| 2005-10-07 00:00:00 | ******** UNSAT ******** |
| | |
| | |
| | 1)PLEASE SEE ADDRESSING WILL STILL NEED |
| | TO BE ASSIGNED. PLEASE ALSO SEE FAC |
| | 61G1-16.004 WHICH REQUIRES THE ADDRESS |
| | OF NEW HOME. |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | PLEASE SEE IT IS NOTED FOR AIC RATINGS |
| | FOR NEW PANELS, HOWEVER NOT SUBMITTED |
| | FOR MAINS. |
| | |
| | 3)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 11.5.1.1 |
| | PLEASE SEE MISSING SD LEADING TO FLOOR |
| | ABOVE IN THE VICINITY OF STAIRS LEADING |
| | TO FLR ABOVE. (IF OPEN CEILING, WALL |
| | MOUNT). |
| | PLEASE ALSO SEE NFPA-72 11.8.3.5, WHICH |
| | REQUIRES SD'S TO BE LOCATED 3' FROM BATH |
| | DOORS,KITCHEN DOORS AND 20' FROM COOKING |
| | APPLICANCES UNLESS MEETING THE |
| | EXCEPTIONS LISTED. |
| | |
| | 4)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | PLEASE SEE ISLAND. |
| | |
| | 5)NOTE: PLEASE SEE RECEPTS SERVING |
| | KITCHEN COUNTERSPACE TO MEET 210.52C- |
| | SEC'S 1,2,3,4 AND 5 |
| | PLEASE SEE MISSING COUNTERSPACE GFI. |
| | REDLINED ON PLANS. |
| | |
| | 6)NOTE: PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6`,12` RULE. |
| | PLEASE SEE REDLINED AREAS ON PLANS. |
| | |
| | 7)NOTE: PLEASE CORRELATE RISER DIGRAM(S |
| | WITH PANEL SCHEDULE(S). |
| | PLEASE SEE RISER SHOWS PANELS AS 200A |
| | AND PANELS ARE SHOWN AS 150A. |
| | PLEASE SEE LOAD ON PANEL WHICH EXCEEDS |
| | 150A RATING OF PANEL. |
| | 240.4 |
| | |
| | 8)NOTE: PLEASE SEE 240.4,310.15B6,310.16 |
| | FOR SIZING OF SERVICE ENTRANCE |
| | CONDUCTORS AND FEEDERS FOR PANELS. |
| | PLEASE SEE PANELS ARE SHOWN HAVING |
| | 1/0'S(RATED AT 150A'S) WITH 200A |
| | OVERCURRENT PROTECTION. |
| | PLEASE SEE FEEDERS FROM MAINS TO PANELS. |
| | PLEASE ALSO SEE SEC'S ARE SHOWN AS |
| | 300MCM WHICH ARE ONLY RATED FOR 285A'S. |
| | PLEASE SEE 310.15B6, WHICH REQUIRES |
| | 400MCM MIN. |
| | PLEASE SEE CONDUCTORS FROM METER SHOULD |
| | BE RUN INDIVIDUALLY TO EACH MAIN |
| | DISCONNECTBY MEANS OF DOUBLE LUGS ON |
| | METER. PLEASE SEE MAIN DISCONNECT SHOULD |
| | NOT BE USED AS A RACEWAY. |
| | PLEASE SEE 300 MCM IS BEING SHOWN TO ONE |
| | MAIN AND 1/0'S ARE BEING SHOWN TO OTHER. |
| | PLEASE ADJUST |
| | PLEASE SEE 408.35 |
| | |
| | 9)NOTE: PLEASE SEE A/C CU'S ARE BEING |
| | NOTED AS HAVING DISCONNECTS, HOWEVER |
| | DISC'S SHOULD BE SHOWN IN ORDER TO |
| | VERIFY MIN CLEARENCE PER 110.26 |
| | 440.11. |
| | |
| | 10)NOTE: PLEASE INDICATE THE REQUIRED |
| | GFI PROTECTION FOR JACUZZI TUB. 680.71 |
| | (VERIFY 4KW AT 240V) |
| | |
| | 11)NOTE: PLEASE SEE CONTTROL SW AT |
| | BOTTOM OF STAIRS DOES NOT INDICATE 3-WAY |
| | , |
| | (MISPRINT). 210.70 |
| | PLEASE SEE "MECH RM" WHICH CONTAINS |
| | WATER HEATER AND CENTRAL VAC, SHOWS A SW |
| | INSIDE FOR OUTSIDE LT, HOWEVER DOES NOT |
| | SHOW A LT INSIDE RM?? |
| | |
| | 12)NOTE: PLEASE SEE DIMMERS ARE SHOWN ON |
| | RECEPTS?? |
| | PLEASE SEE HALF SWICHED RECEPTS ARE |
| | PERMITTED, HOWEVER JUST NOT ON A DIMMER. |
| | |
| | 13)NOTE:PLEASE SEE NUMEROUS BRANCH |
| | CIRCUITS ON PANEL SCHEDULES WHICH |
| | CONTAIN 20A BRKRS(OCP) ON #14 AWG. |
| | PLEASE SEE 240.4, 310.16, WHICH REQUIRES |
| | #12 MIN FOR 20A OCP. |
| | |
| | 14)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| | CONDUCTOR SHALL BE SIZED PER |
| | 310.15B6/310.16/ 250.66 |
| | (1/0 MIN). |
| | |
| | 15)NOTE: PLEASE SEE NOTES 9 AND 10 OF |
| | ELECTRICAL NOTES. BOTH LANDSACPE |
| | LIGHTING AND LV WILL BE REQUIRED TO |
| | UNDER SEPARATE PERMIT IS NOT SHOWN ON |
| | PLANS. |
| | |
| | 16)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 17)NOTE: PLEASE SEE PLANS DO NOT |
| | INDICATE THE 2ND DISCONNECT AS INDICATED |
| | ON RISER. |
| | 215.5 |
| | |
| | 18)NOTE: PLEASE INCLUDE ALL ROOM AND |
| | AREA DESIGNATIONS ON PLANS. |
| | |
| | PLEASE BE SURE TO SEE ANY OTHER COMMENTS |
| | FROM OTHER TRADES WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SEE ONE COPY OF ALL OLD/VOIDED |
| | SHEETS SHOULD BE SUBMITTED FOR |
| | REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESTITATE IN CONTACTING |
| | THIS OFFICE. |
| | |