| Date |
Text |
| 2005-12-17 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | WPB CITY CODE |
| | |
| | 1. PLANS APPEAR TO BE INCOMPLETE AS |
| | SUBMITTED. MORE COMMENTS MAY BE |
| | FORTHCOMING NEXT REVIEW. |
| | 2. SHT L-6 MISSING. (SEE INDEX ON SHT |
| | L-1). SECTION 104.2.1. |
| | 3. SHT A-0.1 INDEX INDICATES THAT SHTS |
| | A-5.1 THRU A-5.6 HAVE KITCHEN AND |
| | BATHROOM ELEVATIONS, NOTES & DETAILS. |
| | THESE SHEETS WERE NOT SUBMITTED. SECTION |
| | 104.2.1. |
| | 4. SHTS A-1.7, A-1.8, A-2.6.1 THRU |
| | A-2.6.6, SUBMIT CALCULATIONS FOR PRIMARY |
| | AND SECONDARY ROOF DRAINS FOR ALL ROOFS. |
| | SHOW THE LOCATION OF ALL SECONDARY ROOF |
| | DRAINS FOR ALL ROOFS/DECKS. |
| | 5. ALL UNIT TYPES SHALL COMPLY WITH |
| | FHA-98 DESIGN MANUAL REQUIREMENTS ONE |
| | THRU SEVEN. SUBMIT DETAILS. |
| | 6. NOT USED |
| | 7. ALL ARCHITECT SHEETS. SEAL OF THE |
| | ARCHITECT SHALL IMPART INFORMATION |
| | REQUIRED BY FAC/FS. LITTLE OR NO |
| | INFORMATION CAN BE GLEANED FROM THE SEAL |
| | ON SOME SHEETS. PLEASE BE SURE EACH |
| | SHEET IS SEALED CORRECTLY & INFORMATION |
| | REQUIRED IS IMPARTED ON EACH SHEET. FAC |
| | 61G1-16.004 & FS 481.2055. |
| | 8. SHT A-2.7.5 SHOW THE LOCATION OF ALL |
| | SECONDARY DRAINS REQUIRED BY SECTION |
| | 1107. |
| | 9. SHTS A-2.7.5 & A-10.1 MORE |
| | INFORMATION IS REQUIRED FOR THE |
| | FOUNTAINS. PLEASE INDICATE IF THERE WILL |
| | BE WATER SUPPLY LINES AND OR DRAINAGE |
| | LINES FOR FOUNTAINS. IF WATER SUPPLY |
| | LINES ARE INSTALLED, BACKFLOW PREVENTION |
| | IS REQUIRED. IF DRAINS ARE INSTALLED, |
| | THEY SHALL CONNECT TO THE SANT. SYSTEM |
| | AND THE OVERFLOW SHALL DRAIN TO STORM. |
| | PLEASE CLARIFY. SECTIONS 104.2.1 & 608. |
| | 10. SHT A-2.7.5 SEPARATE PERMITS |
| | REQUIRED FOR THE POOL & SPA POOL. |
| | (INFORMATIONAL). |
| | 11. SHT P-1 NO PIPING SHOWN TO FLOOR |
| | DRAINS IN THE TRASH ROOM AND IN THE PUMP |
| | ROOMS. SECTION 104.2.1. |
| | 12. SHT P-1 NO PIPING SHOWN TO RISERS |
| | 29, 30, & 44 THRU 51. SECTION 104.2.1. |
| | 13. SHT P-1 RISERS 10 & 26 NOT SHOWN ON |
| | FLOOR PLAN. SECTION 104.2.1. |
| | 14. SHT P-2 NO FLOOR PLANS FOUND FOR THE |
| | FLOOR PLAN A-1.2. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | 15. SHT P-2 4"-180FU DOWNSTREAM OF RISER |
| | S/51A IS NOT CORRECT. PLEASE CHECK |
| | FIGURES. SECTION 104.2.1. |
| | 16. SHT P-2 RECALCULATE FU'S DOWNSTREAM |
| | OF RISERS 64 & 65. SECTION 104.2.1. |
| | 17. SHT P-2 INDICATE FU VALUE FOR RISERS |
| | 75 & 82. SECTION 104.2.1. |
| | 18. SHT P-4 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS. SHOW |
| | SF OF EACH DRAINED AREA PLUS 1/2 AREA OF |
| | ALL VERTICAL WALLS INCLUDING PARAPETS, |
| | PLUS THE AREA OF ROOFS THAT DRAIN ONTO |
| | THE ROOF/DECK AREA FROM ABOVE. |
| | 19. SHT P-4 NUMEROUS RWL'S & DECK DRAINS |
| | ARE SHOWN FOR DD & PLANTER DRAINS ON THE |
| | 9TH FLOOR, BUT NO PIPING IS SHOWN |
| | INDICATING WHERE THE DRAINS ARE DRAINING |
| | TO. PLEASE CLARIFY. SHOW PIPING ON RWL |
| | RISER DIAGRAMS. ALSO NO RWL'S FOR THESE |
| | DRAINS ARE SHOWN ON SUBSEQUENT SHEETS. |
| | SECTION 104.2.1. |
| | 20. SHT P-5 SHOW THE LOCATION OF ALL |
| | SECONDARY DRAINS REQUIRED IN SECTION |
| | 1107. |
| | 21. SHT P-5 RWL 3200SF NOT SHOWN ON THE |
| | FLOOR PLAN. (NEAR RISER 79) 104.2.1. |
| | 22. SHT P-7 SUBMIT CALCULATION FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS. (SEE |
| | COMMENT #18). SECTIONS 1106 & 1107. |
| | 23. SHT P-7 SUBMIT A DETAIL FOR THE |
| | BOILER ROOM. SHOW THE PIPING LAYOUT |
| | INCLUDING ALL PIPE SIZES, VALVES, VACUUM |
| | RELIEF VALVES, CIRCULATION PUMPS, P&T |
| | VALVES, PAN DRAINS, THERMAL EXPANSION |
| | CONTROL ECT. INDICATE ALL PIPE |
| | MATERIALS. SECTION 104.2.1. |
| | 24. SHTS P-8 THRU P-12 ALL UNITS WATER |
| | RISER DIAGRAMS. WATER HAMMER ARRESTOR |
| | REQUIRED AT THE REFRIGERATOR ICE MAKER |
| | IN AN "EFFECTIVE RANGE". PDI-WH 201 AND |
| | MANUF. INSTALLATION REQUIREMENTS. |
| | 25. SHT P-13 FLUSH RING RISER FOR THE |
| | TRASH CHUTE REQUIRES BACKFLOW |
| | PROTECTION. PLEASE INDICATE THE METHOD |
| | OF PROTECTION. SECTION 608. |
| | 26. SHT P-13 WATER RISER 13 INDICATES 1" |
| | COLD WATER SUPPLY TO WATER HEATERS, BUT |
| | HOT WATER RISERS SHOW 2". PLEASE |
| | CLARIFY. SECTION 104.2.1. |
| | 27. SHT P-14 PLEASE INDICATE MATERIAL |
| | USED AND TYPE OF SYSTEM. SECTION |
| | 104.2.1. |
| | 28. P-16 SANT. RISERS 44A 7 51A. PER |
| | SECTION 914.1 A RELIEF VENT IS REQUIRED |
| | AT EACH 10TH INTERVAL BEGINING WITH THE |
| | TOP FLOOR. |
| | 29. SUBMIT A SANITARY HORIZONTAL RISER |
| | DIAGRAM IN ISOMETRIC FORM FOR THE |
| | BUILDING DRAIN. INDICATE ALL PIPE SIZES |
| | AND SHOW THE LOCATION OF ALL RISERS. |
| | SHOW DRAINAGE FIXTURE UNITS AS IT |
| | ACCUMULATES IN THE SYSTEM. SECTION |
| | 104.3.1.1. |
| | 30. SUBMIT A STORM ISOMETRIC RISER |
| | DIAGRAM FOR THE HORIZONTAL PIPING OF THE |
| | BUILDING STORM DRAIN. SHOW ALL PIPE |
| | SIZES, RISER LOCATIONS, AND THE SQUARE |
| | FOOTAGE AS IT ACCUMULATES IN THE SYSTEM. |
| | SECTION 104.3.1.1. |
| | 31. SUBMIT STORM RWL RISER DIAGRAMS. |
| | SHOW ALL PIPE SIZES, OFFSETS & SQUARE |
| | FEET. |
| | 32. SHT P-15 RISER 7 FIRST FLOOR TUB |
| | MISLABLED AS A SHOWER. SECTION 104.2.1. |
| | 33. SHT P-18 RISERS 86, 87, 81, 80 LOWER |
| | OFFSET VENTS REQUIRED. (SHOW AT LOWEST |
| | OFFSET) SECTION 915.3 |
| | 34. SHT P-19 RISER 41 RELIEF VENT |
| | REQUIRED. SECTION 914. |
| | 35. P-20 SPRINKLER DRAIN DETAIL, DRAIN |
| | TO CONNECT TO THE SANITARY SYSTEM, NOT |
| | THE STORM AS SHOWN. CITY CODE 90-203. |
| | 36. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR GAS PERMIT APPLICATION: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | H. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | J. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | K. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | 37. ALL PLUMBING SHEETS. ENGINEERS SEAL |
| | SHALL SHOW ALL INFORMATION REQUIRED BY |
| | FAC 61G15-23.001 & FS 481.025 |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |