| Plan Review Notes For Permit 05091299 |
| Permit Number |
05091299 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-10-12 00:00:00 | *** DENIED *** | | | 1) EQUIP. INFO. FOR A/C SYSTEM RHEEM | | | COND. RMAB-048J IS MISSING ON PLANS. | | | 2) NEED MANUFACTURE'S SPEC. SHEETS FOR | | | GAS FIREPLACE. | | | 3) NEED COMBUSTION AIR CALCULATIONS FOR | | | GAS FIREPLACE. | | | 4) SUPPLY AIR DUCT ON 2ND. FLOOR MAIN | | | HOUSE, FROM AHU TO 1ST. FLOOR IS NOT | | | SIZED. | | | 5) PROVIED AUXILIARY DRAIN PANSWITH | | | DRAIN PROTECTION UNDER AHU'S PER 2001 | | | FBC/M 307.2.3 . | | | 6) DRAIN LINES FOR AHU'S NOT SHOWING ON | | | PLANS PER 2001 FBC/M 307.2 . | | | 7) DRYER TO BE VENTED PER 2001 FBC/M 504 | | | . | | | 8) PLEASE SEE ELECTRICAL REVIEW | | | REGUARDING A/C SYSTEMS. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|