| Plan Review Notes For Permit 05091266 |
| Permit Number |
05091266 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-03-01 00:00:00 | *** DENIED *** | | | 1) ENERGY CALCULATIONS ARE CALLING FOR | | | AN ELECTRIC HEAT PUMP UNIT, MECHANICAL | | | PLANS ARE CALLING FOR A 5 KW ELECTRIC | | | RESISTANCE HEATER, AND THE ELECTRICAL | | | PLANS ARE CALLING FOR A 10 KW ELECTRIC | | | RESISTANCE HEATER. PLEASE CORRECT SO ALL | | | COINCIDE. | | | | | | 2) ENERGY CALCULATIONS ARE CALLING FOR A | | | 9.80 SEER A/C SYSTEM (THE MINIMUM | | | ALLOWABLE IS 10 SEER), THE MECHANICAL | | | PLANS EQUIPMENT LIST IS CALLING FOR A 18 | | | SEER. THE TWO MUST COINCIDE PLEASE | | | CORRECT. | | | | | | 3) NEED TO SHOW ON MECH. PLANS THE | | | RETURN AIR GRILL SIZE (A 5 TON SYSTEM | | | REQUIRES ABOUGHT 725 SQUARE INCHES). | | | | | | 4) CHECK WITH THE MANUFACTURE'S | | | SPECIFICATION'S A 7/8 SUCTION LINE MAY | | | BE TO SMALL FOR A 5 TON SYSTEM, CORRECT | | | IF NECESSARY. | | | | | | 5) THE MECHANICAL PLANS NEED THE | | | ENGINEER'S SEAL ON THEM, PER F.S. | | | 61G1-16.002 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|