| 2006-06-18 00:00:00 | REVIEW IN PROGRESS. |
| | ****** UNSAT 2ND REVIEW ****** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM FIRST |
| | REVIEW AND SOME NEW COMMENTS DUE TO |
| | COMPLETE RISER ETC NOW SUBMITTED. |
| | |
| | |
| | ** IMPORTANT** |
| | WHEN SUBMITTING MANUFACTURES SPECS/CUT |
| | SHEETS, PRODUCT APPROVALS, STRUCTURAL |
| | CALCS ETC,PLEASE PLACE IN A BINDER OF |
| | SOME TYPE AND LABEL EACH SECTION/PRODUCT |
| | FOR EASY REFERENCE. THIS WOULD HELP |
| | GREATLY IN THE PLAN REVIEW PROCESS AND |
| | KEEPING ALL SUBMITTIALS IN ORDER. |
| | |
| | 1) NOTE: PLEASE CORRELATE ALL |
| | SPEC/MANUFACTURES CUT SHEETS SUBMITTED |
| | WITH PLANS. |
| | PLEASE SEE TWO DIFFERENT GENERATORS, TWO |
| | DIFFERENT SIZES, TWO DIFFERENT ATS'S. |
| | PLEASE SEE RISER AND PLANS. |
| | 215.5 |
| | |
| | 2) NOTE: PLEASE SEE SEE ATS IS STILL |
| | BEING SHOWN AS 3-POLE ON PLANS/ RISER |
| | AND SUBMITTIALS. |
| | PLEASE SEE RISER ALSO INDICATES 4-POLE |
| | AS REQUIRED IN ONE LOCATION. |
| | PLEASE SEE E-19 SHOWS 3-POLE ALSO. |
| | 215.5 |
| | |
| | 3) NOTE: PLEASE SEE FIRE PUMP SPECS FOR |
| | DIESEL FP TANK, INDICATES 300 GALS IN ON |
| | ONE SHEET AND 270 GALS ON ANOTHER? |
| | PLEASE SPECIFY THE CORRECT SIZE TANK, |
| | PLEASE SPECIFY THE GPH CONSUMPTION OF |
| | THE DIESEL FIRE PUMP. |
| | ** PLEASE VERIFY MIN 8HRS? |
| | 215.5, UNABLE TO VERIFY. PLEASE SEE |
| | NFPA-20 CHAPTER 11 |
| | |
| | 4) NOTE: PLEASE SEE NO "JOBSITE SPEC |
| | BOOKS" WERE SUBMITTED. THIS IS REQUIRED. |
| | |
| | 5) NOTE: PLEASE SEE RISER NOTE #7A IS |
| | BEING INDICATED YET THIS COULD NOT BE |
| | LOCATED ON RISER. THIS IS FOR METER/UNIT |
| | RISER. |
| | 215.5 |
| | |
| | 6) NOTE: PLEASE SEE NOTE #3 ON HOUSE |
| | RISER INDICATES GFI PROTECTION. (SHOULD |
| | BE GFP.) |
| | 215.5 |
| | |
| | 7) NOTE: PLEASE SEE NOTE #5 HOUSE RISER |
| | NOTES, (3-POLE ATS), SEE NOTES ABOVE AND |
| | CORRELATE. |
| | 215.5 |
| | |
| | 8) NOTE: PLEASE SEE MAIN FOR "TDP" IS |
| | SHOWN AS 1000A'S ON E-19, YET THIS IS |
| | NOTED ON HOUSE RISER NOTES AS BEING |
| | 1200A'S FOR FUTURE> |
| | THE LOAD ON THIS "TDP" IS NOT KNOWN AT |
| | THIS TIME>?? |
| | PLEASE VERIFY AS A 1000A DISCONNECT MAY |
| | FEED A 1200A DISC, AND IS BEING NOTED |
| | FOR COORDINATION. |
| | 215.5 |
| | |
| | 9) NOTE: PLEASE SEE UNIT C-2 MISSING |
| | CIRCUITING FOR KITCHEN WALL. |
| | THIS WAS NOTED AND REDLINED ON PREVIOUS |
| | PLANS. |
| | 215.5 |
| | ** THIS CAN BE REDLINED** |
| | |
| | 10) NOTE: PLEASE SEE UNIT C-9 AS |
| | LOCATION OF SD IN DEN SHOULD BE LOCATED |
| | WITHIN 12" OF THE HIGHEST POINT OF THE |
| | CEILING. IN UNIT C-9.1 THE SD WAS |
| | RELOCATED AND SEEMS TO BE THE SMAE |
| | LAYOUT. |
| | NFPA-72 11.8.3.5 |
| | ** THIS CAN BE REDLINED.** |
| | |
| | 11) NOTE: PLEASE SEE PANEL NOTATIONS ON |
| | E-20 INDICATE PANELS "TR1", TR2" AND TF |
| | PANELS BEING LOCATED ON THAT PAGE, |
| | HOWEVER THESE ARE ON E-22 |
| | 215.5 |
| | |
| | 12) NOTE: PLEASE SEE MISPRINT FOR TWO |
| | PANELS "LP'S" ON LOWER RIGHT HAND CORNER |
| | OF E-22. |
| | ** THIS CAN BE REDLINED ** |
| | |
| | 13) NOTE: PLEASE INDICATE THE |
| | PHOTO-METRICS FOR STAIRS UNDER EM POWER, |
| | AS ONLY THE TYPICAL DETAILS FOR TWO |
| | STAIR TOWERS WERE LOCATED FOR LEVELS |
| | UNDER NORMAL. |
| | LS 101 7.8.1.3,7.9.2.2 |
| | |
| | **PLEASE BE AWARE OF ANY COMMENTS FROM |
| | OTHER TRADES WHICH HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | ** WHEN RESUBMITTING PLANS, PLEASE BE |
| | SURE TO REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2006-06-11 00:00:00 | ONE ROLL IN ELECTRICAL FOR REVIEW, |