2006-03-01 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR
 AN ELECTRIC HEAT PUMP UNIT, MECHANICAL
 PLANS ARE CALLING FOR A 5 KW ELECTRIC
 RESISTANCE HEATER, AND THE ELECTRICAL
 PLANS ARE CALLING FOR A 10 KW ELECTRIC
 RESISTANCE HEATER. PLEASE CORRECT SO ALL
 COINCIDE.
  
 2) ENERGY CALCULATIONS ARE CALLING FOR A
 9.80 SEER A/C SYSTEM (THE MINIMUM
 ALLOWABLE IS 10 SEER), THE MECHANICAL
 PLANS EQUIPMENT LIST IS CALLING FOR A 18
 SEER. THE TWO MUST COINCIDE PLEASE
 CORRECT.
  
 3) NEED TO SHOW ON MECH. PLANS THE
 RETURN AIR GRILL SIZE (A 5 TON SYSTEM
 REQUIRES ABOUGHT 725 SQUARE INCHES).
  
 4) CHECK WITH THE MANUFACTURE'S
 SPECIFICATION'S A 7/8 SUCTION LINE MAY
 BE TO SMALL FOR A 5 TON SYSTEM, CORRECT
 IF NECESSARY.
  
 5) THE MECHANICAL PLANS NEED THE
 ENGINEER'S SEAL ON THEM, PER F.S.
 61G1-16.002 .
  