| Date |
Text |
| 2005-12-07 00:00:00 | REDLINED PLANS. | | | | | | | | | ** SECTION 210.8(B)(3) IS NEW FOR THE | | | 2002 CODE AND REQUIRES ALL 15- AND | | | 20-AMPERE, 125-VOLT RECEPTACLES IN | | | NONDWELLING-TYPE KITCHENS TO BE GFCI | | | PROTECTED. THIS REQUIREMENT APPLIES TO | | | EACH AND EVERY 15- AND 20-AMPERE, | | | 125-VOLT KITCHEN RECEPTACLE, WHETHER OR | | | NOT THE RECEPTACLE SERVES COUNTERTOP | | | APPLIANCES. |
|