Plan Review Notes
Plan Review Notes For Permit 05091395
Permit Number 05091395
Review Stop E
Sequence Number 1
Notes
Date Text
2005-10-07 00:00:00******** UNSAT ********
  
  
 1)PLEASE SEE ADDRESSING WILL STILL NEED
 TO BE ASSIGNED. PLEASE ALSO SEE FAC
 61G1-16.004 WHICH REQUIRES THE ADDRESS
 OF NEW HOME.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE SEE IT IS NOTED FOR AIC RATINGS
 FOR NEW PANELS, HOWEVER NOT SUBMITTED
 FOR MAINS.
  
 3)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 11.5.1.1
 PLEASE SEE MISSING SD LEADING TO FLOOR
 ABOVE IN THE VICINITY OF STAIRS LEADING
 TO FLR ABOVE. (IF OPEN CEILING, WALL
 MOUNT).
 PLEASE ALSO SEE NFPA-72 11.8.3.5, WHICH
 REQUIRES SD'S TO BE LOCATED 3' FROM BATH
 DOORS,KITCHEN DOORS AND 20' FROM COOKING
 APPLICANCES UNLESS MEETING THE
 EXCEPTIONS LISTED.
  
 4)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
 PLEASE SEE ISLAND.
  
 5)NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
 PLEASE SEE MISSING COUNTERSPACE GFI.
 REDLINED ON PLANS.
  
 6)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 PLEASE SEE REDLINED AREAS ON PLANS.
  
 7)NOTE: PLEASE CORRELATE RISER DIGRAM(S
 WITH PANEL SCHEDULE(S).
 PLEASE SEE RISER SHOWS PANELS AS 200A
 AND PANELS ARE SHOWN AS 150A.
 PLEASE SEE LOAD ON PANEL WHICH EXCEEDS
 150A RATING OF PANEL.
 240.4
  
 8)NOTE: PLEASE SEE 240.4,310.15B6,310.16
 FOR SIZING OF SERVICE ENTRANCE
 CONDUCTORS AND FEEDERS FOR PANELS.
 PLEASE SEE PANELS ARE SHOWN HAVING
 1/0'S(RATED AT 150A'S) WITH 200A
 OVERCURRENT PROTECTION.
 PLEASE SEE FEEDERS FROM MAINS TO PANELS.
 PLEASE ALSO SEE SEC'S ARE SHOWN AS
 300MCM WHICH ARE ONLY RATED FOR 285A'S.
 PLEASE SEE 310.15B6, WHICH REQUIRES
 400MCM MIN.
 PLEASE SEE CONDUCTORS FROM METER SHOULD
 BE RUN INDIVIDUALLY TO EACH MAIN
 DISCONNECTBY MEANS OF DOUBLE LUGS ON
 METER. PLEASE SEE MAIN DISCONNECT SHOULD
 NOT BE USED AS A RACEWAY.
 PLEASE SEE 300 MCM IS BEING SHOWN TO ONE
 MAIN AND 1/0'S ARE BEING SHOWN TO OTHER.
 PLEASE ADJUST
 PLEASE SEE 408.35
  
 9)NOTE: PLEASE SEE A/C CU'S ARE BEING
 NOTED AS HAVING DISCONNECTS, HOWEVER
 DISC'S SHOULD BE SHOWN IN ORDER TO
 VERIFY MIN CLEARENCE PER 110.26
 440.11.
  
 10)NOTE: PLEASE INDICATE THE REQUIRED
 GFI PROTECTION FOR JACUZZI TUB. 680.71
 (VERIFY 4KW AT 240V)
  
 11)NOTE: PLEASE SEE CONTTROL SW AT
 BOTTOM OF STAIRS DOES NOT INDICATE 3-WAY
 ,
 (MISPRINT). 210.70
 PLEASE SEE "MECH RM" WHICH CONTAINS
 WATER HEATER AND CENTRAL VAC, SHOWS A SW
 INSIDE FOR OUTSIDE LT, HOWEVER DOES NOT
 SHOW A LT INSIDE RM??
  
 12)NOTE: PLEASE SEE DIMMERS ARE SHOWN ON
 RECEPTS??
 PLEASE SEE HALF SWICHED RECEPTS ARE
 PERMITTED, HOWEVER JUST NOT ON A DIMMER.
  
 13)NOTE:PLEASE SEE NUMEROUS BRANCH
 CIRCUITS ON PANEL SCHEDULES WHICH
 CONTAIN 20A BRKRS(OCP) ON #14 AWG.
 PLEASE SEE 240.4, 310.16, WHICH REQUIRES
 #12 MIN FOR 20A OCP.
  
 14)NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR SHALL BE SIZED PER
 310.15B6/310.16/ 250.66
 (1/0 MIN).
  
 15)NOTE: PLEASE SEE NOTES 9 AND 10 OF
 ELECTRICAL NOTES. BOTH LANDSACPE
 LIGHTING AND LV WILL BE REQUIRED TO
 UNDER SEPARATE PERMIT IS NOT SHOWN ON
 PLANS.
  
 16)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 17)NOTE: PLEASE SEE PLANS DO NOT
 INDICATE THE 2ND DISCONNECT AS INDICATED
 ON RISER.
 215.5
  
 18)NOTE: PLEASE INCLUDE ALL ROOM AND
 AREA DESIGNATIONS ON PLANS.
  
 PLEASE BE SURE TO SEE ANY OTHER COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SEE ONE COPY OF ALL OLD/VOIDED
 SHEETS SHOULD BE SUBMITTED FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESTITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  