Plan Review Notes
Plan Review Notes For Permit 05091395
Permit Number 05091395
Review Stop E
Sequence Number 7
Notes
Date Text
2008-06-16 16:57:06** DENIEDREVISIONS**
  
 1) NOTE: PLEASE SEE ELECTRICAL RISE IS STILL SHOWING AN
 EQUIPMENT GROUNDING CONDUCTOR BEFORE THE FIRST MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED.THIS SAME COMMENT
 HAS BEEN MADE NUMEROUS TIMES.
 THIS CREATES OBJECTIONABLE CURRENTS. 250.6, 250.24
 PLEASE ADJUST PLANS.
  
 2) NOTE: PLEASE COORDINATE RISER AND PANELS. PANEL *B*
 NOW SHOWS A NEW SUB-POOL PANEL YET THE RISER DOES NOT
 INCLUDE THIS. PLEASE INCLUDE.
 215, 230, 240.4, 310.16, ETC
 FBC 106.3.5.4
  
 3) NOTE: PLEASE SEE THE PANELS INDICATE PANELS AS MLO
 (MAIN LUG ONLY) YET THE RISER SHOWS THESE AS CONTAINING
 2-POLE MAIN BREAKERS.
 230.70, 230.71, 230.72.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 4) NOTE: PLEASE CLARIFY WHERE THE DINING ROOM
 RECEPTACLES ARE CIRCUITED. PLEASE SEE 210.52B1, 408.4,
 210.11C1 AND 220.52.
 DINING AREA RECEPTACLES NEED TO BE SPECIFIED MEETING
 THE SECTIONS GIVEN ABOVE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  