| Date |
Text |
| 2005-12-13 00:00:00 | ********** UNSAT *************** |
| | |
| | SOUTH TOWER @CITY PLACE |
| | 550 OKEECHOBEE BLVD. |
| | |
| | **** PLEASE KNOW, PLANS SUBMITTED ARE |
| | NOT COMPLETE, THERFORE A COMPLETE REVIEW |
| | FOR CODE COMPLIANCE CAN NOT BE DONE AT |
| | THIS TIME. |
| | PLEASE SEE THE BELOEW ITEMS KNOWN AT |
| | THIS TIME. |
| | |
| | 1)NOTE: PLEASE SUBMIT ALL MANUFACTURE |
| | SPECIFICATION SHEETS/ CUT SHEETS FOR |
| | FIRE PUMP(DIESEL) FIRE PUMP CONTROLLER, |
| | GENERATOR, AUTOMATIC TRANSFER SWITCH |
| | (ATS) AND ANY SUB BASE FUEL TANKS OR |
| | FUEL TANKS FOR DIESEL FIRE PUMP. |
| | PLEASE SURE ALL INFORMATION SUBMITTED |
| | MUST SHOW LISTINGS FROM A NATIONALLY |
| | RECOGNIZED TESTING LAB. (NRTL). |
| | PLEASE BE SURE ALL FIRE PUMP CONTROLLERS |
| | ETC COMPLY WITH NFPA-20 AND OTHER |
| | APPLICABLE CODES. |
| | |
| | 2)NOTE: PLEASE SEE PLANS INDICATE 600KW, |
| | YET RISER DIAGRAM SHOWS 400KW GEN. |
| | PLEASE ALSO VERIFY IF THE ATS WILLL BE A |
| | 4-POLE AND GEN TO BE SEPARTAELY DERIVED. |
| | |
| | PLEASE SEE 700.6DWHICH IN ORDER TO |
| | INDICATE A GROUND FAULT IN SOLIDLY |
| | GROUNDED WYE EMERGENCY SYSTEMS OF MORE |
| | THAN 150 VOLTS TO GROUND AND |
| | CIRCUIT-PROTECTIVE DEVICES RATED 1000 |
| | AMPERES OR MORE. THE SENSOR FOR THE |
| | GROUND-FAULT SIGNAL DEVICES SHALL BE |
| | LOCATED AT, OR AHEAD OF, THE MAIN SYSTEM |
| | DISCONNECTING MEANS FOR THE EMERGENCY |
| | SOURCE, AND THE MAXIMUM SETTING OF THE |
| | SIGNAL DEVICES SHALL BE FOR A |
| | GROUND-FAULT CURRENT OF 1200 AMPERES. |
| | INSTRUCTIONS ON THE COURSE OF ACTION TO |
| | BE TAKEN IN EVENT OF INDICATED GROUND |
| | FAULT SHALL BE LOCATED AT OR NEAR THE |
| | SENSOR LOCATION. |
| | ALTHOUGH 700.26 INDICATES THAT |
| | GROUND-FAULT PROTECTION OF EQUIPMENT IS |
| | NOT REQUIRED ON THE ALTERNATE SOURCE FOR |
| | EMERGENCY SYSTEMS, GROUND FAULTS CAN |
| | OCCUR ON SUCH SYSTEMS, AND THEY CAN |
| | RESULT IN EQUIPMENT BURNDOWN. BECAUSE OF |
| | THE EMERGENCY NATURE OF SUCH SYSTEMS, |
| | AUTOMATIC DISCONNECT IN THE EVENT OF A |
| | GROUND FAULT IS INAPPROPRIATE. DETECTION |
| | OF SUCH A FAULT, HOWEVER, IS DESIRABLE |
| | SO THAT THE CONDITION CAN BE CORRECTED. |
| | PLEASE PROVIDE ALL INFORMATION AS NEEDED |
| | FROM MANUFACTURE TO VERIFY, AS SOME |
| | MANUFACTURES ALREADY KNOW TO THIS OFFICE |
| | DO REQUIRE THE SWITCHING OF THE NEUTRAL |
| | IN ORDER FOR THE GFP SENSING TO WORK |
| | CORRECTLY. |
| | |
| | 3)NOTE:PLEASE SEE PLANS E-2 REFERENCE |
| | TO SEE LAYOUT OF FIRE COMMAND ROOM ON |
| | E-19, HOWEVER THIS LAYOUT IS "BLANK". |
| | PLEASE SEE NFPA-72, 101 WITH ALL MIN |
| | EQUIPMENT REQUIRED IN SUCH ROOM. PLEASE |
| | INDICATE THESE ITEMS ON PLANS. |
| | FIRE ALARM CONTROL PANEL, GENERATOR |
| | ANNUCIATOR PANEL, SHUNTS ETC. |
| | PLEASE ALSO SEE NOTE FOR EM LTS. |
| | |
| | 4)NOTE: PLEASE SEE THAT NO PLANS WERE |
| | SUBMIT TO SHOW POOL AREA LAYOUT , |
| | LIGHTING, RECEPTS ETC. |
| | UNABLE TO VERIFY MIN REQUIRED BY CODE |
| | FOR THESE AREAS. |
| | |
| | 5)NOTE: PLEASE PROVIDE REFERENCE TO THE |
| | 2002 NEC ON PLANS. |
| | PLEASE ALSO REFERENCE 2002 NFPA-72, AND |
| | THE 2003 NFPA-101. |
| | |
| | 6)NOTE: PLEASE PROVIDE COMPLETE |
| | PHOTOMETRICS FOR ALL CORRIDOR, STAIR |
| | TOWER AND EGRESS PATHS. PLEASE SEE 101 |
| | 7.8 WHICH REQUIRES A MIN OF 10FT CANDLES |
| | MIN FOR STAIR WELLS AND 1FT MIN UNDER EM |
| | CONDITIONS. |
| | PLEASE SEE 7.9.2.2 WHICH REQUIRES WIRING |
| | OF EM LTS TO BE SUCH IN THE EVENT OF THE |
| | SWITCHING OF A SWITCH, BREAKER ETC OR |
| | THE TRIPPING OF A SINGLE OCP DEVICE WILL |
| | IN NO WAY LEAVE ANY ONE AREA OF EGRESS |
| | IN TOTAL DARKNESS. IN ORDER TO |
| | ALLEAVIATE THIS , A MIN BATTTERY BACK UP |
| | FIXTURE OF SOME TYPEWILL BE REQUIRED |
| | TO POVIDE THE MIN 1FT CANDLE FOR MIN |
| | TIME. |
| | |
| | |
| | 7)NOTE: PLEASE SEE ALL MAIN ELECTRICAL |
| | ROOMS, FIRE COMMAND ROOM, GEN RM, FIRE |
| | PUMP RM AND ELEVATOR EQUIPMENT ROOMS ETC |
| | SHALL A BATTERY BACK UP TYPE OF LIGHTING |
| | FIXTURE. |
| | 700.16, LS 101 7-9, 90.4 |
| | |
| | 8)NOTE: PLEASE SEE 620.23 AND 620.24 |
| | WHICH REQUIRES EQUIPMENT ROOMS/AREAS TO |
| | HAVE A DEDICATED BRANCH CIRCUIT FOR |
| | RECEPTS AND LIGHTING.PLEASE SEE A |
| | DEDICATE CIRCUIT WAS LOCATED FOR RECEPT, |
| | HOWEVER LIGHTING COULD NOT BE VERIFIED. |
| | |
| | 9)NOTE: PLEASE SEE FIRE REVIEW FOR EXACT |
| | LOCATIONS OF ANY "KNOX BOX" LOCATION(S) |
| | WHICH MAY BE REQUIRED. ONE OR MORE |
| | LOCATIONS SHALL BE PLACED/NOTED ON |
| | PLANS. |
| | |
| | 10)NOTE: PLEASE SHOW ALL ROOM/AREA |
| | DESIGNATIONS ON PLANS. PLEASE SEE AREAS |
| | IN UNITS. PLEASE SEE AREAS WHICH NOW |
| | INDICATE THE 15A, #14 CIRCUITS IN AREAS |
| | WHICH APPEAR TO BE DINING AREAS. |
| | PLEASE SEE 210.52B1,210.11C1 |
| | |
| | 11)NOTE: : PLEASE SEE 210.63 FOR |
| | REQUIMENTS OF GFI RECEPTS FOR ALL A/C |
| | EQUIPMENT. PLEASE SEE THESE COULD NOT BE |
| | LOCATED ON ROOF PLANS ETC. |
| | |
| | 12)NOTE: PLEASE PROVIDE SPECIFIC NOTES |
| | ON SHEETS CONTAINING A LARGER SCALE OF |
| | ELECTRICAL ROMMS. THE NOTE FOR 110.26 |
| | WAS FOUND ON RISER SHEET, HOWEVER PLEASE |
| | INCLUDE THIS ON ABOVE SHEETS. |
| | |
| | 13)NOTE: PLEASE SEE SOME AREAS, WHICH |
| | ARE LABELED AS ELEVATORS RMS ARE SHOWN |
| | BLANK? |
| | E-7 |
| | |
| | 14)NOTE: PLEASE PROVIDE DETAIL FOR ALL |
| | FLOOR PENETRATIONS AND PENETRATIONS FOR |
| | BUC-DUCT INDICATION THE MIN 4" CURBING. |
| | 368.6B2 |
| | |
| | 15)NOTE: PLEASE INDICATE THE EQUIPMENT |
| | GROUNDING METHOD OF BUS-DUCT. PLEASE |
| | PROVIDE CUT SHEET FROM MANUFACTURE. |
| | PLEASE SEE LOCAL AMENDMENTS WHICH REUIRE |
| | THE EQUIPMENT GROUNDING TO BE |
| | COPPER.250.62 |
| | |
| | 16)NOTE: PLEASE PROVIDE COLOR CODING OF |
| | ELECTRICAL WIRING PER 215.8 OFLOCAL |
| | AMENDMENTS. 120/208 BLK,RED, BLUE, |
| | WHITE. |
| | 277/480V BROWN, PURPLE, YELLOW, GREY. |
| | SEE OTHERS IF ANY OTHER ELECTRICAL |
| | VOLTAGES ARE TO BE USED. |
| | |
| | |
| | 17)NOTE: PLEASE SEE SOME CIRCUTING |
| | MISSING ON UNITS PLANS. THESE HAVE BEEN |
| | REDLINED FOR AREAS OF COMMENT. |
| | |
| | 18)NOTE: PLEASE SEE SOME UNITS MISSING |
| | RECEPTS PER 210.52. |
| | PLEASE SEE REDLINED SET, ONLY A COUPLE. |
| | |
| | 19)NOTE: PLEASE SEE C 2.2 WHICH MENTIONS |
| | TO SEE ENLARGE AREA TO SHOW DETAIL, |
| | HOWEVER THIS SEEMS TO BE BLANK ON PLANS. |
| | |
| | 20)NOTE:PLEASE SEE THAT ALL RECEPTS |
| | SHOWN IN CLOSETS FOR LV TRNSFORMERS TO |
| | BE "PLUGGED IN" SHALL BE LOCATED ATLEAST |
| | 12" MIN FROM SHELVING. THESE MAY BE |
| | LOCATED ABOVE DOOR WAYS. |
| | PLEASE SEE PLUG-IN TYPE TRANSFORMERS |
| | CREATE VERY HIGH TEMPS AND SOME IN THIS |
| | JURISTICTION HAVE HEATED TO THE POINT OF |
| | MELTING, AND CUSE OF FIRE IN CLOSETS AND |
| | CLOSE PROIMITY TO COMBUSTIBLES. PLEASE |
| | SEE THIS CREATES A LIFE-SAFETY SITUATION |
| | AND ANY UNITS CONTAININGOCP, THERMAL |
| | CUT-OUT DEVICES WILL BE REQUIRED TO BE |
| | LOCATED AS ABOVE. 110.26,240.24D |
| | |
| | 21)NOTE: PLEASE SEE SOME UNITS IN WHICH |
| | THERE SEEMS TO BE TWO DIFFERENT HEIGHTS |
| | IN BEDRM CEILINGS. PLEASE SEE NFPA-72 |
| | 11.8.3.5 WHICH REQUIRES THESE SD'S TO BE |
| | LOCATED WITHIN 12" OF THE HIGHESRT POINT |
| | OF THE FLAT CEILING AREA. |
| | PLEASE SEE REDLINED PLANS FOR LOCATIONS. |
| | |
| | 22)NOTE: PLEASE SEE SOME UNITS WHICH |
| | INDICATE A HIGHER LOAD OF 122.5A'S ON A |
| | 125A BREAKER. PLEASE VERIFY AS THIS DOES |
| | NOT SEEM TO LEAVE ANY ALLOTMENT FOR |
| | FURTURE WIRING EXPANTION OF LOADS. |
| | THIS IS THE LOAD AFTER ALL PERMITTED |
| | DE-RATING BY NEC. |
| | PLEASE ALSO SEE ANY ARE VERYCLOSE TO |
| | THE 100A'S PROVIDED. |
| | 90.8 |
| | |
| | 23)NOTE: PLEASE SEE AREAS OF PLANS WHICH |
| | CONTAIN "WHITE-OUT" AND HAND-DRAWN |
| | CHNAGES MADE. (RISER SHEET). |
| | PLEASE SEE FS 471.025 ETC WHICH DOES NOT |
| | PERMIT ANY HAND DRAWN CHANGES TO PLANS, |
| | UNLESS EACH INDIVIDUAL CHANGE IS SIGNED |
| | AND DATED BY THE SAID ENGINEER OF |
| | RECORD. |
| | |
| | 24)NOTE:PLEASE PROVIDE COMPLETE NOTES |
| | WITH RESPECT TO THE LOCATIONS OF SMOKE |
| | DETECTORS. 11.8.3.5 |
| | SMOKE ALARMS AND SMOKE DETECTORS |
| | INSTALLED WITHIN A 6.1-M (20-FT) |
| | HORIZONTAL PATH OF A COOKING APPLIANCE |
| | SHALL BE EQUIPPED WITH AN |
| | ALARM-SILENCING MEANS OR BE OF THE |
| | PHOTOELECTRIC TYPE. |
| | SMOKE ALARMS AND SMOKE DETECTORS SHALL |
| | NOT BE INSTALLED WITHIN A 914-MM |
| | (36-IN.) HORIZONTAL PATH FROM A DOOR TO |
| | A KITCHEN OR A BATHROOM CONTAINING A |
| | SHOWER OR TUB. |
| | SMOKE ALARMS AND SMOKE DETECTORS SHALL |
| | NOT BE INSTALLED WITHIN A 914-MM |
| | (36-IN.) HORIZONTAL PATH FROM THE SUPPLY |
| | REGISTERS OF A FORCED AIR HEATING OR |
| | COOLING SYSTEM AND SHALL BE INSTALLED |
| | OUTSIDE OF THE DIRECT AIRFLOW FROM THOSE |
| | REGISTERS AND 5' MIN FROM RETURN AIR |
| | GRILLES. |
| | SMOKE ALARMS AND SMOKE DETECTORS SHALL |
| | NOT BE INSTALLED WITHIN A 914-MM |
| | (36-IN.) HORIZONTAL PATH FROM THE TIP OF |
| | THE BLADE OF A CEILING-SUSPENDED |
| | (PADDLE) FAN. |
| | |
| | 25)NOTE:PLEASE SHOW GROUNDING SYSTEM |
| | FOR ALL TRANSFORMER. PLEASE INCLUDE |
| | GROUNDING OF THESE TRANSFOMERS ON RISER |
| | DIAGRAM IN NOTES/LINE DIAGRAM. |
| | 250.30, 250.50 ETC. |
| | PLEASE PROVIDE THIS LINE DIAGRAM ON |
| | RISER SHEET. |
| | |
| | 26)NOTE:PLEASE SEE NO GFP INDICATED FOR |
| | HDP. 230.95. 240.13 ETC. |
| | |
| | 27)NOTE: PLEASE SEE ANY PROPOSED |
| | LIGHTNING PROTECTION SYSTEM SHALL BE |
| | INSTALLED AND ACCEPTABLE PER NFPA-780. |
| | ALTHOUGH A LIGHTNING PROTECTION SYSTEM |
| | IS NOT SHOWN ON ANY PLANS, PLEASE BE |
| | SURE A NOTE IS PLACED ON "ROOF-TOP" |
| | SHEET WITH REFERENCE TO NFPA-780. |
| | AS NOTED IN MEETING , "LIGHTNING |
| | PREVENTION" SYSTEMS ARE NOT PERMITTED OR |
| | ACCEPTABLE IN THIS JURISTICTION. |
| | |
| | 28)NOTE: PLEASE SEE THIS NOTE IS ALL |
| | ENCOMPASSING OF ELECTRICAL RISER, |
| | EQUIPMENT SCHEDULE, LOAD CALCULATIONS, |
| | PANEL SCHEDULES AND CALCUALTIONS ETC. |
| | |
| | ** PLEASE COMPLETE ALL OF THE ABOVE AND |
| | SUBMIT FOR REVIEW. |
| | PLEASE CORRELATE ALL PANEL SCHEDULS , |
| | EQUIPMENT WITH RISER |
| | PLEASE COMPLETE RISER WITH INFORMATION |
| | FOR EQUIPMENT, FEEDERS ETC. |
| | PLEASE SEE MANY AREAS OF LOAD |
| | CALCULATIONS WHICH ONLY INDICATE |
| | XXXXXXX'S. |
| | PLEASE SEE 2002 NEC. |
| | |
| | ** PLEASE KNOW THERE MAY BE OTHER |
| | COMMENTS DUE TO THE INCOMPLETE PLANS AT |
| | THIS TIME. |
| | |
| | ** PLEASE SEE REDLINED PLANS FOR |
| | POSSIBLE LOCATIONS. |
| | |
| | PLEASE SUBMITTHE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE TO GO OVER COMMENTS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| 2005-12-09 00:00:00 | ONE ROLL IN ELECTRIC FOR REVIEW. |