| 2006-02-14 00:00:00 | ********* PROVISO *********** |
| | |
| | ** IF PLANS COME BACK AS FAILED FOR ANY |
| | COMMENTS FROM OTHER TRADES, BE SURE TO |
| | MAKE THESE CORRECTIONS AT THIS TIME.**** |
| | |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES DUE TO CHANGES |
| | IN PLANS. |
| | |
| | 1)NOTE: PLEASE SEE PLANS INDICATE THE |
| | FAULT CURRENT CALCULATIONS , HOWEVER DO |
| | NOT INDICAT THE AIC RATINGS FOR THE |
| | MAINS. PLEASE SEE THE AFC AT SERVICE |
| | MAINS IS SHOWN @ 10,942, THEREFORE |
| | 22,000 AIC RATED MAINS (MIN) ARE |
| | REQUIRED. PLEASE INDICATE. |
| | 110.9,215.5 |
| | |
| | 2)NOTE: PLEASE SEE RISER SHOWS |
| | CONDUCTORS TO FPL TRANSFORMER AS 300MCM? |
| | PLEASE KNOW, IF THESE SEC'S ARE |
| | INSTALLED BY FPL, PLEASE DO NOT INDICATE |
| | SIZE. IF THE SEC'S ARE INSTALLED HOWEVER |
| | BY THE ELECTRICAL CONTRACTOR TO FPL, |
| | THESE CONDUCTORS SHALL BE SIZED AT A MIN |
| | PER 310.15B6. (400MCM MIN). |
| | 400MCM IS SHOWN FROM METER TO GUTTER. |
| | |
| | 3)NOTE: PLEASE SEE LOAD CALCUALTIONS |
| | SHALL INCLUDE LOADS FOR RECESSED LTS PER |
| | 220.3B4, THESE LOADS ARE ABOVE THE MIN |
| | GENLT LIGHTING LOADS. |
| | PLEASE ADJUST AND REVISE LOAD |
| | CALCUALTIONS. |
| | PLEASE ALSO SEE THE RECESED LTS ARE NOW |
| | SHOWN ON FIXTURE LEGEND AS 100WATT, |
| | HOWEVER PLEASE VERIFY FIXTURE AS THE |
| | MAJORITY OF "AIR-TITE" RECESSED LTS DO |
| | NOT PERMIT IN EXCESS OF 75W'S. |
| | ADJUST LEGEND AS REQUIRED. |
| | |
| | 4)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS FROM MAINS TO |
| | PANELS. 250.110,250.122 ETC. |
| | |
| | 5)NOTE: PLEASE SEE NFPA-72 11.8.3.5 FOR |
| | LOCATIONS OF SMOKE DETECTORS, PLEASE SEE |
| | ROOMS AND AREAS WITH VAULTED/TRAY |
| | CEILINGS. PLEASE SEE SD'S SHALL BE |
| | WITHIN 12" OF THE HIGHEST POINT OF THESE |
| | CEILINGS. |
| | |
| | 6)NOTE: PLEASE SEE CODE REFERENCED FOR |
| | MIN CLEARENCES FOR DISCONNECTS AT CU'S |
| | STATES THE 2001 NEC. PLEASE SEE THIS |
| | SHOULD BE 2002 NEC. |
| | |
| | 7)NOTE: PLEASE SEE MISSING RECEPT FOR |
| | 2'OR MORE OF WALL IN FOYER.210.52 |
| | |
| | **************************************** |
| | PLEASE SUBMIT THE ABOVE CORRECTIONS |
| | BEFORE ANY ROUGH SLAB INSPECTION IS |
| | CALLED IN. |
| | *************************************** |
| | IF PLANS FAIL OR GO OUT FOR COMMENTS |
| | FROM OTHER REVIEWER(S), PLEASE MAKE |
| | THESE CORRECTIONS AT THIS TIME. |
| | *************************************** |
| | |
| | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS, PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |