2007-04-26 08:54:06** UNSAT **
  
 1) NOTE: PLEASE SEE THAT THE REVISED PLANS APPEAR TO BE
 FOR FINALS, PLEASE SEE MECHANICAL COMMENTS.
 PLEASE SUBMIT REVISED PANEL SCHEDULES PER 408.4. PLEASE
 SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY FROM THE
 NEC.
 * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 2) NOTE: PLEASE NFPA-72 DEFINITIONS. IF THE SMOKE
 DEVICES ARE 120V WIRED INLINE WITH BATTERY BACK-UP
 WHICH DETECT AND SOUND AN ALARM, THEN THESE NEED TO BE
 SHOWN AS SA FOR SMOKE ALARMS.
 ONLY IF THESE ARE DEVICES WHICH ONLY DETECT AND SEND A
 SIGNAL OUT O AN ALARM SYSTEM WITH SOUNDING DEVICES
 WOULD THESE BE SHOWN AS SD. PLEASE KNOW IF THESE ARE
 INDEED LV SMOKE DETECTORS, PLEASE SHOW SOUNDING
 DEVICES.
 IF THERE ARE ANY QUESTIONS ON THIS, PLEASE CALL.
  
 3) NOTE: PLEASE REVISE THE LOAD CALCULATIONS IF NEED
 FOR THE TOTAL SQ FT AND LOADS AS CHANGED.
 220
  
 4) NOTE: PLEASE SEE PREVIOUS REVISED PLANS FROM 4/06
 FOR EQUIPMENT GROUNDIGN CONDUCTOR WHICH IS SHOWN BEFORE
 THE FIRST MEANS OF DISCONNECT.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  