Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop E
Sequence Number 8
Notes
Date Text
2007-06-26 09:04:53 
  
 *** UNSAT ***
  
 ** REVISIONS TO 480 HIBISCUS ST.
  
 1) NOTE: PLEASE SEE THERE ARE NUMEROUS SHEETS WHICH
 INDICATE REVISIONS ON TITLE BLOCK AS REV 11 BUT THE
 LAST REVISION SUBMITTED TO THIS OFFICE WAS REVISION #6.
 WHAT HAPPENED TO 7, 8, 9 AND 10?
 PLEASE SEE THERE ARE SEVERAL SHEETS WHICH INDICATE SOME
 CHANGES TO SHEETS AS NOTED IN THE REVISIONS HOWEVER
 THERE ARE ITEMS WHICH ARE REVISED ON PLANS HOWEVER
 THERE IS NO INDICATION ON PLANS AT THESE LOCATIONS
 WHERE THESE ARE REVISED. (NO CLOUDS/NO TRIANGLES).
 FBC 106.1.2 COORDINATION REQUIRED.
  
 2) NOTE: PLEASE CLARIFY NEW LAYOUT ON GROUND LEVEL AND
 MEZZ LEVEL AS WHAT USED TO BE THE PREVIOUS ELECTRICAL
 ROOM IS NOW SHOWN BLANK, WITH A MISSING RATED WALL.
 PLEASE SE NEW EXIT LIGHTS WHICH DIRECT PEOPLE INTO THIS
 CLOSED IN AREA ELECTRICAL ROOM. IT APPEARS TO INDICATE
 AN EGRESS FROM THE GARAGE INTO THE GROUND LEVEL
 COMMERCIAL TENANT SPACE?
 FBC 106.1.2 COORDINATION REQUIRED.
  
 3) NOTE: PLEASE SEE THERE ARE SEVERAL NEW EXIT LIGHTS
 AND OTHER FIXTURES WITH NOT DESIGNATION FOR CIRCUITS,
 CONTROLS ETC.
 240.4.310.16.FBC 106.1.2, 106.3.5.1.2 ETC
  
 4) NOTE: PLEASE SEE TYPICAL CORRIDORS OUTSIDE STORAGE
 ROOMS WHICH NO AUTOMATED CONTROLS ARE INDICTED FOR
 LIGHTS. 13-415.1.ABC.1.1,.1.2. THIS IS TYPICAL OF
 MULTIPLE FLOORS.
  
 5) NOTE: PLEASE SEE SEVERAL NEW LIGHTING CONTROLS ADDED
 IN ROOMS WHICH INDICATE NOW A STANDARD LIGHTING SWITCH.
 PLEASE SEE MISSING CONTROLS PER 13-415.1.ABC.1.1, .1.2
  
 6) NOTE: PLEASE SEE ALL LIGHTING WHICH HAS BEEN REVISED
 ON PLANS WILL REQUIRE THE ENERGY CALCULATIONS TO BE
 COMPLETELY REVISED.
 13-415.1.AB.1.1, 13-415.2
  
 7) NOTE: PLEASE KNOW WITH THE REVISED LIGHTING ON PLANS
 WILL REQUIRE ALL THE REQUIRED EGRESS LIGHTING TO BE
 REVISED.
 PLEASE SUBMIT THE REVISED MINIMUM LEVELS UNDER NORMAL
 AND UNDER EMERGENCY.
 LS 101 7.8, 7.9
  
 8) NOTE: PLEASE SEE THERE ARE CHANGES TO POOL PATIO
 AREAS FOR LIGHTS WHICH ARE NOT NOTED ON EXPLANATION
 LETTERS AND LOCATIONS WHERE LIGHTS ARE NOT REMOVED?
 PLEASE CLARIFY WHERE THESE LIGHTS ARE? HOW ARE THESE
 AREAS GOING TO BE LIT? PLEASE SEE ELECTRICAL PANELS,
 TRANSFORMERS FOR POWER WHICH HAVE BEEN REMOVED BUT THE
 PLANS DO NOT INDICATE THIS OR NEW LOCATIONS?
 PLEASE SEE THE REVISION EXPLANATION LETTER DOES NOT
 MENTION SEVERAL OF THESE ITEMS.
 FBC 106.1.2 REQUIRED COORDINATION.
  
 9) NOTE: PLEASE SEE THE SUBMITTED EXPLANATION TO
 REVISIONS LETTER STATE SEVERAL SHEETS WHICH WERE NOT
 SUBMITTED IN PACKAGE AND THERE ARE SHEETS SUBMITTED
 WHICH ARE NOT LISTED.
 PLEAS COORDINATE.
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE 221-233 APPEAR TO BE OK, HOWEVER
 INFORMATION FOR PHOTO-METRICS AND COORDINATION OF
 REVISION NUMBERS IN TITLE BLOCKS NEED TO BE ADDRESSED.
  
 11) NOTE: PLEASE SEE SHEETS 602 AND 603 WHICH LETTER
 STATES REVISED FEEDERS FOR ALUM, YET PLANS DO NOT SEEM
 TO HAVE ANY DESIGNATIONS OR REVISIONS FOR THIS?
  
 12) NOTE: *** IMPORTANT** PLEASE SEE ATTACHED INDUSTRY
 BULLETIN WITH RESPECT TO THE NEW HB 7121 WHICH REQUIRES
 FUEL FOR GENERATOR, EMERGENCY LIGHTS, EXIT LIGHTS, AND
 ONE STRETCHER ACCESSIBLE ELEVATOR FOR A PERIOD OF FIVE
 DAYS. PLEASE SEE THIS IS A NEW STATE LAW REQUIRED FOR
 NEW CONSTRUCTION, EXISTING CONSTRUCTION, EXISTING
 BUILDING WHICH MEET THE HIGH-RISE CRITERIA.
 THE SHEET IS ATTACHED AND THE ENTIRE HOUSE BILL CAN BE
 LOCATED ON THE STATE LEGISLATIVE WEBSITE.
  
 13) NOTE: PLEASE KNOW AS THERE ARE NUMEROUS SHEETS
 WHICH NEED COORDINATION OF REVISED ITEMS, NOT ALL CAN
 BE GIVEN IN DETAIL FOR EACH ITEM. ONE SET HAS REDLINED
 AREAS FOR SOME OF THESE LOCATIONS.
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II