| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} INDICATE THE CONDUIT AND CONDUCTOR |
| | SIZES FOR THE RISER. ALSO AIC RATING OF |
| | THE EQUIPMENT PER 110.9 & 10. |
| | |
| | 2} THE BREAKER AND WIRE SIZE IS |
| | INCORRECT FOR THE LOAD INDICATED ON THE |
| | SCHEDULE. CIRCUIT #2-4 AHU. |
| | |
| | 3} PLEASE NOTE THE OCP (60) IS TOO LARGE |
| | FOR THE CONDUCTOR SIZE (#8) FOR THE |
| | RANGE. |
| | |
| | 4} CIRCUIT #28 , MASTER BATH, MUST |
| | COMPLY WITH 210.11(C)(3). |
| | |
| | 5} PLEASE SEE NOTE #3 REGARDING KITCHEN |
| | GFI SHOULD INDICATE ALL COUNTERTOP |
| | RECEPTACLE PER 210.8(A)(6). |
| | |
| | 6} THERE ARE RECEPTACLES LOCATED |
| | THROUGHOUT THE EXISTING HOUSE, BUT THEY |
| | DO NOT SHOW CODE COMPLIANCE WITH ARTICLE |
| | 210.52. INDICATE IF THESE ARE NEW OR |
| | EXISTING. IF PART OF THIS APPLICATION |
| | SHOW EXISTING DEVICES AS WELL SO THAT |
| | COMPLIANCE MAY BE DETERMINED. |
| | |
| | 7} THE ENGINEERING FIRM ADVERTISING AS A |
| | CORPORATION ON THE TITLE BLOCK, MUST |
| | INCLUDE THEIR REQUIRED CERTIFICATE OF |
| | AUTHORIZATION NUMBER ON THE TITLE BLOCK |
| | PER 61G15-23.002, FACODE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |