| Plan Review Notes For Permit 05091266 |
| Permit Number |
05091266 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-10-11 00:00:00 | *** DENIED *** | | | 1) SUPPLY AIR DUCT FROM A.H.U. TO MIXING | | | BOX NOT SIZED. | | | 2) NO VISIBLE MEANS OF RETURN AIR FROM | | | FAMILY ROOM TO A.H.U.. | | | 3) DRYER VENT CAN NOT DISCHARGE AT | | | CONDENSER UNIT. | | | 4) PLANS DO NOT STATE IF A/C EQUIPMENT | | | IS NEW OR EXISTING. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|