| Plan Review Notes For Permit 05091404 |
| Permit Number |
05091404 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-05-15 00:00:00 | ***** UNSAT **** | | | | | | | | | 1) NOTE: PLEASE SEE NO, SERVICE ENTRANCE | | | CONDUIT OR SERVICE ENTRANCE CONDUCTORS | | | ARE SHOWN ON RISER FROM FPL TO 1000A | | | SERVICE MAIN. | | | PLEASE SEE SEC'S ARE NOTED IN FAULT | | | CURRENT CALCS ONLY. | | | PLEASE ALSO VERIFY SIZE WHICH MAY ALSO | | | AFFECT NOTE #2. | | | | | | 2) NOTE: PLEASE SEE #4 GEC SHOWN, WHERE | | | A 3/0 MIN IS REQUIRED PER 250.66, BASED | | | ON THE SEC'S SHOWN IN FAULT CURRENT | | | CALCS. | | | | | | 3) NOTE: PLEASE SEE KEY PLAN INDICATE | | | THIS BEING A 5 UNITS BUILDING AND PLANS | | | IN TITLE BLOCKS ALSO INDOCATE THIS AS A | | | FIVE UNIT BLDG, HOWEVER PLEASE SEE RISER | | | SHOWN , ONLY PROVIDES SERVICE FOR FOUR | | | UNITS. | | | PLEASE CORRELATE AND ADJUST AS NEEDED. | | | 215.5 | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|