| Plan Review Notes For Permit 05091395 |
| Permit Number |
05091395 |
|
| Review Stop |
E |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2007-07-18 14:09:22 | *** REDLINED PLANS**** | | | | | | | | | 1) NOTE: THE ELECTRICAL RISER DIAGRAM IS STILL SHOWING | | | AN "EQUIPMENT GROUNDING CONDUCTOR" AHEAD OF THE FIRST | | | MEANS OF DISCONNECT/MAINS. THIS NOT PERMITTED AND THIS | | | COMMENT HAS BEEN REPEATED ON SEVERAL REVIEWS. PLEASE | | | SEE 250.6 AND 250.24. IF THIS WAS INSTALLED, THIS WOULD | | | CREATE OBJECTIONABLE CURRENTS BETWEEN THE NEUTRAL AND | | | GROUDING. |
|