION TO COMPLY WITH NFPA 241. |
| | |
| | 2. EXIT STAIRS ARE TO BE KEPT UP |
| | WITH CONSTRUCTION. |
| | |
| | 3. TEMPORTARY STANDPIPES ARE |
| | REQUIRED WHEN THE BUILDING REACHES |
| | THREE STORIES OR THIRTY FEET IN HEIGHT. |
| | |
| | 4. DEBRIS REMOVAL SHALL OCCUR |
| | DAILY. |
| | |
| | 5. NO CUTTING OR WELDING IS TO BE |
| | PERFORMED WITHOUT APPROVAL FROM |
| | THE BUREAU OF FIRE PREVENTION AND |
| | COMPLIANCE WITH NFPA 51B. |
| | |
| | 6. WHAT WILL BE THE NAME OF THE NEW |
| | STREET. |
| | |
| | 7. WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| | TO, DURING ,AND AFTER CONSTRUCTION. |
| | |
| | 8. SUITABLE ROADS REQUIRED FOR FIRE |
| | AND PARAMEDICAL EQUIPMENT. |
| | |
| | 9. COULD ONLY LOCATE ONLY TWO FIRE |
| | HYDRANTS ON PAGE C-13. NOT ENOUGH |
| | FIRE HYDRANTS. |
| | |
| | 10. PLEASE REVIEW CODE TAB BOX TO |
| | ENSURE PROPER INFORMATION. |
| | |
| | 11. KNOX-BOXES WILL BE REQUIRED. |
| | |
| | 12. ALL COMMERCIAL SPACES MUST BE FIRE |
| | SPRINKLER PROTECTED PRIOR TO |
| | RECEIVING A C OF O. |
| | |
| | 13. COULD NOT LOCATE EXIT SIGNS GARAGE, |
| | GROUND FLOOR. |
| | |
| | 14. NO EXIT SIGNS SECOND FLOOR, PAGE |
| | E-3. |
| | |
| | 15. EXIT SIGNS APPEAR TO BE MISSING |
| | ON PAGE E-4. WHERE ARE THE ARE THE |
| | EXIT SIGNS LOCATED FOR THE GARAGE. |
| | CORRIDOR NEAR ELECTRICAL ROOM # 3 |
| | DISPLAYS NO EQUIPMENT. |
| | |
| | 16. SAME PROBLEM ON PAGE E-5. |
| | |
| | 17. EXIT SIGNS SHALL NOT EXCEED 100 |
| | FEET APART. |
| | |
| | 18. ELECTRICAL PLANS DO NOT APPEAR TO |
| | BE COMPLETE. |
| | |
| | 19. PLEASE INDICATE FIRE RATINGS OF |
| | SHAFTS SHWON ON PAGE AC-14. |
| | |
| | 20. MECHANICAL EQUIPMENT SHOWN IN |
| | SOME STAIRWELLS. ONLY CERTAIN |
| | EQUIPMENT IS ALLOWED IN STAIRWELLS. |
| | |
| | 21. PLEASE XPLAIN GATE IN PARKING GARAGE |
| | ON PAGE A-1.1. |
| | |
| | 22. PLEASE SUBMIT A LIFE SAFETY PLAN |
| | FOR REVIEW. |
| | |
| | 23. DOORS FOR THE POOL DECK ON THE 9TH |
| | FLOOR APPEAR TO SWING IN THE WRONG |
| | DIRECTION. |
| | |
| | 24. PLEASE INDICATE OCCUPANT LOAD |
| | FOR POOL AND POOL DECK. |
| | |
| | 25. PLEASE EXPLAIN CARD READERS AND HOW |
| | THEY WILL EFFECT EXITING. |
| | |
| | 26. SOFFITS ARE NOT TO INTERFERE WITH |
| | ANY OPERATION OF REQUIRED FIRE |
| | SPRINKLERS. |
| | |
| | 27. PLEASE PROVIDE PRESCRIPTVE STRENGTH |
| | REQUIREMENTS FOR ALL HANDRAILS AND |
| | GUARDRAILS. |
| | |
| | 28. PLEASE INDICATE WHICH ELEVATORS |
| | WILL BE STRETCHER ACCESSIBLE. SIGNS WILL |
| | BE REQUIRED. |
| | |
| | 29. ELEVATOR WARNING SIGNS WILL BE |
| | REQUIRED. |
| | |
| | 30. STAIRWELL SIGNS WILL BE REQUIRED. |
| | |
| | 31. TACTILE SIGNAGE REQUIRED AT STAIRS. |
| | |
| | 32. WHAT SIZE IS THE RISER AND TREADS |
| | SHOWN ON PAGE A-2.1.3. |
| | |
| | ACCORDING TO DEWEY PALMER, NEW SHEETS |
| | ARE TO BE SUBMITTED BY THE ARCHITECT. |
| | THE REVIEW WAS STOPPED BECAUSE THE PLANS |
| | WERE NOT COMPLETE. |
| | |
| | MIKE CARSILLO, CHIEF FIRE PREVENTION |
| | OFFICER |
| | 804-4709 |