Plan Review Notes For Permit 05091323
Permit Number 05091323
Review Stop E
Sequence Number 2
Notes
Date Text
2005-12-07 00:00:00REDLINED PLANS.
  
  
 ** SECTION 210.8(B)(3) IS NEW FOR THE
 2002 CODE AND REQUIRES ALL 15- AND
 20-AMPERE, 125-VOLT RECEPTACLES IN
 NONDWELLING-TYPE KITCHENS TO BE GFCI
 PROTECTED. THIS REQUIREMENT APPLIES TO
 EACH AND EVERY 15- AND 20-AMPERE,
 125-VOLT KITCHEN RECEPTACLE, WHETHER OR
 NOT THE RECEPTACLE SERVES COUNTERTOP
 APPLIANCES.