2007-09-14 15:19:56CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: DENIED
  
 SUBMITTAL NO: 15-400-011 PRO-SLOPE
 1) PLEASE PROVIDE PRODUCT TESTING INFORMATION FROM A
 NATIONAL RECONIZED TESTING AGENCY IN REGARDS TO
 COMBUSTIBLITY OF THIS COMPOSITE MATERIAL.
 .717.5 COMBUSTIBLES IN CONCEALED SPACES IN TYPE I OR
 II CONSTRUCTION. COMBUSTIBLES SHALL NOT BE PERMITTED IN
 CONCEALED SPACES OF BUILDINGS OF TYPE I OR II
 CONSTRUCTION.
  
 PROVIDE INFORMATION ON THE COMBUSTIBILITY OF THIS
 PRODUCT.703.4 NONCOMBUSTIBILITY TESTS.
  
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2 , 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 SHALL
 BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS.
  
 2) PLEASE ALSO PROVIDE TESTING INFORMATION AS TO THE
 DENSITY OF THIS POLYSTYRENE.
  
 3) 2603.2 LABELING AND IDENTIFICATION.
 PACKAGES AND CONTAINERS OF FOAM PLASTIC INSULATION AND
 FOAM PLASTIC INSULATION COMPONENTS DELIVERED TO THE JOB
 SITE SHALL BEAR THE LABEL OF AN APPROVED AGENCY SHOWING
 THE MANUFACTURER?S NAME, THE PRODUCT LISTING, PRODUCT
 IDENTIFICATION AND INFORMATION SUFFICIENT TO DETERMINE
 THAT THE END USE WILL COMPLY WITH THE CODE
 REQUIREMENTS.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  