| 2007-04-26 08:54:06 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE THAT THE REVISED PLANS APPEAR TO BE |
| | FOR FINALS, PLEASE SEE MECHANICAL COMMENTS. |
| | PLEASE SUBMIT REVISED PANEL SCHEDULES PER 408.4. PLEASE |
| | SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY FROM THE |
| | NEC. |
| | * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| | CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| | SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 2) NOTE: PLEASE NFPA-72 DEFINITIONS. IF THE SMOKE |
| | DEVICES ARE 120V WIRED INLINE WITH BATTERY BACK-UP |
| | WHICH DETECT AND SOUND AN ALARM, THEN THESE NEED TO BE |
| | SHOWN AS SA FOR SMOKE ALARMS. |
| | ONLY IF THESE ARE DEVICES WHICH ONLY DETECT AND SEND A |
| | SIGNAL OUT O AN ALARM SYSTEM WITH SOUNDING DEVICES |
| | WOULD THESE BE SHOWN AS SD. PLEASE KNOW IF THESE ARE |
| | INDEED LV SMOKE DETECTORS, PLEASE SHOW SOUNDING |
| | DEVICES. |
| | IF THERE ARE ANY QUESTIONS ON THIS, PLEASE CALL. |
| | |
| | 3) NOTE: PLEASE REVISE THE LOAD CALCULATIONS IF NEED |
| | FOR THE TOTAL SQ FT AND LOADS AS CHANGED. |
| | 220 |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS REVISED PLANS FROM 4/06 |
| | FOR EQUIPMENT GROUNDIGN CONDUCTOR WHICH IS SHOWN BEFORE |
| | THE FIRST MEANS OF DISCONNECT. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |