Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop P
Sequence Number 4
Notes
Date Text
2006-08-22 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE WPB
  
 ** **FROM PREVIOUS REVIEWS: THE COMMENT
 NUMBERS SHALL REMAIN THE SAME AS THE
 PREVIOUS REVIEWS:
  
 FROM PREVIOUS REVIEW: THE COMMENT
 NUMBERS SHALL REMAIN THE SAME AS FIRST
 REVIEW: - NO COMMENT RESPONSES SUBMITTED
 FOR THE FIRST REVIEW.
  
 2. OK
  
 3. SHT A1.0 THE DRINKING FOUNTAIN SHALL
 BE ACCESSIBLE. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTIONS 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 ***COMMENT CONCERNING 11-4.1.3(10)(A)
 NOT ADDRESSED. CLEAR FLOOR SPACE SHALL
 ALLOW FORWARD APPROACH. 11-4.15.5(1).
 ****RESPONSE NOTED, BUT PARALLEL
 APPROACH IS STILL SHOWN ON THE FLOOR
 PLANS ON DIFFERENT SHEETS.
 ** **RESPONSE NOTED, BUT A PARALLEL
 APPROACH IS STILL SHOWN ON THE FLOOR
 PLANS FOR SHEETS A0.3, A0.9, AND A1.21.
  
 4. SHT A1.2 MEN'S & WOMEN'S TOILET ROOMS
 SHALL BE ACCESSIBLE. SUBMIT DETAILS
 SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19, 11-4.21, 11-4.22 AND
 ALL SUBSECTIONS. ALSO FOR THE BREAK ROOM
 SINK, 11-4.24 AND ALL SUBSECTIONS.
 ***COMMENT NOT ADDRESSED. SEE COMMENT
 NUMBER 2 FOR INFORMATION STILL REQUIRED
 FOR W/C'S AND LAVS.
 FOR SHOWERS
 A. 11-4.21.3 SEAT (FOLD-UP TYPE)
 B. 11-4.21.5 CONTROLS (FIG. 11-37)
 C. 11-4.21.6 SHOWER UNIT
 D. 11-4.21.7 CURBS
 SUBMIT ELEVATIONS FOR THE SHOWER SHOWING
 COMPLIANCE FOR THE PRIOR REQUIREMENTS.
 ****RESPONSE NOTED, BUT THE SHOWER UNIT
 REQUIRED BY 11-4.21.6 IS NOT SHOWN, AND
 CURBS ARE INDICATED, WHERE AS SECTION
 11-4.21.7 INDICATES CURBS ARE NOT TO BE
 INSTALLED. - NO BREAK ROOM SINK DETAIL
 OR ELEVATION IS FOUND. -
 DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 THE SHOWER SHALL SHOW A CLEAR FLOOR
 SPACE PER 11-4.21.2. SECTION
 11-4.22.2(1).
 ** **RESPONSE NOTED, BUT THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE BREAK
 ROOM SINK:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 5.OK
 6.OK
 11. OK
  
 12. SHTS A9.2 THRU A9.24 ALL UNITS.
 CLEAR FLOOR SPACE FOR THE WATER CLOSETS
 SHALL BE APPLIED OR SUPERIMPOSED OVER A
 PLAN PER PAGE 7.43 PARAGRAPH ONE.
 ***COMMENT NOT ADDRESSED.
 ****THIS ISSUE HAS NOT BEEN ADDRESSED.
 CLEAR FLOOR SPACE FOR THE LAV & TUB ARE
 SHOWN BUT NOT THE W/C.
 ** **RESPONSE NOTED, BUT A 30"X48" CLEAR
 FLOOR SPACE HAS BEEN SUPERIMPOSED ON THE
 PLANS WHICH DOES NOT REFLECT THE CLEAR
 FLOOR SPACES REQUIRED ON PAGE 7.43.
  
 13. SHTS A9.2 THRU A9.24 PER PAGE 7.7
 MINIMUM CLEARANCES BETWEEN COUNTERS AND
 ALL OPPOSING ELEMENTS IS 40". PLEASE
 INDICATE ON THE PLANS THE MINIMUM
 CLEARANCE FOR ALL KITCHENS.
 ***COMMENT NOT ADDRESSED.
 ****RESPONSE NOTED, BUT THE CLEARANCE
 SHOWN IS NOT THE MINIMUM CLEARANCE. (SEE
 ATTACHED SHEET FROM FHA DESIGN MANUAL).
 ** **RESPONSE NOTED, BUT THIS DOES NOT
 COMPLY WITH THE REQUIREMENT FOR THE
 MINIMUM CLEARANCE.
  
 14. OK
 15. OK
 19. OK
 23. OK
 26. OK
 30. SOK
 31. OK
 32. OK - TO BE A SUBMITTAL
 33. OK
 35. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 **************NEW COMMENTS**************
  
 1B. OK
 2B. OK
 3B. OK
 4B. OK
 5B. OK
 6B. OK
 7B. OK
 8B. OK
 9B. OK
 10B. OK
 11B. OK
 12B. OK
 13B. OK
 14B. OK
 15B. OK
 16B. OK
 17B. OK
 18B. OK
 19B. OK
 20B. OK
 21B. OK
 22B. OK
 23B. OK
 24B. OK
 25B. OK
 26B. OK
 27B. OK
 28B. OK
 29B. OK
 30B. OK
 31B. OK
 32B. OK
 33B. OK
  
 34B. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
 A. OK
 B. OK
 C. OK
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. (EACH SYSTEM).
 ****NOT ADDRESSED.
 ** **RESPONSE NOTED, THE GAS WILL NOT BE
 APPROVED ON THESE PLANS UNTIL ALL
 REQUIREMENTS ARE MET. GAS PLANS CAN BE
 DELETED AND RESUBMITTED AT TIME OF GAS
 APPLICATION.
  
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505. (EACH SYSTEM).
 ****NOT ADDRESSED.
 ** **RESPONSE NOTED, THE GAS WILL NOT BE
 APPROVED ON THESE PLANS UNTIL ALL
 REQUIREMENTS ARE MET. GAS PLANS CAN BE
 DELETED AND RESUBMITTED AT TIME OF GAS
 APPLICATION.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. (EACH
 SYSTEM).
 ****NOT ADDRESSED. ITS UNDERSTOOD THE
 KITCHEN GAS EQUIPMENT WILL BE SUBMITTED
 AT KITCHEN BUILD-OUT, BUT THE POOL
 HEATER SPECIFICATIONS SHEETS WILL BE
 REQUIRED.
 ** **RESPONSE NOTED, THIS ISSUE CAN BE
 TAKEN CARE OF AT THE TIME OF GAS
 APPLICATION.
  
 G. AT TIME OF KITCHEN BUILD OUT
  
 35B. THERE IS ONE SET OF "RED LINED"
 PLANS. PLEASE RETURN THIS SET AND
 COMMENT RESPONSES TO HELP EXPEDITE THE
 NEXT PLAN REVIEW.
 ****COMMENT NOT ADDRESSED.
  
 **************NEW COMMENTS**************
  
 1C. OK
 2C. OK
 3C. OK
  
 4C. EMERGENCY DRAINS FOR THE DECK SHALL
 DRAIN THE TOTAL AREA OF THE DRAIN. SOME
 AREAS HAVE NO EMERGENCY DRAINS, AND ITS
 UNDERSTOOD THAT THOSE AREAS WILL DRAIN
 TO THE EMERGENCY DRAINS SHOWN. THE
 EMERGENCY DRAINS SHALL BE SIZED FOR THE
 TOTAL AREA THAT WILL BE DRAINED FOR EACH
 AREA. PLEASE INDICATE THE TOTAL AREA
 BEING DRAINED FOR EACH EMERGENCY DRAIN
 AND SIZE ED'S ACCORDINGLY. SECTION
 1107.3.
 ** **RESPONSE NOTED, BUT THE AREAS FOR
 MOST EMERGENCY ROOF DRAINS DOES NOT ADD
 UP TO THE SURRONDING AREAS. PLEASE
 RECHECK THE AREAS AND CHECK THE TOTAL
 SQUARE FOOTAGE FOR EACH EMERGNECY DRAIN
 AREA. PLEASE NUMBER EACH EMERGENCY DRAIN
 AND NUMBER AND OUTLINE EACH AREA
 DRAINING TO EACH EMERGENCY DRAIN FOR
 CLARITY. - ALSO RECHECK ALL PIPE SIZES
 AND ROOF DRAIN SIZES AS NOT ALL ARE
 CORRECT. SEE TABLE 1106.3 @ 4.5"/HR
 RAINFALL FOR SECONDARY ROOF DRAINS.
 (EXAMPLE ED 2914 SF ADDS UP TO 2804SF,
 4"RD SHOWN, 5"RD REQUIRED, 6" HORIZONTAL
 PIPE SHOWN, 8" HORIZONTAL PIPE
 REQUIRED).
  
 **************NEW COMMENT**************
  
 1D. SHT A1.18 AREA FROM COL. LINE M TO
 AREA BETWEEN COL'S P & Q FROM COL. 11
 THRU COL. 19 FLOOR PLAN IS MISSING.
 PLEASE RESUBMIT SHEET WILL ALL REQUIRED
 INFORMATION. CHECK TO SEE IF ALL
 INFORMATION IS CORRECT IN THIS AREA.
 SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved