| Plan Review Notes For Permit 05091301 |
| Permit Number |
05091301 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-28 00:00:00 | *** DENIED *** | | | 1) NEED TWO SETS OF MECHANICAL PLANS | | | SUBMITTED. NOTE MECH. PLANS DO NOT | | | COINCIDE WITH MASTER PLANS. | | | 2) ENERGY CALCULATIONS ON FILE CALL FOR | | | A 3 TON, & A 5 TON A/C SYSTEM, | | | MECHANICAL PLANS ARE CALLING FOR A 3 1/2 | | | TON, & A 5 TON A/C SYSTEM (THEY MUST | | | COINCIDE). | | | 3) NEED MANUAL 'J' CALCULATIONS PER 2001 | | | FBC CH. 13 SECTION 607.1.ABC.1 . | | | 4) GAS BBQ GRILL IN COVERED PORCH NEEDS | | | AN APPROVED EXHAUST HOOD, PER 2001 FBC/M | | | 505.3 . | | | 5) A/C UNITS WILL NEED PROGRAMMABLE | | | THERMOSTATS PER ENERGY CALCULATIONS. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|