Plan Review Notes
Plan Review Notes For Permit 05091395
Permit Number 05091395
Review Stop E
Sequence Number 3
Notes
Date Text
2006-03-18 00:00:00*** NOTE **
  
 PLEASE SEE PLANS WERE REVISED FROM
 "PROVISO" ON PREVIOUS REVIEW.
  
 1)PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTORS WERE ADDED TO RISER, HOWEVER
 THESE WERE ADDED TO CONDUITS FROM GUTTER
 TO MAINS(FIRST MEANS OF DISCONNECT)
 ALSO. PLEASE KNOW, "EQUIPMENT GROUNDING
 CONDUCTORS" ARE ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT. 250.6,250.24
 THIS DOES NOT NEED REVISING, ONLY IF
 REVISIONS ARE DONE AT A LATER DATE.
  
 *PLANS STAMPED, ALL OTHER NOTES FROM
 "PROVISO" WERE ADDRESSED 100%.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  