| Plan Review Notes For Permit 05091412 |
| Permit Number |
05091412 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-29 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1. SHTS P2.1.1, P2.1, P-2.2.2, P2.3.1, | | | P2.3 P-3.1.1, P3.1, P-3.2, P3.3.2, AND | | | P3.3. WATER HAMMER ARRESTORS ARE | | | REQUIRED AT THE WASH MACHINES OF ALL | | | UNITS. PER SECTION 604.9. - ALL WATER | | | HAMMER ARRESTORS SHALL BE LOCATED NEAR | | | THE FIXTURES IN AN "EFFECTIVE RANGE", | | | NOT IN THE CEILING AS SHOWN IN SOME | | | CASES. PDI-WH 201 AND MANUF INSTALLATION | | | INSTRUCTIONS. | | | 2. IF INDIVIDUAL METERS NO BACKFLOW | | | DEVISE IS REQUIRED, BUT IF SINGLE METER | | | AN RPZV BACKFLOW WILL BE REQUIRED ON THE | | | WATER SERVICE. PLEASE CLARIFY. SECTION | | | 608.13.2. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|