Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop FIRE
Sequence Number 5
Notes
Date Text
2007-06-12 15:44:18***** UNSAT SUBMITTAL*****
  
  
 THE SUBMITTALS WHICH WERE REVIEWED BY THIS WRITER WERE
 DATE STAMPED WITH THE EXCEPTION OF THE HYDRAULIC
 CALCULATIONS FOR THE STANDPIPE WHICH SHOWS 4.462 PSI AS
 THE SAFETY MARGIN.AS PER WEST PALM BEACH FIRE
 PREVENTION, A SAFETY MARGIN OF AT LEAST 5.0 PSI IS
 REQUIRED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722