Plan Review Notes
Plan Review Notes For Permit 05091265
Permit Number 05091265
Review Stop G
Sequence Number 4
Notes
Date Text
2008-08-06 14:40:24REVISION DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 *****SEPARATE GAS PERMIT REQUIRED*****
  
 1. SHT P3.16 GAS METER PIPING SCHEMATIC NOT APPROVED. A
 LETTER FROM FLORIDA PUBLIC UTILITIES AUTHORIZING THE
 BYPASS OF THE GAS METER IS REQUIRED AS PROVIDER OF THE
 GAS.
  
 2. SHT P3.1.6 THERE ARE CHANGES TO THE PLANS FROM
 PREVIOUS REVISION, (13), THAT ARE NOT INDICATED WITH A
 CLOUD OR A REVISION NUMBER. PLEASE CLOUD AND NUMBER ALL
 REVISIONS. SECTION 106.1.3.
  
 3. SHT P3.1.6 PIPE SIZING DOWNSTREAM OF THE REGULATOR
 TO THE POOL/SPA BOILERS IS NOT CORRECT PER TABLE
 402.4(2). EACH STUBOUT & VALVE FOR THE POOL BOILERS
 SHALL BE 1". (3/4" IS SHOWN). 1" IS REQUIRED TO THE
 LAST POOL HEATER. (3/4" IS SHOWN). 1-1/4" IS REQUIRED
 TO POOL BOILER #2. (1" IS SHOWN). 1-1/2" IS REQUIRED
 FROM THE REGULATOR TO THE SPA BOILER. (1" IS SHOWN).
 PLEASE SEE RED LINE CORRECTION ON SUBMITTED REVISION.
  
 4. SUBMIT MANUF. SPECIFICATIONS FOR THE POOL/SPA
 BOILERS. INDICATE MODEL NUMBER, LISTING & BTU LOAD FOR
 EACH.
  
 5. SUBMIT MANUF. SPECIFICATIONS FOR THE REGULATORS.
 INDICATE MODEL NUMBER AND SHOW MAX CAPACITY FOR TOTAL
 LOAD OF ALL APPLIANCES COMBINED.
  
 6. SHT P3.1.6 GAS RISER DIAGRAM. UNIONS ARE REQUIRED
 DOWNSTREAM OF THE SHUT OFF VALVE FOR THE GAS
 REGULATORS. PLEASE SHOW ON RISER DIAGRAM.
  
 7. SEE BELOW FOR PROVISO FROM PLANS STAMPED AT TIME OF
 PERMIT FOR THE BUILD COM:
  
 PASSED/PROVISO
  
 MANUF. SPECIFICATION SHEETS REQUIRED AT
 THE TIME OF BUILD-0UT OF KITCHEN, AND AT
 THE TIME OF APPLICATION FOR THE GAS
 PERMIT FOR THE POOL HEATERS. - MANUF. SPECIFICATION
 SHEET ALSO REQUIRED FOR
 THE GAS REGULATORS. INDICATE THE MODEL
 NUMBER FOR REGULATORS. REGULATORS SHALL
 BE LISTED.
  
  
 REVISION REQUIRED FOR SHT P3.16
 INDICATING THE CORRECT INLET PRESSURE
 FROM THE METER, AND SHOWING UNIONS
 DOWNSTREAM OF THE SHUT OFF VALVES FOR
 THE REGULATORS.-PIPE SIZING SHALL BE
 CHECKED WHEN INLET PRESSURE IS
 CLARIFIED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]