| Plan Review Notes For Permit 05091395 |
| Permit Number |
05091395 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2007-07-03 15:55:39 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE PREVIOUS NOTES AS THE SMOKE DEVICES | | | ARE STILL BEING SHOWN AS SD ON PLANS AND SYMBOL LEGEND | | | INDICATES SMOKE DETECTORS, HOWEVER THE NOTES ARE | | | SOUNDING LIKE THESE ARE SMOKE ALARMS WHICH ARE NOT THE | | | SAME AS SMOKE DETECTORS. | | | PLEASE SEE NFPA-72 DEFINITIONS. PLEASE CALL IF THERE | | | ARE ANY QUESTIONS ON THIS AS PREVIOUSLY NOTED. | | | | | | 2) NOTE: PLEASE SEE PLANS NOW HAVE A REVISED RISER | | | DIAGRAM WHICH DOES NOT MATCH WITH PLANS. PLEASE SEE | | | PLANS INDICATE TWO MAINS OUTSIDE, HOWEVER THE RISER | | | DOES NOT SHOW ANY MAINS AND THE PANELS ARE NOTED AS | | | 200A MLO PANELS? | | | 230.70,230.71,230.72, ETC | | | DEPENDING ON WHETHER OR NOT THE MAINS ARE OUTSIDE AN | | | *EQUIPMENT GROUNDING CONDUCTOR* IS STILL BEING SHOWN ON | | | RISER FROM METER TO PANEL?? | | | 250.6, 250.24 | | | ** PLEASE CALL TO GO OVER THIS IF THERE IS ANY | | | QUESTIONS AS PREVIOUSLY NOTED. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|