| 2007-06-26 14:27:42 | FBC 2004 CODE FAMILY |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | REVISED MECHANICAL PLANS DATED 5/18/07. THE FOLLOWING |
| | PAGES PASSED REVIEW: |
| | M2.12, M2.18, M2.21, M2.24, M2.27, M2.30, M2.31, M2.34, |
| | M2.35 |
| | |
| | THE BALANCE OF PAGES SUBMITTED FOR REVISION ARE DENIED. |
| | THE FOLLOWING COMMENTS ARE ORGANIZED BY PAGE NUMBER. |
| | SOME COMMENTS ARE REFERENCED MORE THAN ONCE IF THE |
| | ISSUE IS FOUND ON MORE THAN ONE PAGE. |
| | |
| | 1. M2.01: THE ACCESS DOOR FOR GEF-1 APPEARS TO BE IN |
| | CONFLICT WITH THE FAN HOUSING AND WILL NOT OPEN |
| | COMPLETELY. SEE FBC,M 306.5 FOR SERVICE ACCESS |
| | REQUIREMENTS. |
| | |
| | 2. M2.01: THE INTAKE LOUVER FOR GEF-1 IS SHOWN ON PLANS |
| | TO BE APPROXIMATELY 7' WIDE. IN ORDER TO ACHIEVE 94 |
| | SQ.FT., AS NOTED ON PLANS, THE LOUVER WOULD NEED TO BE |
| | OVER 13 FEET TALL. IS THERE SUFFICIENT CLEARANCE? FBC |
| | 106.1.2 |
| | |
| | 3. M2.01, M2.04, M2.07, M2.10, M2.13, M2.16: WHAT ARE |
| | THE ACTUAL DIMENSIONS OF THE INTAKE LOUVERS FOR THE |
| | GEF'S? WHY IS THE FREE AREA OF THE EXHAUST LOUVERS |
| | (23.375 SQ.FT) LESS THAN HALF THE AREA OF THE INTAKE |
| | LOUVERS AT THE FANS (51.7 SQ.FT)? ALSO, PLEASE SHOW HOW |
| | THE REQUIRED MINIMUM VENTILATION RATE (CONTINUOUS) OF |
| | 0.05 CFM PER SQ.FT. IS TO BE PROVIDED IN ACCORDANCE |
| | WITH FBC,M 404.2. |
| | |
| | 4. M2.01: GARAGE VENTILATION NOTE ON PLAN STATES "2 |
| | EXHAUST FANS," BUT THIS FLOOR USES ONLY ONE FAN. PLEASE |
| | REVISE NOTE SHOWING ONE FAN PROVIDING 44,000 CFM. FBC |
| | 106.1.1 |
| | |
| | 5. M2.01: WHAT IS THE ELEVATION OF CU-T1 AND AMF-1? |
| | APPLIANCES LOCATED IN PUBLIC GARAGES, MOTOR |
| | FUEL-DISPENSING FACILITIES, REPAIR GARAGES OR OTHER |
| | AREAS FREQUENTED BY MOTOR VEHICLES, SHALL BE INSTALLED |
| | A MINIMUM OF 8 FEET ABOVE THE FLOOR. WHERE MOTOR |
| | VEHICLES EXCEED 6 FEET IN HEIGHT AND ARE CAPABLE OF |
| | PASSING UNDER AN APPLIANCE, APPLIANCES SHALL BE |
| | INSTALLED A MINIMUM OF 2 FEET HIGHER ABOVE THE FLOOR |
| | THAN THE HEIGHT OF THE TALLEST VEHICLE. |
| | EXCEPTION: THE REQUIREMENTS OF THIS SECTION SHALL NOT |
| | APPLY WHERE THE APPLIANCES ARE PROTECTED FROM MOTOR |
| | VEHICLE IMPACT AND INSTALLED IN ACCORDANCE WITH NFPA |
| | 88B. |
| | |
| | 6. M2.01: PROVIDE WALL MOUNTING DETAIL FOR CU-T1 WHICH |
| | WORKS IN CONJUNCTION WITH MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS, ESPECIALLY RELATED TO REQUIRED CLEARANCES |
| | FOR AIRFLOW, AND IS PROTECTED FROM MECHANICAL DAMAGE |
| | PER FBC,M 303.1 AND 303.4. |
| | |
| | 7. M2.02: FOR CU-T2, CU-T3, CU-G1, CU-G@, CU-SGR1 AND |
| | AMF-1 PLEASE SEE COMMENTS 5 AND 6. |
| | |
| | 8. M2.02: PLEASE SHOW HOW SERVICE ROOM 019 IS TO BE |
| | MAINTAINED AT A POSITIVE PRESSURE IN ACORDANCE WITH |
| | FBC,M 404.3 AND PROVIDED VENTILATION AS REQUIRED BY |
| | FBC,M 403.3. |
| | |
| | 9. M2.02: FUTURE TENANT COMMERCIAL SPACE #14 FRESH AIR |
| | INTAKE LOUVER IS INSIDE THE PARKING GARAGE. THE AIR |
| | REQUIRED BY FBC,M 403.3 SHALL NOT BE RECIRCULATED PER |
| | 403.2.1. ALSO, INTAKE OPENING LOCATIONS SHALL BE IN |
| | COMPLIANCE WITH FBC,M 401.5.1. |
| | |
| | 10. M2.03: ARE INTAKE LOUVERS FOR THE GENERATOR MINIMUM |
| | 10' FROM EXHAUST LOUVERS ON MEZZANINE LEVEL (M2.06)? |
| | FBC,M 401.5.1. ALSO, WHAT IS THE HEIGHT OF THE |
| | GENERATOR EXHAUST OUTLET? IS IT ON GROUND LEVEL OR |
| | MEZZANINE LEVEL? IT IS SHOWN ON BOTH PLANS. PLEASE |
| | CLARIFY AND SHOW COMPLIANCE WITH FBC,M 401.5.2 AND |
| | 501.2. |
| | |
| | 11. M2.03: WHERE IS THE CONTINUATION OF THE 8" ROUND |
| | EXHAUST DUCT FROM BATHROOMS AND JANITOR'S CLOSET? THERE |
| | IS NO CONTINUATION ON M2.06 AS THERE WAS ON PREVIOUS |
| | PLAN. FBC 106.1.1 |
| | |
| | 12. M2.04: FOR AMF-1, PLEASE SEE COMMENT #5. |
| | |
| | 13. M2.04: PLEASE MARK THE SMOKE EXHAUST RISER SERVING |
| | THE MAIN LOBBY AREA. ALSO, IS IT THE INTENT OF THIS |
| | DESIGN TO CONVER THE SUPPLY DUCT SYSTEM FOR AHU-12 INTO |
| | A SMOKE EXHAUST DUCT WHEN THE AREA GOES INTO SMOKE |
| | CONTROL MODE? IF SO, THERE ARE SEVERAL ISSUES WHICH |
| | NEED TO BE ADDRESSED: |
| | A) SUPPLY DUCT APPEARS TO BE A STANDARD DUCTBOARD AND |
| | FLEX SYSTEM. THIS TYPE OF DUCT MAY NOT BE USED FOR ANY |
| | TYPE OF EXHAUST PER FBC,M 501.4 AND MUST BE DESIGNED TO |
| | MEET THE REQUIREMENTS FOR A SMOKE EXHAUST DUCT PER |
| | FBC,M 513.10.2. |
| | B) IF SUPPLY REGISTERS AND DIFFUSERS ARE TO BE USED FOR |
| | SMOKE EXHAUST, PLEASE PROVIDE SUBMITTAL DATA SHOWING |
| | THEIR SUITABILITY FOR USE IN A SMOKE EXHAUST SYSTEM. C) |
| | PLAN SHOWS FIRE DAMPERS IN SUPPLY DUCT WHICH APPEARS TO |
| | BE INTENDED FOR USE AS SMOKE EXHAUST DUCT. WHERE THE |
| | INSTALLATION OF A FIRE DAMPER WILL INTERFERE WITH THE |
| | OPERATION OF A REQUIRED SMOKE CONTROL SYSTEM IN |
| | ACCORDANCE WITH SECTION 513, APPROVED ALTERNATIVE |
| | PROTECTION SHALL BE UTILIZED. FBC,M 607.2.1 |
| | D) WHAT IS THE AIR BALANCE DESIGN FOR THE DUCT SYSTEM |
| | WHEN IN SMOKE CONTROL MODE? FBC 106.1.2. IS THERE |
| | MAKE-UP AIR FOR THE 2000 CFM OF EXHAUST? |
| | E) PLEASE ALSO CHECK SMOKE EXHAUST DUCTS ON M2.05 TO |
| | VERIFY COMPLIANCE WITH THE ABOVE REQUIREMENTS. |
| | |
| | 14. M2.05: FOR AMF-1, PLEASE SEE COMMENT #5. |
| | |
| | 15. M2.05: THERE ARE SOME DUCTS RELATED TO THE SMOKE |
| | EXHAUST WHICH ARE MISSING SIZES ON PLANS. PLEASE |
| | CLARIFY. FBC 106.1.1 |
| | |
| | 16. M2.06: THERE IS NO SEPARATION BETWEEN AREAS MARKED |
| | AS "COMMERCIAL #15 AND "STORAGE." ARE THERE WALLS |
| | MISSING FROM THE PLAN? THIS MAY IMPACT THE NEED FOR |
| | FIRE DAMPERS PER FBC,M 607.5. |
| | |
| | 17. M2.06: WHAT IS THE DESIGNATION, SIZE AND CFM OF |
| | RETURN GRILL IN THE 18X10 DUCT IN "STORAGE?" |
| | |
| | 18. M2.07 REGARDING AMF-1 AND CU-E1, PLEASE SEE COMMENT |
| | #5. |
| | |
| | 19. M2.07: ACORDING TO THE REFLECTIVE CEILING PLAN, THE |
| | ELEVATOR LOBBY AND CORRIDOR HAVE THE SAME CEILING |
| | HEIGHT. HOW IS IT POSSIBLE TO HAVE SIDEWALL GRILLS (TWO |
| | 36X6) FOR SMOKE EXHAUST UNDER THESE CONDITIONS? HOW |
| | DOES THE FIRE WRAP INTERACT WITH THE RATED |
| | CORRIDOR/ELEVATOR LOBBY WALLS? HOW ARE THE OPENINGS AT |
| | THE END OF THE FIRE WRAP PROTECTED AT THE 36X6 GRILLS? |
| | THIS WOULD ESSENTIALLY BE UNPROTECTED OPENINGS IN A |
| | 2-HOUR SHAFT. THE OVERALL INTENT OF THE DESIGN OF THIS |
| | AREA IS UNCLEAR AND MAY BE LACKING COORDINATION WITH |
| | ARCHITECTURAL PLANS. |
| | |
| | 20. M2.08: REGARDING AMF-1 AND CU-19, PLEASE SEE |
| | COMMENT #5. REGARDING CU-E2, PLEASE SEE COMMENTS 5 AND |
| | 6. |
| | |
| | 21. M2.08: FOR SMOKE EXHAUST DUCT IN CORRIDOR ACROSS |
| | FROM ELECTRICAL ROOM, PLEASE SEE COMMENT #19. |
| | |
| | 22. M2.08: PLEASE SHOW VENTILATION (OUTDOOR AIR) RATE |
| | OF 0.05 CFM PER SQ.FT FOR STORAGE AREA AND SHOW HOW THE |
| | AREA WILL BE MAINTAINED AT A POSITIVE PRESSURE PER |
| | FBC,M 404.3. |
| | |
| | 23. M2.09: ARE SHOWN AS BEING REVISED ON PLAN IS |
| | CLOUDED AND MARKED AS REVISION 6, BUT REVISIONS LISTED |
| | IN TITLE BLOCK AREA ONLY GO TO REVISION 4. PLEASE |
| | CLARIFY. FBC 106.1.3. |
| | |
| | 24. M2.10: PLEASE SEE COMMENTS 5 AND 19. |
| | |
| | 25: M2.10: ELECTRICAL ROOM IN CORRIDOR SHOWS AN |
| | UNDERCUT DOOR FOR AIRFLOW. HOWEVER, THERE IS NO |
| | MECHANICAL EQUIPMENT OR MEANS TO CAUSE AIRFLOW INTO THE |
| | ELECTRICAL ROOM. ALSO, THE ELCTRICAL ROOM DOOR IS PART |
| | OF A FIRE AND SMOKE BARRIER (CORRIDOR) AND THEREFORE |
| | SHOULD NOT BE UNDERCUT OR HAVE ANY GAP WHICH IS NOT |
| | PART OF A LISTED RATED DOOR ASSEMBLY.. |
| | |
| | 26. M2.11: PLEASE SEE ALL COMMENTS FOR PAGE M2.08 |
| | (20,21,22). ALSO, SEE COMMENT #25 RELATED TO ELECTRICAL |
| | AND STORAGE ROOMS. |
| | |
| | 27. M2.13 AND M2.16: PLEASE SEE COMMENTS 5, 19 AND 25. |
| | |
| | 28. M2.14 AND M2.17: PLEASE SEE COMMENTS 20,21,22. |
| | ALSO, PLEASE SEE COMMENT #25 FOR ELECTRICAL AND STORAGE |
| | ROOMS. |
| | |
| | 29. M2.15: AREA CLOUDED AS REVISED IS MARKED A REVISION |
| | 7, HOWEVER THE REVISION SCHEDULE SHOWN IN TITLE BLOCK |
| | AREA ONLY GOES TO REVISION 4. PLEASE CLARIFY PER FBC,M |
| | 106.1.3. |
| | |
| | 30. M2.17: THERE IS A "BOILER ROOM" LOUVER CALCULATION |
| | BOX ADDED TO PLAN BUT IT IS NOT MARKED AS PART OF THIS |
| | REVISION. PLEASE CLARIFY. ALSO, THE BOILER/POOL |
| | EQUIPMENT ROOM HAS A NOTE WHICH STATES "DESIGN |
| | PENDING." THIS AREA CAN NOT BE FULLY REVIEWED WITH |
| | INCOMPLETE INFORMATION. |
| | |
| | 31. M2.17: HOW ARE DUCT PENETRATIONS AT THE BOTTOM OF |
| | THE SHAFT FOR POOL ROOM VENT DUCT AND BOILER FLUE TO BE |
| | PROTECTED? FBC 707.11 AND FBC,M 606.5.5.1 |
| | |
| | 32. M2.17: COMBUSTION AIR DUCT FOR BOILER ROOM SHOULD |
| | BE DESIGNED PER FBC,FG 304.6.1 OR 304.6.2. IF TWO |
| | OPENINGS ARE USED, THEN BOTH OPENINGS ARE TO |
| | COMMUNICATE DIRECTLY WITH THE OUTDOORS. SEE FIG. |
| | 304.6.1(3). |
| | |
| | 33. M2.17: PLEASE PROVIDE INFORMATION ON TYPE OF |
| | VENTING TO BE USED FOR THE BOILER. THE HORIZONTAL |
| | LENGTH OF THE VENT CONNECTOR IS PROHIBITED BY FBC, FG |
| | TABLE 504.2. |
| | |
| | 34. M2.19: PLEASE SEE COMMENTS 5 AND 19. |
| | |
| | 35. M2.19: DOES THE RATING OF THE CORRIDOR CONTINUE |
| | INTO THE DECK LOBBY AREA? IF SO, ALL PENETRATIONS SHALL |
| | BE PROTECTED PER FBC,M 607.5. ALSO, THE CORRIDOR (EXIT |
| | ENCLOSURE) VENTILATION SYSTEM SHALL BE INDEPENDENT OF |
| | OTHER BUILDING VENTILATION SYSTEMS PER FBC,M 401.4. |
| | |
| | 36. M2.19: WHERE ARE THE REFRIGERANT LINES AND MEANS OF |
| | CONDENSATE DISPOSAL FOR AHU 17? FBC 106.1.1. |
| | |
| | 37. M2.19: PLEASE SEE COMMENT #19 RELATED TO SMOKE |
| | EXHAUST DUCT ACROSS FROM THE ELECTRICAL ROOM. |
| | |
| | 38. M2.20: PLEASE PROVIDE CONTINUATION OF ROOM ON POOL |
| | DECK WITH AHU 18. NONE COULD BE FOUND ON PLANS. FBC |
| | 106.1.1. |
| | |
| | 39. M2.20,M2.23, M2.26, M2.29: PLEASE SEE COMMENT #19 |
| | REGARDING SMOKE EXHAUST DUCT ACROSS FROM ELECTRICAL |
| | ROOM AND COMMENT #25 REGARDING ELECTRICAL AND STORAGE |
| | ROOM DOORS. |
| | |
| | 40. M2.22: PLEASE SEE COMMENT #19. |
| | |
| | 41. M2.25, M.28: PLEASE SEE COMMENTS 19 AND 25. |
| | |
| | 42. M2.32: SEF-2 SHOWS A FIRE DAMPER IN THE DUCT. WHERE |
| | THE INSTALLATION OF A FIRE DAMPER WILL INTERFERE WITH |
| | THE OPERATION OF A REQUIRED SMOKE CONTROL SYSTEM IN |
| | ACCORDANCE WITH SECTION 513, APPROVED ALTERNATIVE |
| | PROTECTION SHALL BE UTILIZED. FBC,M 607.2.1 |
| | |
| | 43. M2.33: PLEASE PROVIDE SIZE AND OTHER RELEVANT DATA |
| | FOR INTAKE SIDE DUCT FOR SPF-1 AND SPF-2. FBC 106.1.1 |
| | |
| | 44. M2.33: RELIEF DAMPER APPEARS TO BE INSIDE THE STAIR |
| | ENCLOSURE. SHOULD IT BE AN AN EXTERIOR WALL? |
| | |
| | 45. M3.01 THROUGH M3.06: MANY CHANGES ON PAGES, NONE |
| | ARE MARKED AS REVISIONS. PLEASE CLEARLY MARK ON PLANS |
| | THE AREAS WHICH ARE BEING REVISED AND INDICATE A DATE |
| | AND REVISION NUMBER. FBC 106.1.1 AND FBC 106.1.3. |
| | |
| | 46. M4.01: THERE HAVE BEEN SEVERAL REVISIONS TO THIS |
| | PAGE SINCE THE PERMITTED SET. PLEASE CLEARLY MARK ALL |
| | CHANGES WHICH HAVE TAKEN PLACE SINCE THE PERMITTED SET |
| | OF PLANS. FBC 106.1.3. |
| | |
| | 47. M4.02: THE DESIGNATED CFM OF EXHAUST ON EACH FLOOR |
| | DO NOT MATCH THE CFM AS SHOWN ON FLOOR PLANS. PLEASE |
| | COORDINATE DRAWINGS. |
| | |
| | 48. M5.01: THIS PAGE GOES FROM REVISION 1 TO REVISION |
| | 3. PLEASE SHOW WHAT CHANGES HAVE BEEN MADE RELATED TO |
| | REVISION 2. FBC 106.1.3. |
| | |
| | 49. M5.02: THIS PAGE CONTAINS 2 PAGES OF SCHEDULES AND |
| | HAVE BEEN REDUCED IN SIZE AND QUALITY TO A POINT WHERE |
| | MUCH OF THE INFORMATION IS NOT LEGIBLE. PLEASE CORRECT. |
| | FBC 106.1.3 |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |
| | |