| 2007-09-14 15:19:56 | CITY PALMS SUBMITALS/ REVISIONS |
| | PERMIT:05091265 |
| | ADDRESS: 480 HIBISCUS |
| | |
| | ACTION: DENIED |
| | |
| | SUBMITTAL NO: 15-400-011 PRO-SLOPE |
| | 1) PLEASE PROVIDE PRODUCT TESTING INFORMATION FROM A |
| | NATIONAL RECONIZED TESTING AGENCY IN REGARDS TO |
| | COMBUSTIBLITY OF THIS COMPOSITE MATERIAL. |
| | .717.5 COMBUSTIBLES IN CONCEALED SPACES IN TYPE I OR |
| | II CONSTRUCTION. COMBUSTIBLES SHALL NOT BE PERMITTED IN |
| | CONCEALED SPACES OF BUILDINGS OF TYPE I OR II |
| | CONSTRUCTION. |
| | |
| | PROVIDE INFORMATION ON THE COMBUSTIBILITY OF THIS |
| | PRODUCT.703.4 NONCOMBUSTIBILITY TESTS. |
| | |
| | THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2 |
| | SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING |
| | MATERIALS AS SET FORTH IN SECTIONS 602.2 , 602.3 AND |
| | 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM |
| | ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD |
| | CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A |
| | MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE |
| | BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN |
| | INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE |
| | LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF |
| | AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS. |
| | |
| | 703.4.1 ELEMENTARY MATERIALS. |
| | MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED |
| | IN ACCORDANCE WITH ASTM E 136. |
| | |
| | 703.4.2 COMPOSITE MATERIALS. |
| | MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE |
| | MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18 |
| | MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER |
| | THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 SHALL |
| | BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS. |
| | |
| | 2) PLEASE ALSO PROVIDE TESTING INFORMATION AS TO THE |
| | DENSITY OF THIS POLYSTYRENE. |
| | |
| | 3) 2603.2 LABELING AND IDENTIFICATION. |
| | PACKAGES AND CONTAINERS OF FOAM PLASTIC INSULATION AND |
| | FOAM PLASTIC INSULATION COMPONENTS DELIVERED TO THE JOB |
| | SITE SHALL BEAR THE LABEL OF AN APPROVED AGENCY SHOWING |
| | THE MANUFACTURER?S NAME, THE PRODUCT LISTING, PRODUCT |
| | IDENTIFICATION AND INFORMATION SUFFICIENT TO DETERMINE |
| | THAT THE END USE WILL COMPLY WITH THE CODE |
| | REQUIREMENTS. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |