Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop G
Sequence Number 5
Notes
Date Text
2008-08-21 08:40:55REVISION DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 *****SEPARATE GAS PERMIT REQUIRED*****
  
 ****FROM PREVIOUS REVISION REVIEW:
  
 1. SHT P3.16 GAS METER PIPING SCHEMATIC NOT APPROVED. A
 LETTER FROM FLORIDA PUBLIC UTILITIES AUTHORIZING THE
 BYPASS OF THE GAS METER IS REQUIRED AS PROVIDER OF THE
 GAS.
 ****RESPONSE NOTED, BUT THE GAS METER PIPING SCHEMATIC
 SHOWS A TEE ON THE OUTLET SIDE OF THE METER WITH A
 CAPPED LINE. PLEASE INDICATE WHAT THIS LINE IS FOR. IF
 IT IS FOR FUTURE USE, A SHUT OFF VALVE IS REQUIRED
 BETWEEN THE TEE AND THE CAP. ALSO DOWNSTREAM OF THE TEE
 ON THE PIPING TO THE BUILDING, (2PSI), SHOWS A SHUT OFF
 VALVE, A 90 DEG FITTING AND THEN ANOTHER SHUT OFF
 VALVE. PLEASE EXPLAIN WHY TWO SHUT OFF VALVES ARE
 NEEDED. SECTIONS 106.1.2, 106.1.1 & 409.
  
 2. OK
 3. OK
 4. OK
  
 5. SUBMIT MANUF. SPECIFICATIONS FOR THE REGULATORS.
 INDICATE MODEL NUMBER AND SHOW MAX CAPACITY FOR TOTAL
 LOAD OF ALL APPLIANCES COMBINED.
 ****RESPONSE NOTED, BUT THE MAXIMUM CAPACITY FOR THE
 GAS REGULATOR IS NOT INDICATED. 410.2(3)
  
 6. OK
  
 7. SEE BELOW FOR PROVISO FROM PLANS STAMPED AT TIME OF
 PERMIT FOR THE BUILD COM:
  
 PASSED/PROVISO
  
 MANUF. SPECIFICATION SHEETS REQUIRED AT
 THE TIME OF BUILD-0UT OF KITCHEN, AND AT
 THE TIME OF APPLICATION FOR THE GAS
 PERMIT FOR THE POOL HEATERS. - MANUF. SPECIFICATION
 SHEET ALSO REQUIRED FOR
 THE GAS REGULATORS. INDICATE THE MODEL
 NUMBER FOR REGULATORS. REGULATORS SHALL
 BE LISTED.
 ****RESPONSE NOTED, BUT THERE IS NO LISTING INDICATED
 ON THE SUBMITTALS FOR THE REGULATORS. THE SUBMITTALS
 SHOW REGULATORS MANUF. IN ENGLAND. THERE IS A JEAVONS
 J48 REGULATOR MADE BY AMERICAN METER THAT IS LISTED AND
 APPROVED AY AGA & CAGA THAT CAN BE USED. SECTION
 410.2(1).
  
  
 REVISION REQUIRED FOR SHT P3.16
 INDICATING THE CORRECT INLET PRESSURE
 FROM THE METER, AND SHOWING UNIONS
 DOWNSTREAM OF THE SHUT OFF VALVES FOR
 THE REGULATORS.-PIPE SIZING SHALL BE
 CHECKED WHEN INLET PRESSURE IS
 CLARIFIED.
 ****RESPONSE NOTED, BUT THE REVISION FOR THE POOL
 BOILER EQUIPMENT INFORMATION BLOCK STILL SHOWS THE MOST
 REMOTE POOL HEATER/BOILER TO BE 10 FEET FROM THE
 REGULATOR. THE RISER DIAGRAM INDICATES AT LEAST 20
 FEET. PLEASE CORRELATE. SECTION 106.1.1.
  
 ***********NEW COMMENT***********
  
 1B. SHT P3.16 THE GAS METER PIPING SCHEMATIC DOES NOT
 REFLECT THE RISER DIAGRAMS. PLEASE INDICATE IF THE
 PIPING SCHEMATIC IS FOR BOTH METERS OR FOR ONE METER.
 IF FOR BOTH METERS THEN THE RISER DIAGRAMS SHALL
 REFLECT THE PIPING SCHEMATIC FOR THE GAS METERS.
  
 2B. SHT P3.16 REGULATOR SCHEDULE SHOWS 5 REGULATORS,
 BUT ONLY 2 REGULATORS ARE SHOWN ON THE RISER DIAGRAMS.
 PLEASE SHOW WHERE EACH REGULATOR IS LOCATED ON THE
 RISER DIAGRAMS. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS