| Date |
Text |
| 2005-12-28 00:00:00 | DENIED:2001 FLORIDA BUILDING CODE |
| | |
| | 1.PLAN SHEET AC-1 EMERGENCY GENERATOR |
| | NOTE STATES 'SEE 1/4" SCALE DRAWING ON |
| | THIS SHEET FOR LAYOUT.DETAIL FOR THE |
| | LAYOUT IS NOT SHOWN. |
| | |
| | 2.PLEASE PROVIDE DISTANCE TO SIDEWALK |
| | FROM THE GENERATOR EXHAUST TERMINATION. |
| | |
| | 3.PLEASE PROVIDE DETAIL FOR THE |
| | GENERATOR WITH THE ELEVATION FOR MUFFLER |
| | EXHAUST.PLAN SHEET A-2.1.6 INDICATES |
| | LOUVERS, PLEASE SPECIFY INTAKES & |
| | EXHAUST. |
| | |
| | 4.PLAN SHEET AC-1 VENTILATION FOR |
| | VARIOUS ROOMS ARE NOT INDICATED |
| | (TELEPHONE, ELECTRICAL, PUMP ROOM, |
| | OFFICE AREAS, ETC). |
| | |
| | 5.PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS IN ACCORDANCE WITH 2001 FBC |
| | TABLE 403.3. |
| | |
| | 6.PROVIDE CALCULATIONS FOR THE GARAGE |
| | VENTILATION IN ACCORDANCE WITH 2001 FBC |
| | 411.4.2. |
| | |
| | 7.PLEASE NOTE, PLAN SHEET AC-1 FUTURE |
| | COMMERCIAL/RETAIL SPACE.SHOULD A |
| | RESTAURANT BE IN THE FUTURE PLANS |
| | CONSIDER LAYOUT FOR GREASE DUCT AND |
| | EXHAUST TERMINATION. |
| | |
| | 8.PLAN SHEETS AC-8 & 9 MECHANICAL |
| | ROOMS.PLANS DO NOT INDICATE |
| | VENTILATION FOR THE ROOMS. |
| | |
| | 9.PROVIDE LAYOUT FOR CONDENSER WATER |
| | PIPING.INDICATE PIPE SIZE & MATERIAL. |
| | |
| | |
| | 10. AC-12 UNIT C-5 DEN AREA WEST OF THE |
| | KITCHEN AREA, RETURN AIR IN NOT |
| | INDICATED.PLAN SHEET A1.1 SHOWS DOOR |
| | SEPARATING DEN.SHOW COMPLIANCE WITH |
| | 2001 FMC 601.4.PLEASE NOTE, RETURN AIR |
| | JUMPERS SHALL COMPLY WITH 2001 FMC 601.4 |
| | EXCEPTION 1 & 3. |
| | |
| | 11. PROVIDE INFORMATION & DETAILS FOR |
| | THE VENTILATION OF THE POOL EQUIPMENT |
| | ROOM. |
| | |
| | 12. PLAN SHEET P-1 ITEM #2 INDICATES GAS |
| | LINE.PLEASE INDICATE ALL GAS |
| | APPLIANCES. |
| | |
| | 13. PLAN SHEET P-7 INDICATES A BOILER |
| | ROOM.PLEASE PROVIDE VENTILATION & |
| | COMBUSTION AIR CALCULATIONS. |
| | |
| | 14. PLEASE PROVIDE SEQUENCE OF |
| | OPERATION. |
| | |
| | 15. PLEASE INDICATE METHOD OF SMOKE |
| | CONTROL PER 2001 FBC 412.5. |
| | |
| | 16. DRYER SHAFT & TRASH CHUTE SHALL BE |
| | EQUIPPED WITH FIRE SPRINKLERS IN |
| | ACCORDANCE WITH 2001 FBC 705.2.4.6 & |
| | NFPA 13 SECTION 8.14.2.2.1 & 13.15.2.1.1 |
| | |
| | 17. PLEASE PROVIDE MANUFACTURER |
| | SUBMITTAL DATA FOR THE GENERATOR, DRYER, |
| | PUMPS, ETC. |
| | |
| | 18. PLEASE PROVIDE ENERGY CALCULATIONS |
| | PER CHAPTER 13 OF THE 2001 FBC. |
| | |
| | PLEASE NOTE, PLANS APPEAR TO BE |
| | INCOMPLETE WHICH MAY GENERATE ADDITIONAL |
| | COMMENTS ON SUBSEQUENT REVIEWS. |
| | |