2007-07-18 14:09:22*** REDLINED PLANS****
  
  
 1) NOTE: THE ELECTRICAL RISER DIAGRAM IS STILL SHOWING
 AN "EQUIPMENT GROUNDING CONDUCTOR" AHEAD OF THE FIRST
 MEANS OF DISCONNECT/MAINS. THIS NOT PERMITTED AND THIS
 COMMENT HAS BEEN REPEATED ON SEVERAL REVIEWS. PLEASE
 SEE 250.6 AND 250.24. IF THIS WAS INSTALLED, THIS WOULD
 CREATE OBJECTIONABLE CURRENTS BETWEEN THE NEUTRAL AND
 GROUDING.