Plan Review Notes
Plan Review Notes For Permit 05091395
Permit Number 05091395
Review Stop E
Sequence Number 2
Notes
Date Text
2006-02-14 00:00:00********* PROVISO ***********
  
 ** IF PLANS COME BACK AS FAILED FOR ANY
 COMMENTS FROM OTHER TRADES, BE SURE TO
 MAKE THESE CORRECTIONS AT THIS TIME.****
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES DUE TO CHANGES
 IN PLANS.
  
 1)NOTE: PLEASE SEE PLANS INDICATE THE
 FAULT CURRENT CALCULATIONS , HOWEVER DO
 NOT INDICAT THE AIC RATINGS FOR THE
 MAINS. PLEASE SEE THE AFC AT SERVICE
 MAINS IS SHOWN @ 10,942, THEREFORE
 22,000 AIC RATED MAINS (MIN) ARE
 REQUIRED. PLEASE INDICATE.
 110.9,215.5
  
 2)NOTE: PLEASE SEE RISER SHOWS
 CONDUCTORS TO FPL TRANSFORMER AS 300MCM?
 PLEASE KNOW, IF THESE SEC'S ARE
 INSTALLED BY FPL, PLEASE DO NOT INDICATE
 SIZE. IF THE SEC'S ARE INSTALLED HOWEVER
 BY THE ELECTRICAL CONTRACTOR TO FPL,
 THESE CONDUCTORS SHALL BE SIZED AT A MIN
 PER 310.15B6. (400MCM MIN).
 400MCM IS SHOWN FROM METER TO GUTTER.
  
 3)NOTE: PLEASE SEE LOAD CALCUALTIONS
 SHALL INCLUDE LOADS FOR RECESSED LTS PER
 220.3B4, THESE LOADS ARE ABOVE THE MIN
 GENLT LIGHTING LOADS.
 PLEASE ADJUST AND REVISE LOAD
 CALCUALTIONS.
 PLEASE ALSO SEE THE RECESED LTS ARE NOW
 SHOWN ON FIXTURE LEGEND AS 100WATT,
 HOWEVER PLEASE VERIFY FIXTURE AS THE
 MAJORITY OF "AIR-TITE" RECESSED LTS DO
 NOT PERMIT IN EXCESS OF 75W'S.
 ADJUST LEGEND AS REQUIRED.
  
 4)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAINS TO
 PANELS. 250.110,250.122 ETC.
  
 5)NOTE: PLEASE SEE NFPA-72 11.8.3.5 FOR
 LOCATIONS OF SMOKE DETECTORS, PLEASE SEE
 ROOMS AND AREAS WITH VAULTED/TRAY
 CEILINGS. PLEASE SEE SD'S SHALL BE
 WITHIN 12" OF THE HIGHEST POINT OF THESE
 CEILINGS.
  
 6)NOTE: PLEASE SEE CODE REFERENCED FOR
 MIN CLEARENCES FOR DISCONNECTS AT CU'S
 STATES THE 2001 NEC. PLEASE SEE THIS
 SHOULD BE 2002 NEC.
  
 7)NOTE: PLEASE SEE MISSING RECEPT FOR
 2'OR MORE OF WALL IN FOYER.210.52
  
 ****************************************
 PLEASE SUBMIT THE ABOVE CORRECTIONS
 BEFORE ANY ROUGH SLAB INSPECTION IS
 CALLED IN.
 ***************************************
 IF PLANS FAIL OR GO OUT FOR COMMENTS
 FROM OTHER REVIEWER(S), PLEASE MAKE
 THESE CORRECTIONS AT THIS TIME.
 ***************************************
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  