Plan Review Notes
Plan Review Notes For Permit 05091412
Permit Number 05091412
Review Stop M
Sequence Number 1
Notes
Date Text
2005-11-30 00:00:00DENIED:BUILDING 11 / 2001 FBC
 1.PLAN SHEET A-0.0.0 PROJECT
 INFORMATION INDICATES TYPE VI,
 UNPROTECTED SPRINKLERED.PLEASE
 INDICATE WHICH SYSTEM WILL BE UTILITZED
 (13, 13R, 13D?).PLEASE NOTE,
 ADDITIONAL COMMENTS MAY BE GENERATED BY
 THE RESPONSES GIVEN.
  
 2.PLAN SHEET A-4.0.2 KEY NOTES/LEGEND,
 ITEM #25 '1HR CHASE REFER TO 11/A-13'.
 PLAN SHEET A-13 WAS NOT SUMBITTED FOR
 REVIEW.
  
 3.PLAN SHEET M0.1 THE EQUIPMENT
 SCHEDULE INDICATES AHU-1 AS A 5 TON
 UNIT.PER 2001 FMC 606.2.1, SYSTEMS
 WITH THE DESIGN CAPACITY SHALL HAVE DUCT
 SMOKE DETECTOR.NOTE #2 INDICATES AREA
 SMOKE DETECTORS BUT THE ELECTRICAL PLANS
 DO NOT REFLECT THIS.PLEASE CORRELATE.
  
 4.PLEASE CLARIFY FIRE RATING OF THE
 WALL SEPARATING THE GARAGE & THE
 RESIDENCE, DOES THE RATING CONTINUE TO
 THE SLAB OR STOP AT THE RATED CEILING?
  
 5.PLAN SHEET M1 INDICATES 3" EXHAUST
 DUCT PENETRATING THE RATED WALL.DUCT
 SHALL COMPLY WITH 2001 FMC 607.1.3 #3
 ITEMS 1 THROUGH 4.
  
 6.PLAN SHEET M3 DRYER EXHAUST EXCEEDS
 THE 25FT MAXIMUM LENGHT WITH A 5FT
 REDUCTION FOR EACH 90 PER 2001 FMC
 504.6.PLEASE NOTE, A SPECIFIC DRYER
 WITH THE CAPACITY GREATER THAN THE 25FT
 PER MANUFACTURERS SPECIFICATIONS MAY BE
 USED.PLEASE PROVIDE MANUFACTURERS
 SUBMITTAL DATA.
  
 7.R/A TRANSFER GRILLES SHALL BE SIZED
 IN ACCORDANCE WITH 2001 FMC 601.4
 EXCEPTION 2 & 3.
  
 8.MECHANICAL CLOSET SHALL BE
 CONSTRUCTED IN ACCORDANCE WITH 2001 FMC
 603.9.NO COMBUSTIBLES ALLOWED PER
 602.2.1.
  
 9.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2001 FMC
 TABLE 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.