Plan Review Notes
Plan Review Notes For Permit 05091266
Permit Number 05091266
Review Stop E
Sequence Number 2
Notes
Date Text
2006-02-28 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE CONDUIT AND CONDUCTOR
 SIZES FOR THE RISER. ALSO AIC RATING OF
 THE EQUIPMENT PER 110.9 & 10.
  
 2} THE BREAKER AND WIRE SIZE IS
 INCORRECT FOR THE LOAD INDICATED ON THE
 SCHEDULE. CIRCUIT #2-4 AHU.
  
 3} PLEASE NOTE THE OCP (60) IS TOO LARGE
 FOR THE CONDUCTOR SIZE (#8) FOR THE
 RANGE.
  
 4} CIRCUIT #28 , MASTER BATH, MUST
 COMPLY WITH 210.11(C)(3).
  
 5} PLEASE SEE NOTE #3 REGARDING KITCHEN
 GFI SHOULD INDICATE ALL COUNTERTOP
 RECEPTACLE PER 210.8(A)(6).
  
 6} THERE ARE RECEPTACLES LOCATED
 THROUGHOUT THE EXISTING HOUSE, BUT THEY
 DO NOT SHOW CODE COMPLIANCE WITH ARTICLE
 210.52. INDICATE IF THESE ARE NEW OR
 EXISTING. IF PART OF THIS APPLICATION
 SHOW EXISTING DEVICES AS WELL SO THAT
 COMPLIANCE MAY BE DETERMINED.
  
 7} THE ENGINEERING FIRM ADVERTISING AS A
 CORPORATION ON THE TITLE BLOCK, MUST
 INCLUDE THEIR REQUIRED CERTIFICATE OF
 AUTHORIZATION NUMBER ON THE TITLE BLOCK
 PER 61G15-23.002, FACODE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  