| 2008-08-06 14:40:24 | REVISION DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | *****SEPARATE GAS PERMIT REQUIRED***** |
| | |
| | 1. SHT P3.16 GAS METER PIPING SCHEMATIC NOT APPROVED. A |
| | LETTER FROM FLORIDA PUBLIC UTILITIES AUTHORIZING THE |
| | BYPASS OF THE GAS METER IS REQUIRED AS PROVIDER OF THE |
| | GAS. |
| | |
| | 2. SHT P3.1.6 THERE ARE CHANGES TO THE PLANS FROM |
| | PREVIOUS REVISION, (13), THAT ARE NOT INDICATED WITH A |
| | CLOUD OR A REVISION NUMBER. PLEASE CLOUD AND NUMBER ALL |
| | REVISIONS. SECTION 106.1.3. |
| | |
| | 3. SHT P3.1.6 PIPE SIZING DOWNSTREAM OF THE REGULATOR |
| | TO THE POOL/SPA BOILERS IS NOT CORRECT PER TABLE |
| | 402.4(2). EACH STUBOUT & VALVE FOR THE POOL BOILERS |
| | SHALL BE 1". (3/4" IS SHOWN). 1" IS REQUIRED TO THE |
| | LAST POOL HEATER. (3/4" IS SHOWN). 1-1/4" IS REQUIRED |
| | TO POOL BOILER #2. (1" IS SHOWN). 1-1/2" IS REQUIRED |
| | FROM THE REGULATOR TO THE SPA BOILER. (1" IS SHOWN). |
| | PLEASE SEE RED LINE CORRECTION ON SUBMITTED REVISION. |
| | |
| | 4. SUBMIT MANUF. SPECIFICATIONS FOR THE POOL/SPA |
| | BOILERS. INDICATE MODEL NUMBER, LISTING & BTU LOAD FOR |
| | EACH. |
| | |
| | 5. SUBMIT MANUF. SPECIFICATIONS FOR THE REGULATORS. |
| | INDICATE MODEL NUMBER AND SHOW MAX CAPACITY FOR TOTAL |
| | LOAD OF ALL APPLIANCES COMBINED. |
| | |
| | 6. SHT P3.1.6 GAS RISER DIAGRAM. UNIONS ARE REQUIRED |
| | DOWNSTREAM OF THE SHUT OFF VALVE FOR THE GAS |
| | REGULATORS. PLEASE SHOW ON RISER DIAGRAM. |
| | |
| | 7. SEE BELOW FOR PROVISO FROM PLANS STAMPED AT TIME OF |
| | PERMIT FOR THE BUILD COM: |
| | |
| | PASSED/PROVISO |
| | |
| | MANUF. SPECIFICATION SHEETS REQUIRED AT |
| | THE TIME OF BUILD-0UT OF KITCHEN, AND AT |
| | THE TIME OF APPLICATION FOR THE GAS |
| | PERMIT FOR THE POOL HEATERS. - MANUF. SPECIFICATION |
| | SHEET ALSO REQUIRED FOR |
| | THE GAS REGULATORS. INDICATE THE MODEL |
| | NUMBER FOR REGULATORS. REGULATORS SHALL |
| | BE LISTED. |
| | |
| | |
| | REVISION REQUIRED FOR SHT P3.16 |
| | INDICATING THE CORRECT INLET PRESSURE |
| | FROM THE METER, AND SHOWING UNIONS |
| | DOWNSTREAM OF THE SHUT OFF VALVES FOR |
| | THE REGULATORS.-PIPE SIZING SHALL BE |
| | CHECKED WHEN INLET PRESSURE IS |
| | CLARIFIED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |