| 2005-10-11 00:00:00 | ********** UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE RISER DIAGRAM WHICH |
| | SHOWS #4 FOR NEW SUB PANEL "B". PLEASE |
| | SEE 240.4,310.16, #4 IS ONLY RATED AT |
| | 85A'S, WHICH WOULD INDICATE 90A OCP FOR |
| | FEED, HOWEVER PANEL SCHEDULE "A" SHOWS |
| | 100A OCP. |
| | PLEASE ALSO SEE PANEL "A" SHOWS #3. |
| | PLEASE CORRELATE AND ADJUST. |
| | |
| | 2)NOTE: PLEASE CLARIFY METHID OF |
| | EQUIPMENT GROUNDING BETWEEN MAIN AND |
| | PANEL"A" AND PANEL "A" AND PANEL "B> |
| | 250.110,250.24, SIZED PER 250.122 |
| | |
| | 3)NOTE: PLEASE PROVIDE LOAD CALCULATIONS |
| | FOR EXISTING SERVICE/GUTTER. IT IS KNOW |
| | THAT THE SERVICE AT THIS LOCATION IS |
| | EXTREMELY LOADEDAND CLOSE TO MAX |
| | RATING. |
| | 215.5,220 |
| | |
| | 4)NOTE: PLEASE SEE 700.12E WHICH |
| | REQUIRES EMERGENCY/EXIT LTS TO BE WIRED |
| | AHEAD OF THE LOCAL "AREA" LIGHTING. |
| | SHOWN ON "B-10", HOWEVER THIS APPEARS |
| | THIS SHOULD BE "B-6". |
| | |
| | 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | |
| | ** PLEASE BE SURE TO SEE ANY POSSIBLE |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE BE SURE TO SUBMIT ONE COPY OF ANY |
| | VOIDED/REMOVED SHEETS SEPARATELY FOR |
| | REFERENCE. |
| | |