| 2005-11-30 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- ENGINEER SIGNED AND SEALED DRAWING IN | | | THE YEAR 2000. THIS IS YEAR 2005 AND | | | BUILDING CODES HAVE CHANGED. ENGINEER TO | | | UPDATE BUILDING CODE INFORMATION. SINCE, | | | PERMIT APPLICATION WAS SUBMITTED BEFORE | | | OCTOBER 1ST 2005, THEN, THE BUILDING | | | CODE IN EFFECT IS THE FBC 2001 AND THE | | | WIND LOAD TO HAVE IN CONSIDERATION IS | | | 140MPH 3 SECOND GUST. PROPER EDITION OF | | | ASCE TO BE USED IS ASCE 7-98. REVISE | | | PLANS AS REQUIRED. | | | *** NOTE: REVISE ORIGINAL DRAWINGS. | | | WHITE-OUT IS NOT ACCEPTABLE. ENGINEER | | | NEEDS TO RE-SIGN AND SEAL DRAWINGS AFTER | | | CORRECTIONS ARE DONE. | | | | | | 2- ENGINEER TO PROVIDE ALL HIS | | | INFORMATION IN DRAWINGS AS REQUIRED BY | | | CHAPTER 471 FLORIDA STATUTES AND FLORIDA | | | ADMINISTRATIVE CODE CHAPTER 61G15-23.002 | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712. |
|