| 2008-08-21 08:40:55 | REVISION DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | *****SEPARATE GAS PERMIT REQUIRED***** |
| | |
| | ****FROM PREVIOUS REVISION REVIEW: |
| | |
| | 1. SHT P3.16 GAS METER PIPING SCHEMATIC NOT APPROVED. A |
| | LETTER FROM FLORIDA PUBLIC UTILITIES AUTHORIZING THE |
| | BYPASS OF THE GAS METER IS REQUIRED AS PROVIDER OF THE |
| | GAS. |
| | ****RESPONSE NOTED, BUT THE GAS METER PIPING SCHEMATIC |
| | SHOWS A TEE ON THE OUTLET SIDE OF THE METER WITH A |
| | CAPPED LINE. PLEASE INDICATE WHAT THIS LINE IS FOR. IF |
| | IT IS FOR FUTURE USE, A SHUT OFF VALVE IS REQUIRED |
| | BETWEEN THE TEE AND THE CAP. ALSO DOWNSTREAM OF THE TEE |
| | ON THE PIPING TO THE BUILDING, (2PSI), SHOWS A SHUT OFF |
| | VALVE, A 90 DEG FITTING AND THEN ANOTHER SHUT OFF |
| | VALVE. PLEASE EXPLAIN WHY TWO SHUT OFF VALVES ARE |
| | NEEDED. SECTIONS 106.1.2, 106.1.1 & 409. |
| | |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | |
| | 5. SUBMIT MANUF. SPECIFICATIONS FOR THE REGULATORS. |
| | INDICATE MODEL NUMBER AND SHOW MAX CAPACITY FOR TOTAL |
| | LOAD OF ALL APPLIANCES COMBINED. |
| | ****RESPONSE NOTED, BUT THE MAXIMUM CAPACITY FOR THE |
| | GAS REGULATOR IS NOT INDICATED. 410.2(3) |
| | |
| | 6. OK |
| | |
| | 7. SEE BELOW FOR PROVISO FROM PLANS STAMPED AT TIME OF |
| | PERMIT FOR THE BUILD COM: |
| | |
| | PASSED/PROVISO |
| | |
| | MANUF. SPECIFICATION SHEETS REQUIRED AT |
| | THE TIME OF BUILD-0UT OF KITCHEN, AND AT |
| | THE TIME OF APPLICATION FOR THE GAS |
| | PERMIT FOR THE POOL HEATERS. - MANUF. SPECIFICATION |
| | SHEET ALSO REQUIRED FOR |
| | THE GAS REGULATORS. INDICATE THE MODEL |
| | NUMBER FOR REGULATORS. REGULATORS SHALL |
| | BE LISTED. |
| | ****RESPONSE NOTED, BUT THERE IS NO LISTING INDICATED |
| | ON THE SUBMITTALS FOR THE REGULATORS. THE SUBMITTALS |
| | SHOW REGULATORS MANUF. IN ENGLAND. THERE IS A JEAVONS |
| | J48 REGULATOR MADE BY AMERICAN METER THAT IS LISTED AND |
| | APPROVED AY AGA & CAGA THAT CAN BE USED. SECTION |
| | 410.2(1). |
| | |
| | |
| | REVISION REQUIRED FOR SHT P3.16 |
| | INDICATING THE CORRECT INLET PRESSURE |
| | FROM THE METER, AND SHOWING UNIONS |
| | DOWNSTREAM OF THE SHUT OFF VALVES FOR |
| | THE REGULATORS.-PIPE SIZING SHALL BE |
| | CHECKED WHEN INLET PRESSURE IS |
| | CLARIFIED. |
| | ****RESPONSE NOTED, BUT THE REVISION FOR THE POOL |
| | BOILER EQUIPMENT INFORMATION BLOCK STILL SHOWS THE MOST |
| | REMOTE POOL HEATER/BOILER TO BE 10 FEET FROM THE |
| | REGULATOR. THE RISER DIAGRAM INDICATES AT LEAST 20 |
| | FEET. PLEASE CORRELATE. SECTION 106.1.1. |
| | |
| | ***********NEW COMMENT*********** |
| | |
| | 1B. SHT P3.16 THE GAS METER PIPING SCHEMATIC DOES NOT |
| | REFLECT THE RISER DIAGRAMS. PLEASE INDICATE IF THE |
| | PIPING SCHEMATIC IS FOR BOTH METERS OR FOR ONE METER. |
| | IF FOR BOTH METERS THEN THE RISER DIAGRAMS SHALL |
| | REFLECT THE PIPING SCHEMATIC FOR THE GAS METERS. |
| | |
| | 2B. SHT P3.16 REGULATOR SCHEDULE SHOWS 5 REGULATORS, |
| | BUT ONLY 2 REGULATORS ARE SHOWN ON THE RISER DIAGRAMS. |
| | PLEASE SHOW WHERE EACH REGULATOR IS LOCATED ON THE |
| | RISER DIAGRAMS. SECTION 106.1.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |