| Date |
Text |
| 2005-10-07 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} INDICATE THE CONDUIT AND CONDUCTOR |
| | SIZES FOR THE RISER. ALSO AIC RATING OF |
| | THE EQUIPMENT PER 110.9 & 10. |
| | |
| | 2} THERE MUST BE A DISCONNECT PER |
| | 230.70(A)(1), PREFERABLY NEXT TO THE |
| | METER. |
| | |
| | 3} PLEASE NOTE THE OCP (60) IS TOO LARGE |
| | FOR THE CONDUCTOR SIZE (#8) FOR THE |
| | RANGE. |
| | |
| | 4} CIRCUIT # 27, MASTER BATH, MUST |
| | COMPLY WITH 210.11(C)(3). |
| | |
| | 5} THE RECEPTACLES IN THE GARAGE MUST BE |
| | GFI PROTECTED PER 210.8(A)(2). |
| | |
| | 6} THERE ARE RECEPTACLES LOCATED |
| | THROUGHOUT THE EXISTING HOUSE, BUT THEY |
| | DO NOT SHOW CODE COMPLIANCE WITH ARTICLE |
| | 210.52. INDICATE IF THESE ARE NEW OR |
| | EXISTING. IF PART OF THIS APPLICATION |
| | SHOW EXISTING DEVICES AS WELL SO THAT |
| | COMPLIANCE MAY BE DETERMINED. |
| | |
| | 7} THE ENGINEERING FIRM ADVERTISING AS A |
| | CORPORATION ON THE TITLE BLOCK, MUST |
| | INCLUDE THEIR REQUIRED CERTIFICATE OF |
| | AUTHORIZATION NUMBER ON THE TITLE BLOCK |
| | PER 61G15-23.002, FACODES. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |
| | |
| | |