| 2006-03-20 00:00:00 | *** DENIED *** |
| | 1) ENERGY CALCULATIONS ARE CALLING FOR |
| | 104,200 TOTAL BTU'S. PLANS ARE CALLING |
| | FOR 108,000 TOTAL BTU'S.. THE PLANS CAN |
| | NOT CALL FOR MORE THAN THE ENERGY CAL'S. |
| | PLEASE CORRECT. |
| | |
| | 2) THE JOB ADDRESS MUST APPEAR ON THE |
| | MCCHANICAL PLANS. |
| | |
| | 3) ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. PER |
| | FBC 104.2.1 . |
| | |
| | 4) PLEASE SHOW THE TOTAL BTU'S. FOR EACH |
| | UNIT ON THE MECHANICAL PLANS. |
| | |
| | 5) SUPPLY AIR DUCT (FLEX) FROM AHU #1 TO |
| | THE MIXING BOX NEEDS TO SHOW THE SIZE. |
| | |
| | 6) OPEN DUCTS MAY NOT BE IN THE STORAGE |
| | AREA AS IT IS OPEN TO THE GARAGE. |
| | |
| | 7) PLANS ARE SHOWING A GAS FIRE PLACE |
| | THE MANUFACTURE'S SPECIFICATION'S |
| | SUBMITTED ARE FOR A WOODBURNING FIRE |
| | PLACE PLEASE CORRECT. |
| | |
| | 8) SUPPLY AIR DUCTS (FLEX) TO BEDROOMS 2 |
| | & 3 ALL NEED TO BE SIZED. |
| | |
| | 9) RETURN AIR TRANSFER DUCT (FLEX) TO |
| | MINI MASTER/OFFICE (GUEST) IS TO SMALL, |
| | SEE NOTE #11. |
| | |
| | 10) RETURN AIR TRANSFER DUCT (FLEX) TO |
| | DEN IS NOT SIZED, SEE NOTE #11. |
| | |
| | 11) BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |