| 2005-10-17 00:00:00 | ********* UNSAT ********* |
| | |
| | |
| | 1)NOTE: PLEASE SEE PROJECT IS SUBMITTED |
| | AS CONDO'S YET ELECTRICALSERVICES |
| | PROVIDED IS SHOWN AS EACH WOULD BE A |
| | TOWNHOUSE (FEE SIMPLE). |
| | PLEASE SEE WATER SERVICE SHOWS |
| | MULTI-FAMILY BLDG. |
| | PLEASE KNOW, IF THESE AS MULTI-FAMILY |
| | CONDO BLDGS; ONE SERVICE FOR EACH BLDG |
| | IS PERMITTED,230.2,230.70MAINS WILL BE |
| | REQUIRED TO BE GROUPED PER 230.72. |
| | MCB'S SHOWN IN EACH GARAGE PANEL IS |
| | PERMITTED. |
| | PLEASE ADJUST SERVICE FOR BLDG. |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | AIC RATINGS ARE SHOWN FOR EACH PANEL, |
| | BUT WILL ALSO BE REQUIRED FOR MAINS.(NEW |
| | SERVICE). |
| | |
| | 3)NOTE: PLEASE CLARIFY LOCATION OF |
| | DISHWASHER RECEPT. APPEARS TO BE SHOWN |
| | BEHIND UNIT? THIS IS ONLY A NOTE: |
| | |
| | 4))NOTE: PLEASE SEE RECEPTS SERVING |
| | KITCHEN COUNTERSPACE TO MEET 210.52C- |
| | SEC'S 1,2,3,4 AND 5 |
| | PLEASE SEE PLANS REDLINED FOR SOME |
| | MISSING |
| | |
| | 5)NOTE: PLEASE SHOW OUTLET SPACING PER |
| | 210.52.DFOR MISSING BATH WITH 3' OF |
| | LAV EDGE. PLEASE ADD ONE OR MORE |
| | EXISTING TO CENTER. |
| | |
| | 6)NOTE: PLEASE SEE LOCATION WASHER/DRYER |
| | APPEARS TO SHOW ONLY ONE RECEPTS FOR |
| | DRYER, ALTHOUGH PANEL SCHEDULES SHOWS |
| | WASHER CIRUIT ALSO. |
| | |
| | 7 )NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS NEEDS |
| | TO BE SHOWN ABOVE THE GEN. KT/RECEPT |
| | LOADS. THIS SHOULD BE ABOVE THE FIGURED |
| | 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 8)NOTE: PLEASE LIST ALL THE REQUIRD ARC |
| | FAULT PROECTED CIRCUITS AS REQUIRED PER |
| | 2002 210.12 |
| | PLEASE KNOW, SD'S ARE BEING SHOWN |
| | CIRCUITED TO KITCHEN LIGHTING CIRCUIT, |
| | THIS IS OK, HOWEVER PLEASE KNOW, THIS |
| | WOULD ALSO REQUIRE ARC FAULT PROTECTION |
| | FOR THIS ADDITIONAL CIRCUIT. |
| | THIS IS ONLY A NOTE: |
| | |
| | 9)NOTE: PLEEASE SEE NFPA-72 (2002) |
| | EDITION,11.8.3.5. |
| | PLEASE PLACE NOTE ON PLANS WHICH STATES |
| | LOCATIONS OF SD'S TO BE A MIN OF 3' FROM |
| | BATH(S) AND KITCHEN DOORS AND 20' FROM |
| | KITCHEN COOKING APPLIANCES. |
| | ** PLEASE SEE EXCEPTION TO 20' FROM |
| | COOKING WITH TYPE OF SD USED.** |
| | PLEASE SEE PLANS SHOWS A SD IN KITCHEN |
| | AREA AT THIS TIME. |
| | |
| | 10)NOTE: PLEASE SEE MECHANICAL NOTES |
| | PERTAINING TO "DRYER BOOSTER FANS". |
| | AS PER MECHANICAL THESE MAY NOT BE |
| | PERMITTED AND ANY COMMENT THEY MAY HAVE |
| | WILL DIRECTLY AFFECT ELECTRICAL PLANS. |
| | THIS IS A NOTE, AS IT IS NOT AN NEC |
| | ISSUE. |
| | PLEASE SEE ALL SYSTEMS DO HAVE BE |
| | LISTED.110.3,90.7 |
| | PLEASE KNOW, THESE COULD NOT LOCATED ON |
| | THESE PLANS FOR UNITS "C" AND "D". |
| | |
| | 11)NOTE: PLEASE VERIFY OCP FOR AHU HEAT, |
| | PER 424.3B, MIN 125%. |
| | |
| | 12)NOTE: PLEASE SEE RECEPTS SHOWN IN |
| | CLOSET SBOVE SHELF AREA WILL NOT BE |
| | PERMITTED. THE RECEPT FOR LV PANEL MAY |
| | BE OCER DOOR OR OUT OF ROOM ONLY. |
| | THIS IS RELATED TO LIFE SAFTEY ISSUE AND |
| | CLOSE PROXIMITY TO EASILY IGNITIBLE |
| | MATERIALS.240.24D |
| | |
| | |
| | 13)NOTE: PLEASE SEE PLANS DO NOT |
| | INDICATE ANY ACCESIBLITY TO GFI RECEPTS |
| | SHOWN FOR JACUZZI/WHIRLPOOL TUB. |
| | |
| | 14)NOTE: PLEASE SEE 406.2B,210.21B3&4 |
| | WHICH REQUIRES THE MAX OCP FOR A 50A |
| | RANGE RECEPT TO BE 50A'S. PLEASE SEE A |
| | 2P-60A BRKR IS SHOWN. |
| | |
| | 15)NOTE: PLEASE PROVIDE AREA AND ROOM |
| | DESIGNATIONS ON PLANS. PLEASE SEE SOME |
| | ARE MISSING. |
| | THIS WILL ALSO BE REQUIRED TO DETERMINE |
| | CIRCUITING FOR DINING AREAS. |
| | |
| | 16)NOTE: PLEASE SEE PLANS REFERENCE THE |
| | 2000 NFPA 101, WHEN AS OF JAN 1ST 2005, |
| | THE 2003 NFPA-101 IS IN EFFECT. |
| | |
| | ** PLEASE KNOW, MANY ITEMS HAVE BEEN |
| | REDLINED ON PLANS FOR LOCATIONS OF |
| | NOTES. |
| | |
| | ** PLEASE KNOW, A REVIEW OF MAIN |
| | ELECTRICAL SERVICECAN NOT BE DONE AT |
| | THIS TIME, AS SERVICE WILL BE CHANGING. |
| | |
| | PLEASE SEE ANY OTHER POSSIBLE COMMENTS |
| | FROM OTHER TRADES WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | ** PLEASE SEE THIS MAY BE CONSIDERED A |
| | "THRESHOLD" PROJECT. IF SO, THREE SETS |
| | OF PLANS WILL BE REQUIRED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |