| 2008-06-26 16:42:30 | CITY PALMS SUBMITALS/ REVISIONS |
| | PERMIT:05091265 |
| | ADDRESS: 480 HIBISCUS |
| | |
| | ACTION:DENIED |
| | |
| | SUBMITTAL NO.FIRESTOPPING JUDGEMENT/ C-AJ-8093 |
| | |
| | THE SUBMITTAL FOR AN ENGINEERS JUDGEMENT IN REGARDS TO |
| | THE SYSTEM NO. C-AJ-8093 HAS BEEN DENIEDIT WILL NEED TO |
| | MEET THE INTENT OF 712.1.1 AND 712.1.2.WE WOULD NEED |
| | ADDITIONAL INFORMATION TO BE ABLE TO DO A COMPLETE |
| | REVIEW. |
| | 1) THE STI DIAGRAM DOES NOT PROVIDE HOW LARGE THE HOLE |
| | IS IN THE WALL NOR THE DIMENSIONS OF THE BUSWAY. NUMBER |
| | 7 OF THE STANDARD INDICATES THEY CAN BE 19 INCHES X 5 |
| | INCHES DEEP. |
| | |
| | 2) STI DIAGRAM ALSO IS NOT CLEAR AS TO HOW MANY BUSWAYS |
| | ARE PENETRATING THIS RATED WALL IS THERE TWO OR FOUR |
| | UNITS? THE COVER SHEET INDICATES THERE ARE THREE |
| | BUSWAYS THAT ACTUALLY ARE PENETRATING THIS WALL? |
| | |
| | 3) STI DIAGRAM ALSO FAILS TO IDENTIFY THE CLEARENCES |
| | BETWEEN THE BUSWAYS WHERE AS THE C-AJ-8093 SYSTEM |
| | CLEARLY STATES THE SPACE BETWEEN THE BUSWAYS SHOULD BE, |
| | PLEASE PROVIDE THESE DEMINSIONS. |
| | |
| | PLEASE PROVIDE THIS ADDITIONAL INFORMATION SO A |
| | THOROUGH REVIEW CAN BE COMPLETED. THANK YOU. |