| 2008-12-17 17:30:56 | REVSIONS DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT P2.31 REVISION 2 ADDENDUM #3 DATED 4-17-06 AS |
| | SHOWN ON THE FILE SET OF PLANS FOR PUBLIC RECORD HAS |
| | BEEN CHANGED TO REVISION 4. ALL REVISIONS SHALL BE |
| | INDICATED ON THE REVISION INDEX FOR THE LIFE OF THE |
| | PROJECT. NEW REVISIONS SHALL BE INDICATED WITH CLOUDS |
| | AND A NEW REVISION NUMBER. SECTION 106.1.3. |
| | |
| | 2. SHT P3.10 THE DRAIN LINE FROM THE THERMAL EXPANSION |
| | VALVE IS SHOWN CONNECTING DIRECTLY TO THE PAN DRAIN |
| | LINE. PER SECTION 608.1 POTABLE WATER SHALL BE |
| | DESIGNED, INSTALLED, INSTALLED AND MAINTAINED TO |
| | PREVENT CONTAMINATION FROM NONPOTABLE LIQUIDS, SOLIDS |
| | OR GASES BEING INTRODUCED INTO THE POTABLE WATER SUPPLY |
| | THROUGH CROSS-CONNECTIONS. AN AIR GAP OR AIR GAP |
| | FITTING IS REQUIRED. TABLE 608.1. -- KEY NOTES #5 SHOWS |
| | NOT CHANGE & KEY NOTE #7 HAS BEEN ADDED WITHOUT A CLOUD |
| | TO INDICATE A REVISION NOR A REVISION NUMBER. PLEASE |
| | CLOUD AND NUMBER ALL REVISIONS. SECTION 106.1.3. |
| | |
| | 3. SHT P3.11 THE DRAIN LINE FROM THE THERMAL EXPANSION |
| | VALVE IS SHOWN CONNECTING DIRECTLY TO THE PAN DRAIN |
| | LINE. PER SECTION 608.1 POTABLE WATER SHALL BE |
| | DESIGNED, INSTALLED, INSTALLED AND MAINTAINED TO |
| | PREVENT CONTAMINATION FROM NONPOTABLE LIQUIDS, SOLIDS |
| | OR GASES BEING INTRODUCED INTO THE POTABLE WATER SUPPLY |
| | THROUGH CROSS-CONNECTIONS. AN AIR GAP OR AIR GAP |
| | FITTING IS REQUIRED. TABLE 608.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |