| Plan Review Notes For Permit 05091265 |
| Permit Number |
05091265 |
|
| Review Stop |
FIRE |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2007-09-21 11:06:58 | ***DENIED*** | | | | | | 1) PLEASE SEE ELECTRICAL COMMENT #2 AND CLARIFY EXIT | | | SIGN LOCATION. ANY CHANGE TO MEANS OF EGRESS SHOULD BE | | | REFLECTED ON LIFE SAFETY SHEETS WHERE PROVIDED. | | | | | | 2) MANY REVISIONS IDENTIFY CHANGES TO FLOOR ELEVATIONS. | | | IN ADDITION TO APPLICABLE BUILDING CODES, PLEASE SHOW | | | COMPLIANCE WITH NFPA 101, CHAPTER 7 WITH REGARDS TO | | | WALKING SURFACES THAT IMPACT REQUIRED MEANS OF EGRESS. | | | | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 | | | |
|