| Plan Review Notes For Permit 05091395 |
| Permit Number |
05091395 |
|
| Review Stop |
E |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2008-06-16 16:57:06 | ** DENIEDREVISIONS** | | | | | | 1) NOTE: PLEASE SEE ELECTRICAL RISE IS STILL SHOWING AN | | | EQUIPMENT GROUNDING CONDUCTOR BEFORE THE FIRST MEANS OF | | | DISCONNECT WHICH IS NOT PERMITTED.THIS SAME COMMENT | | | HAS BEEN MADE NUMEROUS TIMES. | | | THIS CREATES OBJECTIONABLE CURRENTS. 250.6, 250.24 | | | PLEASE ADJUST PLANS. | | | | | | 2) NOTE: PLEASE COORDINATE RISER AND PANELS. PANEL *B* | | | NOW SHOWS A NEW SUB-POOL PANEL YET THE RISER DOES NOT | | | INCLUDE THIS. PLEASE INCLUDE. | | | 215, 230, 240.4, 310.16, ETC | | | FBC 106.3.5.4 | | | | | | 3) NOTE: PLEASE SEE THE PANELS INDICATE PANELS AS MLO | | | (MAIN LUG ONLY) YET THE RISER SHOWS THESE AS CONTAINING | | | 2-POLE MAIN BREAKERS. | | | 230.70, 230.71, 230.72. | | | FBC 106.1.2 FOR ADDITIONAL INFORMATION AND | | | COORDINATION. | | | | | | 4) NOTE: PLEASE CLARIFY WHERE THE DINING ROOM | | | RECEPTACLES ARE CIRCUITED. PLEASE SEE 210.52B1, 408.4, | | | 210.11C1 AND 220.52. | | | DINING AREA RECEPTACLES NEED TO BE SPECIFIED MEETING | | | THE SECTIONS GIVEN ABOVE. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|