| Plan Review Notes For Permit 05091307 |
| Permit Number |
05091307 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-10-13 00:00:00 | IF THE "PANEL" SHOWN ON THE SCHEMATIC | | | IS INSTALLED UNDER THIS PERMIT, PLEASE | | | SUBMIT DETAILS FOR THE PANEL SHOWN ON | | | THE SCHEMATIC, FEEDER AND CONDUIT SIZE | | | AND TYPE, PANEL RATING AND OCP, PANEL | | | SCHEDULE AND COMPUTED LOAD, AS A | | | REVISION TO THIS PLAN , PRIOR TO CALLING | | | FOR AN ELECTRICAL INSPECTION. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|