| 2007-06-26 09:04:53 | |
| | |
| | *** UNSAT *** |
| | |
| | ** REVISIONS TO 480 HIBISCUS ST. |
| | |
| | 1) NOTE: PLEASE SEE THERE ARE NUMEROUS SHEETS WHICH |
| | INDICATE REVISIONS ON TITLE BLOCK AS REV 11 BUT THE |
| | LAST REVISION SUBMITTED TO THIS OFFICE WAS REVISION #6. |
| | WHAT HAPPENED TO 7, 8, 9 AND 10? |
| | PLEASE SEE THERE ARE SEVERAL SHEETS WHICH INDICATE SOME |
| | CHANGES TO SHEETS AS NOTED IN THE REVISIONS HOWEVER |
| | THERE ARE ITEMS WHICH ARE REVISED ON PLANS HOWEVER |
| | THERE IS NO INDICATION ON PLANS AT THESE LOCATIONS |
| | WHERE THESE ARE REVISED. (NO CLOUDS/NO TRIANGLES). |
| | FBC 106.1.2 COORDINATION REQUIRED. |
| | |
| | 2) NOTE: PLEASE CLARIFY NEW LAYOUT ON GROUND LEVEL AND |
| | MEZZ LEVEL AS WHAT USED TO BE THE PREVIOUS ELECTRICAL |
| | ROOM IS NOW SHOWN BLANK, WITH A MISSING RATED WALL. |
| | PLEASE SE NEW EXIT LIGHTS WHICH DIRECT PEOPLE INTO THIS |
| | CLOSED IN AREA ELECTRICAL ROOM. IT APPEARS TO INDICATE |
| | AN EGRESS FROM THE GARAGE INTO THE GROUND LEVEL |
| | COMMERCIAL TENANT SPACE? |
| | FBC 106.1.2 COORDINATION REQUIRED. |
| | |
| | 3) NOTE: PLEASE SEE THERE ARE SEVERAL NEW EXIT LIGHTS |
| | AND OTHER FIXTURES WITH NOT DESIGNATION FOR CIRCUITS, |
| | CONTROLS ETC. |
| | 240.4.310.16.FBC 106.1.2, 106.3.5.1.2 ETC |
| | |
| | 4) NOTE: PLEASE SEE TYPICAL CORRIDORS OUTSIDE STORAGE |
| | ROOMS WHICH NO AUTOMATED CONTROLS ARE INDICTED FOR |
| | LIGHTS. 13-415.1.ABC.1.1,.1.2. THIS IS TYPICAL OF |
| | MULTIPLE FLOORS. |
| | |
| | 5) NOTE: PLEASE SEE SEVERAL NEW LIGHTING CONTROLS ADDED |
| | IN ROOMS WHICH INDICATE NOW A STANDARD LIGHTING SWITCH. |
| | PLEASE SEE MISSING CONTROLS PER 13-415.1.ABC.1.1, .1.2 |
| | |
| | 6) NOTE: PLEASE SEE ALL LIGHTING WHICH HAS BEEN REVISED |
| | ON PLANS WILL REQUIRE THE ENERGY CALCULATIONS TO BE |
| | COMPLETELY REVISED. |
| | 13-415.1.AB.1.1, 13-415.2 |
| | |
| | 7) NOTE: PLEASE KNOW WITH THE REVISED LIGHTING ON PLANS |
| | WILL REQUIRE ALL THE REQUIRED EGRESS LIGHTING TO BE |
| | REVISED. |
| | PLEASE SUBMIT THE REVISED MINIMUM LEVELS UNDER NORMAL |
| | AND UNDER EMERGENCY. |
| | LS 101 7.8, 7.9 |
| | |
| | 8) NOTE: PLEASE SEE THERE ARE CHANGES TO POOL PATIO |
| | AREAS FOR LIGHTS WHICH ARE NOT NOTED ON EXPLANATION |
| | LETTERS AND LOCATIONS WHERE LIGHTS ARE NOT REMOVED? |
| | PLEASE CLARIFY WHERE THESE LIGHTS ARE? HOW ARE THESE |
| | AREAS GOING TO BE LIT? PLEASE SEE ELECTRICAL PANELS, |
| | TRANSFORMERS FOR POWER WHICH HAVE BEEN REMOVED BUT THE |
| | PLANS DO NOT INDICATE THIS OR NEW LOCATIONS? |
| | PLEASE SEE THE REVISION EXPLANATION LETTER DOES NOT |
| | MENTION SEVERAL OF THESE ITEMS. |
| | FBC 106.1.2 REQUIRED COORDINATION. |
| | |
| | 9) NOTE: PLEASE SEE THE SUBMITTED EXPLANATION TO |
| | REVISIONS LETTER STATE SEVERAL SHEETS WHICH WERE NOT |
| | SUBMITTED IN PACKAGE AND THERE ARE SHEETS SUBMITTED |
| | WHICH ARE NOT LISTED. |
| | PLEAS COORDINATE. |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: PLEASE SEE 221-233 APPEAR TO BE OK, HOWEVER |
| | INFORMATION FOR PHOTO-METRICS AND COORDINATION OF |
| | REVISION NUMBERS IN TITLE BLOCKS NEED TO BE ADDRESSED. |
| | |
| | 11) NOTE: PLEASE SEE SHEETS 602 AND 603 WHICH LETTER |
| | STATES REVISED FEEDERS FOR ALUM, YET PLANS DO NOT SEEM |
| | TO HAVE ANY DESIGNATIONS OR REVISIONS FOR THIS? |
| | |
| | 12) NOTE: *** IMPORTANT** PLEASE SEE ATTACHED INDUSTRY |
| | BULLETIN WITH RESPECT TO THE NEW HB 7121 WHICH REQUIRES |
| | FUEL FOR GENERATOR, EMERGENCY LIGHTS, EXIT LIGHTS, AND |
| | ONE STRETCHER ACCESSIBLE ELEVATOR FOR A PERIOD OF FIVE |
| | DAYS. PLEASE SEE THIS IS A NEW STATE LAW REQUIRED FOR |
| | NEW CONSTRUCTION, EXISTING CONSTRUCTION, EXISTING |
| | BUILDING WHICH MEET THE HIGH-RISE CRITERIA. |
| | THE SHEET IS ATTACHED AND THE ENTIRE HOUSE BILL CAN BE |
| | LOCATED ON THE STATE LEGISLATIVE WEBSITE. |
| | |
| | 13) NOTE: PLEASE KNOW AS THERE ARE NUMEROUS SHEETS |
| | WHICH NEED COORDINATION OF REVISED ITEMS, NOT ALL CAN |
| | BE GIVEN IN DETAIL FOR EACH ITEM. ONE SET HAS REDLINED |
| | AREAS FOR SOME OF THESE LOCATIONS. |
| | |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-06-24 15:53:05 | 200-06-024 15:53:05 |
| | ELEC SHEETS OF REVISIONS IN ELEC FOR REVIEW. |