Plan Review Notes
Plan Review Notes For Permit 05091301
Permit Number 05091301
Review Stop M
Sequence Number 1
Notes
Date Text
2005-09-28 00:00:00*** DENIED ***
 1) NEED TWO SETS OF MECHANICAL PLANS
 SUBMITTED. NOTE MECH. PLANS DO NOT
 COINCIDE WITH MASTER PLANS.
 2) ENERGY CALCULATIONS ON FILE CALL FOR
 A 3 TON, & A 5 TON A/C SYSTEM,
 MECHANICAL PLANS ARE CALLING FOR A 3 1/2
 TON, & A 5 TON A/C SYSTEM (THEY MUST
 COINCIDE).
 3) NEED MANUAL 'J' CALCULATIONS PER 2001
 FBC CH. 13 SECTION 607.1.ABC.1 .
 4) GAS BBQ GRILL IN COVERED PORCH NEEDS
 AN APPROVED EXHAUST HOOD, PER 2001 FBC/M
 505.3 .
 5) A/C UNITS WILL NEED PROGRAMMABLE
 THERMOSTATS PER ENERGY CALCULATIONS.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.