2005-10-13 00:00:00IF THE "PANEL" SHOWN ON THE SCHEMATIC
 IS INSTALLED UNDER THIS PERMIT, PLEASE
 SUBMIT DETAILS FOR THE PANEL SHOWN ON
 THE SCHEMATIC, FEEDER AND CONDUIT SIZE
 AND TYPE, PANEL RATING AND OCP, PANEL
 SCHEDULE AND COMPUTED LOAD, AS A
 REVISION TO THIS PLAN , PRIOR TO CALLING
 FOR AN ELECTRICAL INSPECTION.
  