| 2005-11-22 00:00:00 | DENIED:BUILDING 10 / 2001 FBC |
| | 1.PLAN SHEET A-0.0.0 PRODUCT |
| | INFORMATION INDICATES TYPE VI, |
| | UNPROTECTED SPRINKLERED.PLEASE |
| | INDICATE WHICH SYSTEM WILL BE UTILIZED - |
| | (13, 13R, 13D, ETC).PLEASE NOTE, |
| | ADDITIONAL COMMENTS MAY BE GENERATED BY |
| | THE RESPONSE GIVEN. |
| | |
| | 2.PLAN SHEET M1 INDICATES EXHAUST DUCT |
| | PENETRATING FIRE RATED WALLS.PLEASE |
| | SHOW COMPLIANCE WITH 2001 FMC 607.1.3 #3 |
| | ITEMS 1 THROUGH 4. |
| | |
| | 3.PLAN SHEET M1 UNIT #88 R/A JUMPER |
| | FROM THE GUEST SUITE IS NOT SIZED |
| | PROPERLY.R/A SHOULD BE A MINIMUM OF |
| | 12".PLEASE REVISE. |
| | |
| | 4.R/A TRANSFER GRILLES ARE NOT SIZE |
| | PROPERLY.PLEASE REFERENCE 2001 FMC |
| | 601.4 EXCEPTION #2 & 3 AND SIZE GRILLES |
| | ACCORDINGLY. |
| | |
| | 3.PLAN SHEET M3 THE DRYER EXHAUST |
| | DUCTS EXCEED THE 25FT REQUIREMENT WITH |
| | REDUCTIONS FOR THE 90'S PER 2001 FMC |
| | 504.6. |
| | |
| | 5.PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS IN ACCORDANCE WITH 2001 FMC |
| | TABLE 403.3. |
| | |
| | 6.PLEASE PROVIDE DETAIL FOR THE AHU |
| | LOCATED IN THE CLOSET.PLEASE NOTE, |
| | MECHANICAL CLOSET SHALL COMPLY WITH 2001 |
| | FMC 603.9 & 610.1.ABC.3.7 OF CHAPTER 13 |
| | OF THE 2001 FBC. |
| | |
| | 7.CONDENSATE SHALL TERMINATE A MINIMUM |
| | OF 12" AWAY FROM THE BUILDING STRUCTURE |
| | PER 2001 FBC 1503.4.4. |
| | |
| | 8.AUXILIARY DRAIN PAN WITH OVERFLOW |
| | PROTECTION REQUIRED PER 2001 FMC |
| | 307.2.3. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |