| 2005-10-06 00:00:00 | ********* UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SEE BUILDING REVIEW |
| | COMMENTS FOR ADJUSTED VALUE FOR SCOPE OF |
| | WORK. |
| | 104.6.5, FBC, CITY-WIDE ADMINISTRATIVE |
| | CODE. |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | AIC RATING FOR MAIN WAS SUBMITTED, |
| | HOWEVER PLEASE INDICATE PANELS ALSO. |
| | PLEASE SEE FOLLWING COMMENT. |
| | |
| | 3)NOTE: PLEASE PROVIDE MORE INFORMATION |
| | ON PANELS. TYPE, VOLTAGE, ETC. MCB, MLO |
| | ETC.215.5 |
| | PLEASE SEE FOLLOWING COMMENTS. |
| | |
| | 4)NOTE: PLEASE SHOW AND IDENTIFY ALL |
| | PANELS, DISCONNECTS ETC ON PLANS. |
| | COULD NOT LOCATE DISCONNECT SHOWN ON |
| | RISER FOR PANEL "C" ON PLANS. |
| | COULD NOT LOCATE POOL PANEL? |
| | PLEASE SEE NEXT COMMENT. |
| | |
| | 5)NOTE: PLEASE SEE PLANS WHICH INDICATE |
| | METER/MAIN AT DETACHED BLDG, HOWEVER |
| | PANEL "C" SEEMS TO BE SHOWN WITH THE |
| | GROUNDING ELECTRODE SYSTEM WHICH IS |
| | ACTUALLY REQUIRED FOR PANELS "A" AND "B" |
| | AT MAIN HOUSE. |
| | 250.32 |
| | |
| | 6)NOTE: PLEASE SEE PANELS AT MAIN HOUSE |
| | SHALL INDICATE MAIN CIRCUIT BREAKER(S) |
| | (MCB) FOR DISCONNECTING MEANS AT MAIN |
| | HOUSE.225.31 |
| | THE GROUNDING ELECTRODE ATTACHMENTS FROM |
| | PREVIOUS NOTE SHALL BE ATTACHED TO THESE |
| | PANELS. |
| | |
| | 7)NOTE: PLEASE SEE 400A METER/MAIN SHALL |
| | INDICATE 400A MCB. PLEASE SEE ONE 200A |
| | BRKR IN THIS PANEL IS SHOWN AS MAIN |
| | BREAKER?? |
| | PLEASE ALSO SEE PANEL "C" IS NOT |
| | SHOWN/IDENTIFIED ON SCHEDULE FOR |
| | METER/MAIN. |
| | 215.5 |
| | |
| | 8)NOTE: PLEASE SEE PLANS FOR NUMEROUS |
| | SMOKE DETECTORS MISSING. |
| | PLEASE SEE NFPA-72 11.5.1.1 WHICH |
| | REQUIRES SD'S INSIDE AND OUTSIDE ALL |
| | SLEEPING RMS OR ADAPTABLE SLEEPING |
| | RMS(THOSE WITH BATHS OR CLOSETS). |
| | PLEASE SEE SD'S REQUIRED ON ALL LEVELS |
| | OF A MULTI-LEVEL DWELLING. |
| | PLEASE SEE SD IN MASTER BEDRM SAHLL BE |
| | REQUIRED AT FIRST FLR AND SECOND FLR. |
| | SINCE THIS IS AN OPEN RM, SD FOR FIRST |
| | FLR SHALL BE WALL MOUNTED IN THE |
| | VICINITY OF STAIRS LEADING TO FLR ABOVE. |
| | PLEASE ALSO SEE AREA FOR OTHER STAIRS |
| | LEADING TO FLR ABOVE. MAIN HOUSE, |
| | DETACHED CABANA. |
| | PLEASE SEE SD'S HAVE BEEN REDLINED ON |
| | PLANS FOR ALL LOCATIONS REQUIRED. |
| | |
| | 9)NOTE: PLEASE SEE 210.8A2, WHICH |
| | REQUIRES ALL RECEPTS IN GARAGE TO BE |
| | GFI. |
| | |
| | 10)NOTE: PLEASE SEE MISSING GFI RECEPTS |
| | FOR A/C EQUIPMENT. |
| | 210.8A, 210.63 |
| | |
| | 11)NOTE: PLEASE SEE NUMEROUS GFI RECEPTS |
| | MISSING ALONG KITCHEN COUNTERSPACES. |
| | 210.8A6, 210.52C1-5 |
| | PLEASE SEE A GFI WILL BE REQUIRED ON 2ND |
| | FLR "NOOK" AREA OF CABANA ALSO ABOVE |
| | DISHWASHER. |
| | |
| | 12)NOTE: PLEASE SEE NUMEROUS MISSING |
| | RECEPTS REQUIRED PER 210.52. 2', 6', 12' |
| | OF WALL SPACES. |
| | PLEASE SEE RAIL AREA AT 2ND FLR IS |
| | CONSIDERED WALL SPACE AND FLR RECEPTS |
| | WILL BE REQUIRED PER 210.52 |
| | PLEASE CLARIFY AREA T SUNK-IN LIV RM |
| | NEXT TO FIRE PLACE. ?? WALL SPACE?? |
| | PLEASE SEE MANY OF THE ABOVE HAVE BEEN |
| | REDLINED ON PLANS WHERE REQUIRED. MANY |
| | OF MISSING. |
| | |
| | 13)NOTE: PLEASE SEE MISSING HALLWAY |
| | RECEPTS PER 210.52H |
| | REDLINED. |
| | |
| | 14)NOTE: PLEASE SEE MISSING GFI RECEPTS |
| | PER 210.52D,210.11C3,210.8 |
| | |
| | 15)NOTE: PLEASE SEE ALL RECEPTS WITIN 6' |
| | OF SINKS SHALL BE GFI/GFI PROTECTED. |
| | (LAUNDRY RM )210.8A |
| | |
| | 16)NOTE:PLEASE SEE MISSING EGRESS |
| | LIGHTING CONTROL AT LOCATION OF MASTER |
| | BEDRM, HALL/LIVING RM ETC. |
| | 210.70 |
| | PLEASE CORRELATE SWITCHES SHOWN FOR |
| | MASTER BEDRM LTS, SCONCES ETC. |
| | STAIR-WAY LT CONTROL. GRADE LEVEL |
| | ACCESS. MOST HAVE BEEN REDLINED ON PLANS |
| | AT LOCATIONS MENTIONED. |
| | LS 101 7.8 |
| | |
| | 17)NOTE: PLEASE LIST THE REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S) PER |
| | 210.52D,210.11C3. PLEASE SEE THESE ARE |
| | REQUIRED TO BE 20A AND #12 AWG. |
| | |
| | 18)NOTE: PLEASE SEE NO SWITCHES SHALL BE |
| | LOCATED WITHIN THE 3' ZONE OF A |
| | TUB/JACUZZI TUB. PLEASE SEE NO RECEPTS |
| | SHALL BE LOCATED WITH 3' OF TUB. |
| | PLEASE SEE REDLINED PLANS FOR MASTER |
| | BATH RM LT CONTROLS, BEDRM #3. |
| | 680.71, 410.4 |
| | |
| | 19)NOTE: PLEASE SEE SYMBOL FOR JACUZZI |
| | TUB/WHIRLPOOL TUB IS BEING SHOWN AS |
| | 220V, HOWEVER THIS IS NOT LOCATED ON |
| | PANEL SCHEDULE(S) OR LOAD CALCS?? |
| | PLEASE SEE 680.71, FOR REQUIRED GFI |
| | PROTECTION. |
| | PLEASE ALSO ADJUST LOAD CALCS. |
| | |
| | 20)NOTE: PLEASE SEE A GDO IS SHOWN ON |
| | LOAD CALCS FOR PANELS LOCATED ON MAIN |
| | HOUSE,HOWEVER NO GDO COULD BE LOCATED AT |
| | MAIN HOUSE? |
| | PLEASE SEE DETACHED "GARAGE" DOES NOT |
| | INDICATE OR SHOW A GARAGE DOOR OR GDO. |
| | PLEASE INCLUDE IN PANEL "C" , LOADS ETC. |
| | 215.5 |
| | |
| | 21)NOTE: PLEASE SEE MISSING DISCONNECTS |
| | REQUIRED FOR WATER HEATERS. |
| | 422.31 |
| | |
| | 22)NOTE: PLEASE SEE MISSING |
| | DISCONNECTING MEANS REQUIRED FOR AHU'S , |
| | PER 440.11 |
| | PLEASE SEE MIN CLEARENCES REQUIRED PER |
| | 110.26. |
| | PLEASE ALSO SEE DISCONNECT CLEARENCE |
| | REQUIRED FOR CU'S OUTSIDE. |
| | PLEAS ADJUST. |
| | |
| | 23)NOTE: PLEASE CORRELATE ALL A/C LOADS |
| | ON LOAD CALCS, NUMBER OF UNITS INDICATED |
| | ON PANEL SCHEDULE(S) AND NUMBER OF UNITS |
| | SHOWN ON PLANS. |
| | PLEASE SEE LOAD CALCS FOR MAIN HOUSE |
| | INDICATE 4-5 AHU'S??? WHEREAS PLANS SHOW |
| | 3-CU'S AND PANEL SCHEDULES ONLY INDICATE |
| | 2 UNITS TOTAL??? |
| | 215.5 ETC. |
| | |
| | 24)NOTE: PLEASE SEE PREVIOUS NOTE, ONCE |
| | A/C UNITS HAVE BEEN CORRELATED, PLEASE |
| | SEE 424.3B FOR MIN OCP OF 125% OF HEAT |
| | KW LOAD. PLEASE ALSO NOTE, MAX OCP OF |
| | 150% |
| | PLEASE ADJUST OCP AND CONDUCTORS AS |
| | LISTED ON PLANS. |
| | PLEASE SEE LOAD CALCS AND KW RATING |
| | SHOWN. |
| | |
| | 25)NOTE: PLEASE PROVIDE LOADS ON EACH |
| | PANEL.PLEASE SEE MISSING POOL PANEL, |
| | PANEL SCHEDULE. LOADS ARE SHOWN ON MAIN |
| | CALCS, HOWEVER THESE LOADS CAN NOT BE |
| | VERIFIED. |
| | PLEASE KNOW, ALL CONTINUOUS LOADS SHALL |
| | BE SHOWN AT 125%. (3 OR MORE HRS). |
| | POOL PUMP, HEAT PUMPS? |
| | 215.3,230.42 ETC. |
| | |
| | 26)NOTE: PLEASE SEE 250.66, 310.15B6 FOR |
| | MIN GROUNDING ELECTRODE CONDUCTOR. |
| | PLEASE SEE 1/0 MIN AT MAIN SERVICE AT |
| | DETACHED GARAGE. PLEASE ALSO SEE MIN AT |
| | MAIN HOUSE SHALL BE #2 |
| | |
| | 27)NOTE: PLEASE CORRELATE ALL DEDICATED |
| | CIRCUITS WHICH ARE SHOWN ON PLANS, |
| | HOWEVER NOT ALL ARE LISTED ON PANEL |
| | SCHEDULES. |
| | COULD NOT LOCATE ELEC OVEN ON PLANS? |
| | PLEASE MOVE ANY 220V OUTLETS FOR |
| | OVENS/RANGES DIRECTLY BEHIND UNITS. |
| | PLEASE SEE PLANS SHOW TWO RANGES, HOWEVR |
| | PANEL SCHEDULE ONLY SHOWS ONE?? |
| | PLEASE SEE ZONING NOTES. |
| | PLEASE SEE # OF ICE MAKERS LISTED ON |
| | LOAD CALCS, YET ONLY ONE DEDICATED |
| | CIRCUIT IS SHOWN ON PANEL SCHEDULE? |
| | PLEASE CORRELATE OTHERS. |
| | |
| | 28)NOTE: PLEASE VERIFY WHAT APPEARS TO |
| | BE A 220V RECEPT SHOWN IN PANTRY.?? |
| | PLEASE ALSO CALRIFY RECEPTS SHOWN IN |
| | CLOSETS? ABOVE? BELOW? COMBUSTIBLES.? |
| | PLEASE BE AWARE OF INTENDED USE OF THESE |
| | WHICH MAY NOT PERMIT THESE TO BE LOCATED |
| | IN CLOSETS. |
| | 240.24 ETC |
| | |
| | 29)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 30)NOTE: PLEASE SEE DISHWASHER IS SHOWN |
| | ON PLANS FOR CABANA, HOWEVER PANEL |
| | SCHEDULE AND LOAD CALCS DO NOT INDICATE |
| | THE SAME.?? |
| | PLEASE ALSO SEE MICROWAVE SHOWN ON PANEL |
| | SCHEDULE, BUT NOT ON PLANS FOR DEDICATED |
| | CIRCUIT?? |
| | |
| | 31)NOTE: PLEASE SEE GFI SHOWN ON |
| | COUNTERSPACE IN DETACHED CABANA, IS |
| | SHOWN AS "WP" ?? THIS IS PERMITTED, |
| | HOWEVER NOT REQUIRED. |
| | 210.8A6 |
| | |
| | 32)NOTE: PLEASE IDENTIFY OTHER 220V |
| | RECEPTS SHOWN ON PLANS , HOWEVER THESE |
| | ARE NO LISTED IN LOAD CALCS OR ON PANEL |
| | SCHEDULES?? |
| | PLEASE SEE CABANA AND MAIN HOUSE. |
| | |
| | |
| | PLEASE CORRELATE ALL A/C EQUIPMENT WITH |
| | MECHANICAL PLANS. |
| | THESE DO NOT MATCH. |
| | |
| | PLEASE KNOW, MANY OF THE ABOVE ITEMS |
| | HAVE BEEN REDLINED ON PLANS AT LOCATIONS |
| | OF NOTES. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM |
| | SETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. PLEASE ONLY SUBMIT ONE SET OF |
| | OLD/VOIDED SHEETSREQUIRED FOR |
| | REFERENCE. |
| | |
| | PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS , |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REIVEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |