| 2005-10-06 00:00:00 | *********** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE MOVESMOKE DETECTOR IN |
| | MASTER BEDROOM AREA TO BE LOCATED WITH |
| | THE HIGHEST POINT OF THE CEILING. THIS |
| | IS REQUIRED TO BE WITH 12" OF THE |
| | HIGHEST POINT OF A FLAT CEILING. |
| | NFPA-72 11.8.3.5 |
| | |
| | 2)NOTE: PLEASE SEE WATER HEATER #2 AS |
| | LISTED ON PANEL SCHEDULE "A" COULD NOT |
| | BE LCOATED ON PLANS. PLEASE SHOW. |
| | |
| | 3)NOTE: PLEASE SEE MIN OCP REQUIRED FOR |
| | POOL HEAT PUMP TO BE 125%. |
| | 680.9 |
| | |
| | 4)NOTE: PLEASE INDICATE ALL CONTINUOUS |
| | LOADS AT 125%. (POOL PUMP, HEAT PUMP). |
| | PLEASE SEE 215.3,230.42 ETC. |
| | PLEASE SEE POOL PANEL ALREADY SHOWS LOAD |
| | AT 59.45A'S. |
| | THIS PANEL, FEEDER, OCP ETC WILL BE |
| | REQUIRED TO BE INCREASED. PLEASE SEE |
| | PANEL MUST ALSO CONTAIN SPACE FOR FTURE |
| | LOAD. 90.8 |
| | PLEASE FOLLOW THROUGH WITH LOAD |
| | CALCULATIONSON PANEL "B". |
| | |
| | 5)NOTE: PLEASE CORRELATE AHU LOADS, |
| | PLEASE SEE LOAD CALCS FOR PANEL "B" |
| | SHOWS 6750 @65%?, YET PANEL SHOWS |
| | 7500VA? |
| | |
| | 6)NOTE: PLEASE LIST ALL THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUITS AS REQUIRED |
| | UNDER THE 2002 NEC. 210.12. |
| | SD'S,LTS, RECEPTS, FANS ETC ARE ALL |
| | REQUIRED TO HAVE ARC FAULT PROTECTION. |
| | |
| | 7)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS FROM MAINS TO SUB |
| | PANELS. |
| | 250.110,250.122 ETC. |
| | |
| | 8)NOTE: PLEASE CORRELATE THE NUMBER OF |
| | RECESSED LT FIXTURES ON PLANS WITH THE |
| | NUMBER OF FIXTURES INDICATED IN LOAD |
| | CALCULATIONS. |
| | 215.5 |
| | |
| | 9)NOTE: PLEASE SEE 410.8 FOR MIN |
| | CLEARENCE REQUIRED FOR LT IN PANTRY. |
| | PLEASE KNOW, PANTRIES ARE LIKELY TO |
| | CONTAIN COMBUSTIBLES. |
| | |
| | 10)NOTE: PLEASE SEE PLANS APPEAR TO HAVE |
| | A GFI RECEPT MISSING ALONG KITCHEN |
| | COUNTERSPACE. |
| | PLEASE SEE 210.52C1 |
| | |
| | 11)NOTE: PLEASE SEE GDO'S ARE SHOWN ON |
| | PANEL SCHEDULES, HOWEVER THESE RECEPTS |
| | COULD NOT BE LOCATED ON PLANS. |
| | |
| | ** PLEASE SEE MOST OF THE ITEMS ABOVE |
| | HAVE BEEN REDLINED ON ONE SET OF PLANS |
| | FOR AREAS OF COMMENTS. |
| | |
| | ** PLEASE BE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS FROM SETS AND AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |